LIMIT SWITCH Setting

Close / Open Limit Cam Switch Setting

1. With the power off, remove the cover and manually rotate

    the ACTUATOR to the closed, clockwise, position.

2. Loosen the close cam set screw and rotate the cam in a  

    clockwise direction to actuate the close limit switch. Also, the   

    close auxiliary switch camcan be adjusted at this time too.

AOLS

Dry Open Limit Switch

ACLS

Dry Close Limit Switch

OLS

Open Limit Switch

CLS

Close Limit Switch

3. Firmly tighten the cam set screws.

4. To set the open cam switches, repeat the previous instructions 

    except rotate the ACTUATOR to the open, counter-clockwise 

    position and rotate the open cams in the counter-clockwise 

    direction to actuate the open switches.

AOLS

OLS

ACLS

CLS

POTENTIOMETER Setting

• 

Actuator delivered full close at 80 ~ 120Ω

• 

After limit setting it should check at closed 80 ~ 120Ω

• 

Make actuator full closed and power off by moving of gear

• 

When finished setting the device, fix the mudu bolt so that the gear will not move.

Warning when setting the POTENTIOMETER:

When setting the resistance value on the POTENTIOMETER, always

operate when the ACTUATOR power if OFF.

If the power is on, the resistance value on the calibrator will not show accurately.

Indicator Setting

The position of the valve is indicated by the visual DOME 

indicator.

LED lights illuminate to allow for easy visual confirmation 

of valve position.

*

 If the position of the indicator is not aligned correctly, 

   an adjustment can be made by simply loosening the

   bolt and manually turning the indicator to the proper  

   location, then re-tightening the bolt.

Содержание RCEL SA

Страница 1: ...scale 0 5 Output Signal 4 20mA DC Load Resistance 750 Wiring Terminals YW 396 2P 3EA 3P 5P connector Visual Indicators 4 LEDS Power Blue Fault Yellow Open Red Close Green Calibration Method ASCN Auto...

Страница 2: ...Specification PCU Board A PCU Board B AC INPUT SIGNAL SELECTION AUTOSCAN SPAN ZERO TIME DELAY DEAD BAND 4 20mA DC OUTPUT SIGNAL 4 20mA DC INPUT SIGNAL OUTPUT SIGNAL CONNECTION OPEN AUTO CLOSE AC POWER...

Страница 3: ...CU Board A PCU Board B DC INPUT SIGNAL SELECTION AUTOSCAN SPAN ZERO TIME DELAY DEAD BAND 4 20mA DC OUTPUT SIGNAL 4 20mA DC INPUT SIGNAL OUTPUT SIGNAL CONNECTION CCW CW OLS CLS OPEN CLOSE AUTO POWER PO...

Страница 4: ...button SPAN Open manual control button Input module button ASCN AUTO SCAN BUTTON ACTUATOR automatic control button delivered from the factory the resistance value of potentiometer may can be changed i...

Страница 5: ...mine the value The factory is set to 80 120 If you have not been set 80 120 please reset Refer to page 6 3 POTENTIOMETER CHECK Using the manual lever or handle to the FULL OPEN ACTUATOR then in the sa...

Страница 6: ...irection to actuate the open switches AOLS OLS ACLS CLS POTENTIOMETER Setting Actuator delivered full close at 80 120 After limit setting it should check at closed 80 120 Make actuator full closed and...

Страница 7: ...plug provided with the ACTUATOR Do not remove the remaining plug as it is already sealed Main Power must only be applied when the top cover is re installed on the actuator body If the main power is on...

Страница 8: ...mA 0 10V or 0 5V and 6 18mA 1 9V If you want to change a current signal 1 Optional Modulation DIP SWITCH No 4 Button ON 2 6mA input Push the ZERO BUTTON ACTUATOR CLOSE 4 After the 18mA input SPAN BUTT...

Страница 9: ...Limit Power input Wage terminal No 2 No 5 Jump ACTUATOR automatic close open AUTO Button push 25sec Check the resistent value of PIU The resistant value when closed 80 120 4mA Close 20mA Open 4 20mA...

Страница 10: ...isengaged Check frequency of operation or JAMMED gears Wiring failure Confirm unit is properly wired per wiring diagram Main board failure Replace main board LED lights not operating LED board failure...

Отзывы: