Torque at x% when opening
There is a set of registers that each record the last value
for the torque generated when the actuator is moving from closed to
open and reaches a particular position (x%). The registers contain 11
values of torque generated in 10% position increments between 0%
and 100% of valve travel.
Torque at x% when closing
There is a set of registers that each record the last value
for the torque generated when the actuator is moving from open to
closed and reaches a particular position (x%). The registers contain
11 values of torque generated in 10% position increments between
100% and 0% of valve travel.
Motor Starts
– Closing Direction
Two registers (one double register) contain the
total number of times the motor contactor to close the valve has been
operated. The first register contains the low order 16 bits. The counter
cannot be reset to zero.
Motor Starts
– Opening Direction
Two registers (one double register) contain the
total number of times the motor contactor to open the valve has been
operated. The first register contains the low order 16 bits. The counter
cannot be reset to zero.