5/22   Rev. E 171551

7

IMPORTANT 

•  Confirm that the ambient temperatures are within the tolerances allowed.

•  Do not locate next to heat generating devices.

•  Confirm the unit is level.

•  Do not use an extension cord to connect the unit to power. Use of an extension cord will void all warranties.

•  Do not tamper with the ground pin on the power cord.

•  Confirm that the power receptacle has a properly wired ground connection.

•  The unit must be isolated on a power circuit. 

•  Confirm the power supply matches the require power supply noted on the serial plate.

START-UP AND OPERATION

Once the set-up and installations requirements are complete the Capsule Pak ECO is ready to start-up. Once 

the power cord is connected to a live power outlet and the power switch on the unit is in the on position the unit 

will start running. The display will light up immediately but the unit may not start running for 1 minute. On a Low 

Temperature Capsule Pak ECO the evaporator fans will not run until the evaporator coil has pulled down to 40°F.

Allow the unit to run for a minimum of two (2) hours and verify the walk-in is down to temperature prior to loading 

with product. 

TEMPERATURE CONTROL

Note: It is the installing contractors responsibility to check the operation upon start-up and make any 

necessary temperature adjustments as required for proper operation.

Capsule Pak ECO systems come equipped with an electronic control. The temperature control display and user 

interface are located on the side of the system. The control comes pre-set to give walk-in air temperatures of 

approximately 37°F for coolers and -10°F for freezers. Refer to the accompanying electronic control manual for 

detailed instructions on adjusting the control parameters.

On dual compressor systems, there is a programmed delay from the start of the first compressor and the second 

to reduce the start-up power surge on the power supply.

COOLER OPERATION

There is a programmed one-minute delay to start the system upon start-up. As noted, coolers come set at 37°F.  

The control will shut the cooling off when it reaches the set temperature and re-start when the set temperature 

plus the set differential (4) are reached. There is a minimum set point for the control of 30°F and a maximum set 

point of 55°F. The control is pre-set to have a timed off cycle defrost every 6 hours. The defrost duration is 20 

minutes. The evaporator fans will operate at high speed when the compressors are running and low speed when 

the compressors are off.

FREEZER OPERATION

There is a programmed one-minute delay to start the system upon start-up. As noted, freezers come set at -10°F.  

The control will shut the cooling off when it reaches this temperature and re-start when the set temperature plus the 

set differential (5) are reached. There is a minimum set point of -20°F and a maximum set point of 10°F. The control 

is pre-set to have a timed electric defrost cycles every 6 hours. The maximum defrost duration is 30 minutes.  

The defrost is terminated by evaporator temperature first or time if the coil does not teach the temperature. The 

evaporator fans are off during defrost and start when the evaporator reaches 40°F. After defrost the evaporator 

fans will operate at high speed when the compressors are running and low speed when the compressors are off.

General Installation Instructions

Содержание CAPSULE PAK ECO

Страница 1: ...5 22 Rev E 171551 CAPSULE PAK ECO REFRIGERATION SYSTEMS INSTALLATION MANUAL ...

Страница 2: ...spection 3 Safety Information 3 General Installation Instructions 5 8 Set Up and Installation 6 Start Up and Operation 7 Temperature Control 7 Cooler Operation 7 Freezer Operation 7 Condensate Water 8 Loading Product 8 Locating and Mounting Condensing Units 8 Maintenance 9 Maintenance Analysis 10 ...

Страница 3: ...oncealed damage claim Please remember the carrier is your only source for reclaiming freight damages The manufacturer should not be contacted to attempt a return of the product No returns are accepted without a prior authorization SAFETY INFORMATION This manual may contain notices that identify situations that could cause death serious injury and or damage to the appliance or property Please make ...

Страница 4: ...rvision or instruction concerning its use by a person responsible for their safety Do not climb stand or hang on or into the appliance or its components Death or serious injury could occur or the appliance could be damaged Use caution when opening doors or lids and keep fingers out of pinch points areas Do not use combustible sprays or aerosols around the appliance as they may catch fire Do not st...

Страница 5: ...nsideration should be given to accessibility for service Capsule Pak ECO systems are designed for indoor applications only and should be operated in the controlled environment of an air conditioned space The ambient conditions should be at or below 75 F and 55 RH Higher humidity may result in condensate issues If multiple units are located in the same area be sure they do not exhaust hot air into ...

Страница 6: ...tion of air and improve the efficiency of the Capsule Pak ECO SET UP AND INSTALLATION CEILING MOUNTED SELF CONTAINED CAPSULE PAK ECO REFRIGERATION SYSTEM CAUTION This unit uses a flammable refrigerant Use care when handling and operating to avoid damaging the refrigerant tubing or increasing the risk of a leak WARNING This appliance must be installed in accordance with all applicable national stat...

Страница 7: ...ximately 37 F for coolers and 10 F for freezers Refer to the accompanying electronic control manual for detailed instructions on adjusting the control parameters On dual compressor systems there is a programmed delay from the start of the first compressor and the second to reduce the start up power surge on the power supply COOLER OPERATION There is a programmed one minute delay to start the syste...

Страница 8: ... from one will enter into the air intake of others nor where the air flow is toward a wall or obstruction Avoid locating units in restricted spaces where heat will build up and can enter the condenser There must be room around the unit for regular inspection and service We recommend 200CFM in any area where condensing units may be located Air flow should be sufficient to maintain an ambient temper...

Страница 9: ... The Evaporator Coil section is accessible by unlatching and removing the cover Cleaning the Condenser Coil The efficiency of the refrigeration system depends on the unrestricted flow of air through the Condenser Coil Over time dust and debris will collect on the face of the Condenser Coil and will require cleaning A vacuum cleaner with a soft bristle attachment can be used to clean the coil If th...

Страница 10: ...s or replace relay shorted or blown 2 Low voltage to unit 2 Determine reason and correct 3 Improper relay 3 Replace Relay defective or burned out 1 Incorrect relay 1 Check and replace 2 Voltage too high or too low 2 Determine reason and correct Refrigerated space too warm 1 Control setting too high 1 Reset control 2 Refrigerant overcharge 2 Purge refrigerant 3 Dirty condenser 3 Clean condenser 4 E...

Страница 11: ...5 22 Rev E 171551 ...

Страница 12: ...3 5253 Norlake Walk In Installation 800 647 1284 Master Bilt Sales 800 684 8988 Master Bilt Parts Service Thank you for purchasing Refrigerated Solutions Group equipment Please visit the links below to complete your WARRANTY REGISTRATION Information within this publication subject to change without notice For Norlake Equipment norlake com register For Master Bilt Equipment master bilt com register...