Roxtec B frame Скачать руководство пользователя страница 3

Modules installation

Remove any dirt inside the frame.

Lubricate the inside surfaces of 
the frame with Roxtec Lubricant, 
especially into the corners.

Adapt modules which are to hold 
cables or pipes by peeling layers until 
you reach the gap seen in pic. 3.

Achieve a 0.1-1.0 mm gap between 
the two halves when held against 
the cable/pipe.

Lubricate all modules for the frame 
thoroughly, both the inside and the 
outside surfaces.

Insert the modules according to 
your installation plan (transit plan). 
Usually start with the largest 
modules.

Insert a stayplate on top of the 
finished row of modules.

Before inserting the final row of 
modules, insert two stayplates.

Separate the two stayplates and 
insert the final row of modules 
between the stayplates.

Drop the upper stayplate on top of 
the modules.

Lubricate all sides of the wedge 
sparsely, except front and back. 
Please read the markings on the 
wedge and turn it correctly before 
inserting it in the top of the frame 
(standard position). Face with 
“Stayplate this side” must always 
face a stayplate.

Tighten the screws until full stop,
approx. 20 Nm (15 ft.lb.).

Attach the Wedge Clip to the wedge 
bolts to check that the wedge has 
been properly tightened.

Optional wedge positions 
(anywhere within the frame).

Stayplate Clips (D) and Stayplate 
Clamps (E) can be used to simplify 
horizontal assembly.

Содержание B frame

Страница 1: ...mbled around already routed cables or pipes Installation Casting Before concrete is poured the frame and casting mould is fixed in position with the frame flange inside the wall To be able to make a correct installation the size of the opening in the wall must be 5 mm 0 197 wider than the inside dimensions of the frame on all sides The reason for this is the fact that the stayplates need this spac...

Страница 2: ...4 x5 Frame mm in mm in B frame aperture dimensions for bolted installations Theoretically recommended dimensions Mark a rectangular opening according to frame type see table below Use the frame as template for the drilling of the screw holes Hole in flange Ø 9 mm 0 354 Attach the frame to the cabinet wall using bolts and nuts An optional rubber gasket can be placed between frame and cabinet wall T...

Страница 3: ... the finished row of modules Before inserting the final row of modules insert two stayplates Separate the two stayplates and insert the final row of modules between the stayplates Drop the upper stayplate on top of the modules Lubricate all sides of the wedge sparsely except front and back Please read the markings on the wedge and turn it correctly before inserting it in the top of the frame stand...

Страница 4: ...ore exposing the cables pipes to strain or pressure To be used with RM components To simplify installation in combination frames fill all openings before tightening the wedge Cables shall go straight through the frame Packing space Frame sizes 2 4 6 and 8 accommodate the following height of modules 60 mm 120 mm 180 mm and 240 mm As example shows for frame size 6 the 180 mm can be the result of 4 r...