Mapping 

– Auto-Configure Mode to Manual Configure Mode 

To transition from Auto-Configure Mapping Mode to Manual Configure Mode, click the dropdown at the 
top of the Mapping Configuration page and select Manual Configure.  

After you click this button, you will be prompted to confirm if this is really what you want to do.   

 

Click 

OK

 to proceed to Manual Configure Mode or click 

Cancel

 to remain in Auto-Configure Mappings 

Mode.   

Once OK is clicked, there are 2 options on how to proceed from here.  

 

1)

 

To keep the mappings that are already configured press 

OK

a.

 

You would want this option if you are adding additional mappings or you want to modify 
the mapping(s) that already exist. 

2)

 

To delete the mappings that are already there and start over press 

Cancel

To modify the number of mappings, enter a number next to 

# of Mappings to Configure

 and click the 

Set Max # of Mappings

 button. You can always add more mappings if needed. 

Содержание 460ESBM-N34

Страница 1: ...Real Time Automation Inc 1 1 800 249 1612 Software Build Date June 7 2016 Firmware Version 5 460ESBM N34 Protocol Gateway Product User Guide...

Страница 2: ...ion or limitation of incidental or consequential damages therefore the limitations set forth in this agreement may not apply to you No patent liability is assumed by Real Time Automation with respect...

Страница 3: ...8 EtherNet IP Adapter Data Group Configuration Manual Mode 19 EtherNet IP Adapter Data Group Configuration Using Strings 20 EtherNet IP Adapter Data Group Configuration Connection Parameters 21 Settin...

Страница 4: ...arm Configuration 43 Diagnostics Alarm Status 45 Alarms Active 45 Alarms Clear 46 Change of State COS Configuration 47 Diagnostics Info 48 Diagnostics Data and String Mapping 48 Diagnostics EtherNet I...

Страница 5: ...onfigure the 460ESBM gateway For further customization and advanced use please reference the appendices located on the CD or online at http www rtaautomation com product 460 gateway support If at any...

Страница 6: ...h as LEDs For these sections be sure to identify the hardware platform you are using To find which hardware platform you are using 1 Look on the front or back label of the unit for the part number 2 O...

Страница 7: ...Real Time Automation Inc 7 1 800 249 1612 Hardware N34...

Страница 8: ...WARNING EXPLOSION HAZARD Substitution of components may impair suitability for Class I Division 2 THIS EQUIPMENT IS AN OPEN TYPE DEVICE AND IS MEANT TO BE INSTALLED IN AN ENCLOSURE SUITABLE FOR THE E...

Страница 9: ...ettings of the device s that you are connecting to When you have completed your port configuration click the Save Parameters button The default jumper configurations are setup for the following serial...

Страница 10: ...to match that of your PC if DHCP has failed i You will know DHCP has failed if the gateway s IP address is AutoIP at 169 254 X Y ii If successful it will say DHCP d at ex 192 168 0 100 or however you...

Страница 11: ...fault Gateway 2 The gateway must be on the same Network Subnet as the PC whether it s setup for DHCP or Static Once you have both devices on the same network you should be able to ping the gateway usi...

Страница 12: ...s can be made before a restart but they will not be committed until the gateway is restarted When all desired changes have been made press the Restart Now button The webpage will redirect to our reboo...

Страница 13: ...led Configuration cannot be changed during Running Mode If changes are needed click the Configuration Mode button shown in the green box below Configuring Mode Protocol communication is stopped and no...

Страница 14: ...o make these changes Once you are done configuring the Description and the Network Settings click the Save Parameters button If you are changing the IP Address of the gateway the change will not take...

Страница 15: ...Time Automation Inc 15 1 800 249 1612 EtherNet IP Adapter Configuration Click the EIP Adapter button to access the configuration page 1 Device Label Enter a label to identify the device within the gat...

Страница 16: ...per group 2 Data Format sets the formatting of the data Automap will use this packing size to map data to from the other protocol There are three ways to configure this protocol Auto Configure Group b...

