3.2
SET UP MODE PARAMETERS
3-2
O075-3
PM-0075
Parameter
Legend
Adjustment Range
Default
Input Filter Time
Constant
OFF, 0.5s to 100.0s In 0.5s
increments
2.0s
Process Variable Offset
±
input span of Controller
0
Output Power
0 to 100%
Read Only
Output Power 2
4
0 to 100%
Read Only
Proportional Band 1
0.0% to 999.9% of input span
10.0%
Proportional Band 2
14
,
0.0% to 999.9% of input span
10.0%
Reset (Integral Time
Constant)
1
1s to 99m 59s and OFF.
5m 00s
Rate (Derivative Time
Constant)
1
00s to 99m 59s
1m 15s
Overlap/Deadband
1 4
,
−
20% to + 20% of Proportional
Band 1 + Proportional Band 2
0%
Manual Reset (Bias)
1
0% to 100% (single output)
−
100% to +100% (dual output)
25%
ON/OFF Differential
2
:
Output 1 only
Output 2 only
4
Outputs 1 & 2
4
0.1% to 10% of input span
0.5%
Setpoint High Limit
Setpoint to Range Max.
Range
Max.
Setpoint Low Limit
Range Min. To Setpoint
Range
Min.
Table 3-1 Set Up Parameters