OPC90 Server
7.13
Harmony Digital Input (HDI)
quence of events data.
The HDI OPC90 block is used to retrieve the exception reported output from
Bailey Harmony Digital Input (function code 224) blocks.
Restrictions: This OPC block is only valid for Bailey interface types INICI03,
INICI12 and INICI13. This OPC block does not support the reception of
Harmony digital input se
TAGNAME TYPE
ACCESS
DESCRIPTION
ADDR_RING VT_I2 Config/Read
Bailey
ring
address.
ADDR_NODE
VT_I2
Config/Read
Bailey node address.
ADDR_MODULE
VT_I2
Config/Read
Bailey module address.
ADDR_BLOCK
VT_I2
Config/Read
Bailey block address.
OUTLSD0 VT_BSTR
Config/Read
Output state zero logic state descriptor.
OUTLSD1 VT_BSTR
Config/Read
Output state one logic state descriptor.
MESSAGE
VT_BSTR
Read
Provides the block operational message.
TAG
VT_BSTR
Read
Provides the block name.
TAGLONG VT_BSTR
Read
Provides
the block long OPC path name.
TAGDESC
VT_BSTR
Read
Provides the block descriptor.
CHAN_NAME
VT_BSTR
Read
Channel name assigned to this point
CHAN_STATE
VT_BOOL
Read
Channel state (0-Ok, 1-Open, 2-Short, 3-
Overdrive)
ALARM_CODE VT_I2
Read
Alarm
code
QUALITY VT_BOOL
Read Current
quality
of Bailey values (0-good, 1-bad).
QUAL_PROP
VT_BOOL
Read
Propogated Quality (0-Good, 1-Bad)
OUT
VT_R4
Read
Current output value from Bailey.
OUT_TEXT
VT_BSTR
Read
Discrete Output Value as Text
DISC_LIM
VT_UI2
Read
Discrete alarm state.
DISC_ACT
VT_BOOL
Read
Alarm active indicator.
OVR_ENABLE
VT_BOOL
Read
Override allowed (0-No, 1-Yes)
OVR_VALUE VT_BOOL
Read
Override
value
OVR_STATUS
VT_BOOL
Read
Value overridden (0-No, 1-Yes)
STAT_INHIBT
VT_BOOL
Read
Status inhibit (0-No, 1-Yes)
SUSPECT
VT_BOOL
Read
Value suspect (0-No, 1-Yes)
CONFIG_ERR VT_BOOL
Read
Configuration error exists (0-No, 1-Yes)
READBACK
VT_BOOL
Read
Readback status (0-Good, 1-Bad)
SIM_ENABLE
VT_BOOL
Read
Simulation enable indicator
SIM_BLOCK
VT_I2
Read
Simulation value block number
The RoviSys Company
Version 7.0
Page 79