Страница 17: ...t Signed Unsigned data will be mapped as 64 Bit Int or 64 Bit Uint matching signs whenever possible Any 32 Bit Float will be mapped as 32 Bit Float Any 64 Bit Float will be mapped as 64 Bit Float Any...

Страница 18: ...mized there could potentially be a lot of wasted unused data space but it will be organized more logically from the Master Client s point of view Group by Data Type Group by Data Type goes through the...

Страница 19: ...on if you are adding additional data groups or you want to modify the data group s that already exist ii To delete the data groups that are already there and start over press Cancel 2 Enter the number...

Страница 20: ...ngth Each String may have 99 characters When using 1 String use Input Assembly 101 Output Assembly 113 where Byte 0 would be the length and Byte 1 99 would contain the data When using 2 Strings use In...

Страница 21: ...he instances and sizes next to the connection for information on how to connect to an EtherNet IP Scanner Client To establish communications with the above settings configure the EtherNet IP Scanner C...

Страница 22: ...ection Parameters must match exactly NOTE The Connection Parameters table indicates how many bytes to use for the assembly instance If you are using a Data Format that is not type 8 Bit Int Uint this...

Страница 23: ...ll communicate with on the BACnet MS TP network This value should be equal to or greater than the largest MAC ID on the MS TP Network The gateway cannot communicate with any MAC ID that is greater tha...

Страница 24: ...itional changes needed to that new slave 2 The Enable check box should be selected for the device 3 Enter a Device Label to identify the device within the gateway 4 Enter the unique Instance that matc...

Страница 25: ...type You can enter a value of 1 to 128 Configuring Writes Scan Lines Follow these steps to manually configure Write Scan Lines 1 Select View Write Scan Lines if not already selected 2 Select an Objec...

Страница 26: ...e details Option 2 String Auto Configure The gateway will automatically take the string data type from one protocol and map it into the other See String Auto Configure section for more details Option...

Страница 27: ...tocol 1 to Protocol 2 or Protocol 2 to Protocol 1 button correlating to the direction you wish to see the data This page is very useful when verifying that all data is mapped somehow from one protocol...

Страница 28: ...m Modbus registers 400001 400005 and therefore can pass the data on to the PLC tag called MC2PLC_INT The 460 gateway has NOT received valid responses from Modbus register 400011 400012 As a result the...

Страница 29: ...ex and ASCII If there are values of Data Not Valid on this page it indicates that the source has not been validated yet and no data is being sent to the destination In the example below this page refl...

Страница 30: ...r data type If the Auto Configure function does not map the data as you want or you want to add modify the mappings you may do so by going into Manual Configure mode The following are examples of the...

Страница 31: ...then only 1 operation is allowed c Select the Operation s to perform i Math Operations are performed in the order they are selected ii If more than one point is selected on the source the Math Operati...

Страница 32: ...except manipulations will be conducted against the 64bit floating point to allow for large data 3 Ticks Per Second a The gateway operates at 200 ticks per second This equates to one tick every 5ms Th...

Страница 33: ...ult 0x80 7 128 nonrecoverable fault For this example the ETC Status is mapped to a PLC tag called PLC_Status Example ETC Status is 0x00000013 19 decimal here is the break down Hex Bit Decimal Explanat...

Страница 34: ...e fault config err 0x10 28 268 435 456 Configuration Mode 0x20 29 536 870 912 No Ethernet Cable Plugged In For this example the MC Status is mapped to a PLC tag called MC_Status Example MC Status is 0...

Страница 35: ...string 1 Enable red box above Check to enable mapping If not checked this mapping is skipped 2 Source Field yellow box above a Group Select the string data group you set up in the protocol config to...

Страница 36: ...ed to Manual Configure Mode or click Cancel to remain in Auto Configure Mappings Mode Once OK is clicked there are 2 options on how to proceed from here 1 To keep the mappings that are already configu...

Страница 37: ...of the Mapping Configuration page and select Auto Configure Mappings Click OK to proceed to delete all current mappings and go back to Auto Configure Mappings Mode Click Cancel to keep all mappings an...

Страница 38: ...at register 1 and want to see if 400011 is mapped If it is not in this text box then it is not mapped and no data will be transferred This is the text display for the example shown under the Data Mapp...

