EN-9
5-4 Trip Test (x1) ( x 1 0, only button 4 illuminated )
a). Select the
×
1 test tripping current.
b). Press the test button. The RCD should trip and the
tripping time will be displayed on the instrument LCD in
mS. While the test is being conducted the display will
indicate “ms”.
c). Reset the breaker and push the phase angle switch.
Press the “Press to Test” button and the breaker should
trip.
d). Reset the breaker and push the phase angle switch
again. Press the “Press to Test” button the breaker
should trip.
e). The readings obtained in 5-4-d and 5-4-c should both
be within the trip time specified for the breaker at its
rated tripping current.
f). If the breaker does not trip there is a fault.
5-5 Fast Trip Test ( x5 , both buttons 3 and 4
illuminated )
a). This is a special test required for a circuit breaker that is
installed to reduce the risk associated with direct contact
for breakers rated up to 30 mA.
b). Set the test tripping current function switch to the x 5
position.
c). Set the RCD rated tripping current switch to 30 mA.
d). Set the phase angle switch to the 0 position.