12
Vent System
Termination Kits
Vent System Components
SL D-SERIES
D-SERIES
SLK-01D
SLK-TVCD
SLK-01TRD
Figure 6. Vent Components and Terminations
A. Vent System Approvals
These models have vent starting collars on both the top and
the back of the unit. Depending upon the installation, decide
which ONE set of starting collars will be used to attached
the vent system. The starting collar sealing cap must remain
on the starting collar NOT used.
These models use SL-D-series, direct vent components when
using the
TOP
vent collars and D-series direct vent components
when using the
REAR
vent collars.
The flame and ember appearance may vary based on the type
of fuel burned and the venting configuration used.
WARNING: YOU MUST NOT MIX D-SERIES AND
SL D-SERIES COMPONENTS IN ANY VENT
SYSTEM CONFIGURATION.
Identifying Vent Components
Approved vent system components are labeled for identification.
NO OTHER VENTING SYSTEMS OR COMPONENTS MAY
BE USED
. This pipe is tested and listed as an approved
component of the fireplace. There is no requirement for
inspection openings at each joint within the wall. The pipe is
tested to be run inside an enclosed wall. There is no required
pitch for horizontal vent runs. Detailed installation instructions
are included with each vent termination kit and should be used
in conjunction with this
Installers Guide
. Figure 6 shows vent
system components and terminations.
The vent systems installed on this gas fireplace may include
one, two, or three 90°
elbow assemblies. The relationships of
vertical rise to horizontal run in vent configurations using 90°
elbows
MUST BE
strictly adhered to. The rise to run
relationships are shown in the venting drawings and tables on
the next several pages.
NOTE:
Two 45° elbows may be used in place of one 90° elbow.
You
MUST
always maintain the
MAXIMUM
and
MINIMUM
rise-
to-run ratios in the vent system when using 45° elbows.
Step 3
Installing the
Vent System
DVK-TVCD
DVK-01TRD
DVK-01D
!