Страница 39: ...ax of 32 characters case sensitive a Re enter the Password 4 E mail In case the password was forgotten a user can have their password e mailed to them if e mail was configured 5 Hint A helpful reminde...

Страница 40: ...can have a separate security level associated with it for each user Security Levels 1 Full Access Capability to view and configure a web page 2 View Access Capability to view a web page but cannot co...

Страница 41: ...word This is used to reset security settings Confirm reset password must be selected to confirm this action Once confirmed there is a 15 minute window to do a hard reset of the gateway by physically r...

Страница 42: ...use 2 SMTP Mail Password If authentication is required enter the SMTP Server s password Optional 3 SMTP Server Enter the Name of the SMTP Server or the IP Address of the Server 4 From E mail Enter th...

Страница 43: ...ction a Top dropdown select the Data Group This dropdown menu will contain all groups that go from the gateway to the network b Lower dropdown select the Data Point s Specific Point This is used to se...

Страница 44: ...he Clear Error Value Ex Ticks Since Powerup 5000 This will clear the alarm after 5000 ticks have elapsed since the unit powered up 6 Enter an Alarm Name This will make the alarm unique and will be ava...

Страница 45: ...either OK or ALARM 8 of Times Active This count represents the number of times this alarm has become active If an alarm is triggered this count will increment Alarms Active While one or more alarms a...

Страница 46: ...occur 1 A one time notification will be sent to the email associated with the alarm a For duplicate emails to occur the alarm must become active and then be cleared again 2 Total Alarms Active will d...

Страница 47: ...his is to be used to prevent jitter Default value is 0ms This timer takes priority over the Stale Data Timer There is a separate timer per data mapping This timer is active only after the first write...

Страница 48: ...t are enabled Error The number of mappings that are enabled that have an error First Error This is a detailed description of the first mapping that has an error Common Errors 1 Destination or Source P...

Страница 49: ...urn all values displayed to 0 and clear the status string 2 If Viewing EtherNet IP Adapter this will only clear the values for the EtherNet IP Adapter section of the gateway Device Status 1 Connected...

Страница 50: ...I O Output Msgs Received a Number of Messages received from the Scanner b Note Sum of all connections 4 I O Heartbeat Msgs Sent a Number of Heartbeat Messages sent to the Scanner Used with Output Only...

Страница 51: ...Owner Output Only connection that is already established 3 Connection size mismatch a Connection Input Output Size set up in the Scanner does not match what is in the gateway 4 Connection unconfigure...

Страница 52: ...ice This will reduce the overall values indirectly Device Status This will only display when viewing All Slaves 1 Connected The gateway is connected to all of the BACnet MS TP Slaves that are enabled...

Страница 53: ...BACnet MS TP Slave is valid and is not a duplicate on the network b Verify that there are valid scan lines configured for each Slave that is enabled 5 Flashing Red Dependency Error The dependent prot...

Страница 54: ...hat the gateway attempted to Read 10 of Object Write Attempts Total number of objects that the gateway attempted to Write Status Strings These are the values for All Slaves or the specific Slave selec...

Страница 55: ...The gateway tried to write a priority that was out of range or reserved Priority 6 and was rejected ii The gateway tried to write an array for an object or property that doesn t have an array index k...

Страница 56: ...otocol 2 If either Protocol is a Master Client you may set the LED to represent either all Slaves Servers configured in the gateway or a particular Slave Server device To select a particular Slave Ser...

Страница 57: ...onfiguration file or a configuration file from another device into the 460 gateway whenever it is in Configuration Mode Upon clicking the Choose File button you will be prompted to select a location f...

Страница 58: ...m gateway you wish to copy the configuration from 2 Power up the gateway you wish to copy the configuration to DO NOT INSERT SD CARD YET 3 Navigate to the webpage inside the unit 4 Navigate to the dro...

Страница 59: ...red in the Flash File System within the gateway Identify your device by clicking the Start Flashing LED s button By clicking this button the two diagnostic LED s will flash red and green Once you have...

Отзывы: