String Mapping 

– Explanation 

Below are the different parts that can be modified to make up a string mapping. 

String data types can only be mapped to other string data types. There is no manipulation that can be 
done on the string. 

 

1)

 

Enable 

(red box above):

 Check to enable mapping. If not checked, this mapping is skipped. 

2)

 

Source Field

 

(yellow box above): 

a)

 

Group - Select the string data group you set up in the protocol config to use for this mapping.   

b)

 

String - This is the string used for this mapping. 

3)

 

Destination Field

 

(green box above)

a)

 

Group - Select the string data group you set up in the protocol config to use for this mapping.   

b)

 

String - This is the string where the data is being stored. 

Содержание 460MSBC-NNA1

Страница 1: ...Real Time Automation Inc 1 1 800 249 1612 Firmware Version 8 7 22 460MSBC NNA1 Protocol Gateway Product User Guide...

Страница 2: ...ion or limitation of incidental or consequential damages therefore the limitations set forth in this agreement may not apply to you No patent liability is assumed by Real Time Automation with respect...

Страница 3: ...evice vs Auto Configure Group by Data Type 18 Group by Device Default Method 18 Group by Data Type 18 Modbus TCP IP Server Data Group Configuration Auto Configure 19 Modbus TCP IP Server Data Group Co...

Страница 4: ...curity Log In 46 Security Log Out 46 Email Configuration 47 Alarm Configuration 48 Diagnostics Alarm Status 50 Alarms Active 50 Alarms Clear 51 Change of State COS Configuration 52 Diagnostics Info 53...

Страница 5: ...7 4 9 1 20 Features Added 1 BMS BM DFM DS DM TCP USB PBS have been ported to the latest base software 2 TCP BMS BM now Available on N2E and N2EW hardware Platform 3 New ASCII Mode Available on TCP A U...

Страница 6: ...nfigure the 460MSBC NNA1 gateway For further customization and advanced use please reference the appendices located on the CD or online at http www rtautomation com product 460 gateway support If at a...

Страница 7: ...h as LEDs For these sections be sure to identify the hardware platform you are using To find which hardware platform you are using 1 Look on the front or back label of the unit for the part number 2 O...

Страница 8: ...Real Time Automation Inc 8 1 800 249 1612 Hardware NNA1 Powering the Gateway 1 Connect a 12 24 VDC power source to the gateway Red Wire Black Wire a The unit draws 175mA 12 V...

Страница 9: ...under the DIN Rail 3 While pressing the 460MSBC NNA1 against the rail press up to engage the spring loaded lower clip and rotate the unit parallel to the DIN Rail 4 Release upward pressure Removing F...

Страница 10: ...ogram from the CD ROM 3 Find unit under Select a Unit a Change Gateway s IP address to match that of your PC if DHCP has failed i You will know DHCP has failed if the gateway s IP address is AutoIP at...

Страница 11: ...fault Gateway 2 The gateway must be on the same Network Subnet as the PC whether it s setup for DHCP or Static Once you have both devices on the same network you should be able to ping the gateway usi...

Страница 12: ...ed after every change Multiple changes can be made before a restart but they will not be committed until the gateway is restarted When all desired changes have been made press the Restart Now button T...

Страница 13: ...led Configuration cannot be changed during Running Mode If changes are needed click the Configuration Mode button shown in the green box below Configuring Mode Protocol communication is stopped and no...

Страница 14: ...ice Configuration The device configuration area is where you assign the device description parameter Changes can only be made when the gateway is in Configuration Mode Once you are done configuring th...

Страница 15: ...Once you are done configuring the Network Settings click the Save Parameters button If you are changing the IP Address of the gateway the change will not take effect until the unit has been rebooted...

Страница 16: ...listen on Default for Modbus TCP IP is 502 4 Inactivity Timeout Amount of time the gateway will wait for a read write request before issuing a timeout 5 To enable data swapping select the required Sw...

Страница 17: ...gure up to 100 data groups for both the read and write There are three ways to configure this protocol 1 Auto Configure Group by Device Default 2 Auto Configure Group by Data Type 3 Manual Mode NOTE Y...

Страница 18: ...other protocol on the gateway and auto configures the data groups in the Modbus TCP IP server for all the data points within the other protocol Another way to view this option is to say that the data...

Страница 19: ...whenever possible 4 Any 64 Bit Signed Unsigned data will be mapped as 4x Hold Reg 64 Bit Int or 64 Bit Uint matching signs whenever possible 5 Any 32 Bit Float will be mapped as 4x Hold Reg 32 Bit Fl...

