Multifunction Installation Tester/English
Multifunction Installation Tester/English
13/08/2017 Version No. 001
13/08/2017 Version No. 001
6-When the measuring is complete the impedance
of L-PE and PFC (lf) value appears on the screen
7-Press TEST button if re-test is necessary
When symbol from , ,
appears lower left corner, and if the voltage
exceeds 260V, the measurement will not take place
6-When measuring is completed, impedance of
L-N and PSC value appears on the screen
7-Press TEST button if re-test is necessary
When symbol from , ,
appears lower left corner, and if the voltage
exceeds 260V, the measurement will not take place
You can select UL Voltage by Pressing and hold
F3 button for more than two seconds (25V or 50V).
Uf value appears is the contact voltage on the
screen.
1-Turn the rotary switch to the LOOP / Psc position
2-Press F1 button to change from L - PE to L-N
3-Connect the test leads as shown in Figure 12
4-If voltage of the L-PE on the lower left appears, the
unit is ready to TEST
5-Press the TEST button when ready
5.2.4-Using the L-N Line Impedance Measurement
5.2.5-Using The RCD Function
Figure 11 N Line Impedance-When measuring
Figure 12 N Line Impedance-Test Ieads
connection
Figure 10 L-N Line-Standby screen
Figure 14 RCD-Standby screen
Figure 13 L-N Line Impedance-Measurement
completed
Figure 9 Hi Amp LOOP-Measurement finished