17
3.3.3 NPN/PNP selectable models
(
MCCB
L1
AC
source
S2
S3
S4
AO
3
+
250VAC/1A
(30VDC/1A)
T1
T2
T3
RB
RA
S5
L3
(
ON-OFF
Surge
Suppressor
10V
AVI
ACI
GND
Magnetic
Contactor
RS485
FWD (Run/Stop)
REV (Run/Stop)
Speed Control
External speed
potentiometer = 10 Kohm
or PID input
Induction
Motor
COM:NPN
MC
Thermal
relay
MC
S1
GND
0~10V
2
AO
+
-
Frequency
Indicator
0~10VDC
CON2
Thermal
relay
M
0~20mA
P
P'
2'
1
-
L2
(
+24V:NPN *
RC
SC
COM:PNP
+24V:PNP
Power
input
P
BR
Inverter
output
Ground
Pin 1 to Pin 8
Multifunction
Input
Terminals
Relay
Output
Analog
Output
Analog
Input
Note:
Earth wire of
CON2 must be
connected
Model:
400V : RS510-405-SH3(F), RS510-408-SH3(F), RS510-410-SH3(F),
RS510-415-SH3(F)
NPN/PNP input type selection
PNP: 1.Link SC and COM terminal
2.Use +24v terminal for S1~S5 common point
NPN: 1.Link SC and +24V terminal
2.Use COM terminal for S1~S5 common point
Please ensure correct connection before setting parameter
group3 digital inputs.
1:Data+
2:Data-
3:Data+
4:Reserved
5:Reserved
6:Data-
7:5V
8:GND
Содержание RS510 Series
Страница 3: ...3 ...