Страница 20: ...Once OK is clicked there are two options for how to proceed 3 To keep the data groups that are already configured press OK a You would want this option if you are adding additional data groups or you...

Страница 21: ...them a String Point Type If the mating protocol supports strings you may select string as a point type in Modbus With this point type 2 characters will be packed into a single register and the first...

Страница 22: ...on Default is 47808 0xBAC0 4 Enter a unique Instance identifier for the gateway This Instance must be unique on the BACnet IP network 5 Enter a Name Description and Location for the gateway These are...

Страница 23: ...rver button d Click the Save Parameters button to save all changes made before you restart or go to another configuration page 2 The Enable check box should be selected for the device 3 Enter a Device...

Страница 24: ...cterString Value 3 Enter a Starting Object 4 Enter the of consecutive objects to read for that object type You can enter a value of 1 to 128 Configuring Writes Scan Lines Follow these steps to manuall...

Страница 25: ...eway will automatically take the string data type from one protocol and map it into the other See String Auto Configure section for more details Option 3 Manual Configure Mappings If you don t want to...

Страница 26: ...isplay Data button to view how the data is mapped and what the values of each mapping are Here you will see how each data point excluding strings is mapped To view select the device from the dropdown...

Страница 27: ...3 on BACnet NOTE If a data point is mapped twice only the first instance of it will show here EX If Modbus 400001 400040 from Slave 1 are both mapped to AI1 only 400001 will show as being mapped to AI...

Страница 28: ...iew the actual data mappings click the Edit Mapping button For more details see the Data Mapping Explanation section To view the data mappings purely as text click the View as Text button For more det...

Страница 29: ...ps from a string click the dropdown menu to generate the information regarding that device The string data will be displayed in both Hex and ASCII only the ASCII data is sent The example below shows d...

Страница 30: ...Info drop down and navigating to ASCII Diagnostics page You will also have to select the port you want to view in the dropdown below ASCII To view the string mappings click the Edit Mapping button Fo...

Страница 31: ...on would look like my example below There are more detailed examples of what all the fields represent in the ASCII Parsing section The message is broken up into 3 Groups or Parsing fields To view the...

Страница 32: ...ata type If the Auto Configure function does not map the data as you want or you want to add modify the mappings you may do so by going into Manual Configure mode The following are examples of the Aut...

Страница 33: ...then only 1 operation is allowed c Select the Operation s to perform i Math Operations are performed in the order they are selected ii If more than one point is selected on the source the Math Operat...

Страница 34: ...ase In this example Ram0 is scaled into Ram1 Ram1 is then increased by 5 and stored into Ram2 Ram0 and Ram2 could be considered a source or destination group 2 Temporary Ram Double a This is like the...

Страница 35: ...ys to map the NetBmpStat Option 1 Map the whole 32bit value to a destination Example below shows the NetBmpStat is going to an Analog BACnet object Using a connection of 5 Modbus Slave devices AI1 wil...

Страница 36: ...ult 0x80 7 128 nonrecoverable fault For this example the ETC Status is mapped to a PLC tag called PLC_Status Example ETC Status is 0x00000013 19 decimal here is the break down Hex Bit Decimal Explanat...

Страница 37: ...e fault config err 0x10 28 268 435 456 Configuration Mode 0x20 29 536 870 912 No Ethernet Cable Plugged In For this example the MC Status is mapped to a PLC tag called MC_Status Example MC Status is 0...

Страница 38: ...string 1 Enable red box above Check to enable mapping If not checked this mapping is skipped 2 Source Field yellow box above a Group Select the string data group you set up in the protocol config to...

Страница 39: ...ual Configure Mode or click Cancel to remain in Auto Configure Mappings Mode Once OK is clicked there are 2 options on how to proceed from here 1 To keep the mappings that are already configured press...

Страница 40: ...op of the Mapping Configuration page and select Auto Configure Mappings Click OK to proceed to delete all current mappings and go back to Auto Configure Mappings Mode Click Cancel to keep all mappings...

Страница 41: ...at register 1 and want to see if 400011 is mapped If it is not in this text box then it is not mapped and no data will be transferred This is the text display for the example shown under the Data Mapp...

Страница 42: ...ake value is set equal to Trigger value 5 Map Handshake to reference data point Note is an internal reference to the Server Slave number you are settings up ex RTA Server Slave products can only be Tr...

