OPEL C Owner's Manual
6
RSF Woodburning Fireplaces
UNIT DIMENSIONS AND CLEARANCES
For the side wall
clearance
Distance from the
fireplace side standoff
to the side of the
firebox opening:
7
1
/
8
"
For the mantel
shelf clearance
Distance from the
fireplace base to the
top of the firebox
opening:
26
3
/
8
"
OPEL2C
with Decorative Grills
OPEL3C
with Regular Louvers
Figure 1 Unit Dimensions and Clearances
Refer to
Table 1 (J)
for maximum
mantel depth
Refer to Table 1 (K)
for minimum mantel
height above the
door opening
Refer to Table 1 (H)
for minimum width
of hearth extension
Refer to Table 1 (G)
for minimum depth
of hearth extension
Non-combustible hearth extension
and spark guard (refer to Table1
(I) and text for particulars)
Refer to Table 1
(B) for minimum
distance of side
wall to the
fireplace