Real Time Automation, Inc.
67
1-800-249-1612
Variables:
1)
Total Msg Request Count
–
Total number of messages received from the BACnet/IP client.
2)
Read Property Request Received
–
Number of Read Property requests received from the BACnet/IP
client.
3)
Read Multiple Property Request Received
–
Number of Read Property Multiple requests received
from the BACnet/IP client.
4)
Write Property Request Received
–
Number of Write Property requests received from the BACnet/IP
client.
5)
Write Property Multiple Request Received
–
Number of Write Property Multiple requests received
from the BACnet/IP client.
6)
Total Msg Response Count
–
Total number of messages sent to the BACnet/IP client.
7)
Read Property Response Sent
–
Number of Read Property Responses sent to the BACnet/IP client.
8)
Read Multiple Property Response Sent
–
Number of Read Property Multiple responses sent to the
BACnet/IP client.
9)
Write Property Response Sent
–
Number of Write Property responses sent to the BACnet/IP client.
10)
Write Multiple Property Response Sent
–
Number of Write Property Multiple responses sent to the
BACnet/IP client.
11)
Error Response Count
–
Total number of read/write errors received.
12)
Timeout Response Count
–
Total number of read/write timeouts.
13)
COV Success Count
–
Total number of successful COV messages.
14)
COV Error Count
–
Total number of COV error messages.
Common Error Strings:
1)
BS: UNHANDLED_MSG_TYPE
–
The gateway received a BACnet/IP message that it doesn’t know how
to process.
2)
BS: Message Abort - The gateway aborted a message due to one of the common reasons below:
Содержание 460BSUS-NNA1
Страница 19: ...Real Time Automation Inc 19 1 800 249 1612 ...
Страница 34: ...Real Time Automation Inc 34 1 800 249 1612 ...
Страница 36: ...Real Time Automation Inc 36 1 800 249 1612 ...