IP Converter
YT-930
Product Manual
Ver. 1.23
14
5
Connection
–
Power
5.1
Safety
➢
There is a conduit entry on the product. Conduit entry thread is G 1/2.
➢
Before connecting terminal, ensure that the power is off completely.
➢
Please use ring terminal to protect against vibration or any other external impact.
➢
YT-930 series should be grounded at outside of terminals or inside of the product.
➢
Please use twisted cable with conductor section are 1.25mm
2
and that is suitable for 600V
(complying with the conductor table of NEC Article 310). The outer diameter of the cable should
be between 6.35 ~ 10mm. Use shield wire to protect against electro-magnetic field and noise.
➢
Please do not install the cable near high noise equipment, such as high-capacity transformer or
motor. Please use shielded cable if necessary.
➢
DO NOT connect Voltage source (9~28V DC) to Input (4~20mA DC) terminal (IN+, IN-) as it will
cause PCB failure.
5.2
Terminal Overview
Fig. 5-1 Terminal Overview
AO:
Analog Output
AI:
Analog Input
Vs:
Voltage Source