Страница 43: ...ppings 4 The first mapping is going to be the Data Validation Triggering AO21 will write to the RTA MC Trigger 1 will mark data invalid 5 The second mapping the MC Handshake will increment that all da...

Страница 44: ...ax of 32 characters case sensitive a Re enter the Password 4 E mail In case the password was forgotten a user can have their password e mailed to them if e mail was configured 5 Hint A helpful reminde...

Страница 45: ...can have a separate security level associated with it for each user Security Levels 1 Full Access Capability to view and configure a web page 2 View Access Capability to view a web page but cannot co...

Страница 46: ...word This is used to reset security settings Confirm reset password must be selected to confirm this action Once confirmed there is a 15 minute window to do a hard reset of the gateway by physically r...

Страница 47: ...use 2 SMTP Mail Password If authentication is required enter the SMTP Server s password Optional 3 SMTP Server Enter the Name of the SMTP Server or the IP Address of the Server 4 From E mail Enter th...

Страница 48: ...ction a Top dropdown select the Data Group This dropdown menu will contain all groups that go from the gateway to the network b Lower dropdown select the Data Point s Specific Point This is used to se...

Страница 49: ...he Clear Error Value Ex Ticks Since Powerup 5000 This will clear the alarm after 5000 ticks have elapsed since the unit powered up 6 Enter an Alarm Name This will make the alarm unique and will be ava...

Страница 50: ...m 7 Status The current status of the alarm either OK or ALARM 8 of Times Active This count represents the number of times this alarm has become active If an alarm is triggered this count will incremen...

Страница 51: ...hen an alarm is cleared the following will occur 1 A one time notification will be sent to the email associated with the alarm a For duplicate emails to occur the alarm must become active and then be...

Страница 52: ...his is to be used to prevent jitter Default value is 0ms This timer takes priority over the Stale Data Timer There is a separate timer per data mapping This timer is active only after the first write...

Страница 53: ...larm that was active Common Errors 1 Destination or Source Point does not exist a Solution Re map the mapping 2 Source or Destination Pointer too small a There is not enough space on either the Source...

Страница 54: ...dbus TCP IP Server section of the gateway Device Status 1 Connected A Modbus TCP IP client has a connection for the gateway 2 Not Connected a Ethernet Cable not plugged in b The Modbus TCP IP client h...

Страница 55: ...e Register Modbus Function Code 6 Number of Write Holding Register requests received 7 FC15 Force Multiple Coils Modbus Function Code 15 Number of Write Multiple Coil Status requests received 8 FC16 P...

Страница 56: ...down and clicking View Additional diagnostic information can be found by clicking the Help button NOTE This page will auto refresh every five seconds with the latest data Clear All Values This will on...

Страница 57: ...Real Time Automation Inc 57 1 800 249 1612 Device Status This will only display when viewing All Servers...

Страница 58: ...IP server that is configured and enabled a Verify BACnet IP settings and ensure that the Enable checkbox is checked for the appropriate device s b Verify the Enable checkbox is checked for the appropr...

Страница 59: ...Single RD Multiple WR Multiple Variable Counts 7 RD WR Response Error Number of read or write error responses received a NOTE If the gateway receives an error of Unsupported Service for a RPM or WPM...

Страница 60: ...ateway tried to access a property the server does not support for that object type g Unsupported Object Type The gateway tried to access an object type the server does not support h Value out of range...

Страница 61: ...col is a master client you may set the LED to represent either all slaves servers configured in the gateway or a slave server device To select a slave server device 1 Select the protocol in the left d...

Страница 62: ...her device into the 460 gateway whenever it is in Configuration Mode Upon clicking the Choose File button you will be prompted to select a location from which to load the saved file Once the location...

Страница 63: ...tered an error while trying to load the saved configuration the gateway will indicate the first error it found and a brief description about it under the Load Configuration button Contact RTA Support...

Страница 64: ...y you wish to copy the configuration from 2 Power up the gateway you wish to copy the configuration to DO NOT INSERT SD CARD YET 3 Navigate to the webpage inside the unit 4 Navigate to the dropdown Ot...

Страница 65: ...on the hardware 1 On the side of the gateway with the SD card slot there is a small pinhole Using a paperclip press the button through this pinhole and hold the button for at least 5 seconds 2 After...

Страница 66: ...tored in the Flash File System within the gateway Identify your device by clicking the Start Flashing LEDs button By clicking this button the two diagnostic LEDs will flash red and green Once you have...

Отзывы: