Redefining Flow Control

Specifications

-4-

Specifications

Standard Line Voltage

: 120/240Vac, ±10%,

50/60 Hz (Slide switch select)

(Voltage input MUST match

the actuator motor voltage

rating).

Power Consumption

: Less than 20 watts for amplifier

functions only.

Voltage Output: 

Identical to voltage input.

Current Output: 

10 amps max. at 120 or 240 Vac.

Fuse protection:

Customer supplied.  Size based on

actuator controlled and local codes.

Null output (AD-8240):

Rated 2 ampers

@120/240Vac, 50/60Hz.

Command Signal Inputs

:

• 4-20mA, 4-12mA, 12-20mA into a 200

Ω

 shunt

resistor

• 0-5Vdc into 100,000

Ω

 impedance

• 0-10Vdc into 100,000

Ω

 impedance

Position Feedback Signal

: 1000

Ω

 potentiometer

4-20mA (optional on

AD-8240 models only).

Position Output Signal

: Isolated 4-20mA, loop

powered with 12-36Vdc

external power supply.

Field Wiring Terminations

: Plugable terminal block,

wire size range 26-14

AWG.

Command Signal Monitor

: The 8000 series loss-of-

signal circuitry monitors

the command signal

input. If the command

signal drops below or

above the rating, the

actuator will either lock

in place or run to a

preset position (user

selectable).

Limit Signals

:  Internal:  Part of servo control.

Output Shaft Motion

: All models can go either

direction on an increasing

command signal.  This is

determined by the ZERO and

SPAN settings.

Temperature Limits

: -40° to 150° F (-40° to 65° C).

Duty Cycle

: Unrestricted modulating duty.

(Cont. duty).

Position Accuracy

: 1% of full range.

Deadband

: Factory preset to 1%.  Field adjustable.

Troubleshooting

For visual troubleshooting, LEDs are provided to display the status of the actuator.

These are located on the same side of the lower board as SW1.  The identification of

these LEDs are shown in the table below.

LED

Function

MICRO OK

This LED flashes when the microprocessor is running.  If this is not on, verify 
power to the board.

INC

This LED is on when the actuator is extending the ouput shaft for linear 
actuators, or rotating the output shaft CW for rotary actuators.

DEC

This LED is on when the actuator is retracting the ouput shaft for linear 
actuators, or rotating the output shaft CCW for rotary actuators
1 Flash - Indicates loss of 4-20 mA signal (LOS).
2 Flashes - Indicates loss of the feedback signal.
3 Flashes - Indicates a stall condition.

L.O.S.

Troubleshooting

Содержание AD-8140

Страница 1: ...Digital Servo Amplifiers Redefining Flow Control AD 8140 AD 8240 Instruction Manual...

Страница 2: ...iring of this device should follow the print supplied with the unit Instruction Manual IM 0665 AD 8140 AD 8240 Digital Servo Amplifiers Table of Contents General Information 2 3 Installation Wiring 3...

Страница 3: ...Name Contact Person Phone Fax Address Repair Purchase Order Number Brief description of the problem GENERAL INFORMATION 2 INTRODUCTION Rotork Controls designs manufactures and tests its products to m...

Страница 4: ...warranty information ABBREVIATIONS USED IN THIS MANUAL A or Amps Ampere ac Alternating Current C Degrees Celsius CW Clockwise CCW Counterclockwise dc Direct Current F Degrees Fahrenheit G Earth Ground...

Страница 5: ...actuator will either lock in place or run to a preset position user selectable Limit Signals Internal Part of servo control Output Shaft Motion All models can go either direction on an increasing comm...

Страница 6: ...ctuators Turn the adjusting knob CCW to retract the ouput shaft for linear actua tors or rotate the output shaft CCW for rotary actuators Release button Start Up 5 Transmitter This adjustment sets the...

Страница 7: ...nction ON Up Current Command OFF Down 0 5V 0 10V Voltage Command ON Up 0 5V Voltage Command OFF Down Current 0 10V Command ON Up LOS Lock in Place OFF Down LOS Preset Position ON Up Dynamic Brake On O...

Страница 8: ...8 Typical Wiring Diagrams 7 Typical Wiring Diagrams Due to wide variations in terminal numbering of actuator products actual wiring should follow the print supplied with the unit AD 8140 AD 8240...

Страница 9: ...are available upon request ROTORK CONTROLS 5607 West Douglas Avenue Milwaukee Wisconsin 53218 Phone 414 461 9200 FAX 414 461 1024 www rotork com IM 0665 04 15 AD 8240 AD 8140 Location of J1 With power...

Страница 10: ...nd change specifications without prior notice Published data may be subject to change For the very latest version release visit our website at www rotork com The name Rotork is a registered trademark...

Отзывы: