A4
US
US
A4
US
A4
US
A4
4
General Information
-3-
GENERAL ACTUATOR DESCRIPTION
The AD-8000 series of digital servo amplifiers are
on/off triac output AC servo amplifiers suitable for
operating a variety of Rotork Controls actuators.
Standard features include: onboard switch selectable
command input for 0-5Vdc, 0-10Vdc, or 4-20mA;
selectable loss of command signal operation; 4-20mA
isolated output transmitter tracking actuator shaft
position; dynamic motor braking; 120 to 240Vac, 50/
60Hz input power depending on actuator motor being
used; and on-board LED’s and encoder adjusting knob
for ease of set-up.
The customer’s command signal is isolated from both
the ac line and the electric motor in the actuator. In
addition, the AD-8240 servo amplifiers feature an
isolated, “null” output for customer use.
WARRANTY INFORMATION
Warranty: Subject to the following, Jordan expressly warrants the
products manufactured by it as meeting the applicable Rotork
product specifications and that such products are free from defects
in material and workmanship for a period of one (1) year from the
date of delivery.
The foregoing is the sole and exclusive warranty made by Jordan
with respect to the products. Rotork makes no other warranties,
either express or implied (including, without limitation, warranties
as to merchantability or fitness for a particular purpose).
The purchaser retains responsibility for the application and
functional adequacy of the offering. See Rotork's General
Conditions of Sale - Product, for complete warranty information.
ABBREVIATIONS USED IN THIS MANUAL
A or Amps ........................................................ Ampere
ac ................................................... Alternating Current
° C ......................................................Degrees Celsius
CW .............................................................. Clockwise
CCW ...............................................Counterclockwise
dc .........................................................Direct Current
° F ................................................. Degrees Fahrenheit
G ............................................................ Earth Ground
Hz ....................................................................... Hertz
kg ................................................................... Kilogram
L ................................................... Line (power supply)
lbs ..................................................................... Pounds
lbf. ................................................................ Lbs. Force
LVDT .............. Linear Variable Differential Transformer
mA ................................................................. Milliamp
mfd .............................................................Microfarad
mm ............................................................ Millimeters
N ......................................................... Newton (force)
NEMA ........... National Electrical Manufacturing Assoc.
Nm .......................................................Newton Meter
NPT ........................................... National Pipe Thread
Ph .......................................................................Phase
PL ............................................... Position Limit Switch
P/N .......................................................... Part Number
RPM ........................................ Revolutions per Minute
SEC .................................................................. Second
TL .................................................. Thrust Limit Switch
Vac ................................................................... Volts ac
Vdc .................................................................. Volts dc
VR .................................................. Variable Resistance
W ........................................................................ Watt
General Information
Most installations locate the servo amplifier inside a
Rotork Controls actuator, for ease of mounting and to
protect the amplifier. This is the preferred mounting
arrangement. For remote mounting, the servo
amplifier and actuator should be as close to each other
as possible.
Ensure all connections are correct and tight before
applying power. Power, command signal, feedback
signal, and motor output are the minimum required
connections.
To connect optional features refer to wiring diagram
for the specific amplifier and actuator.
Installation Wiring
All wiring should be done in accordance with
prevailing codes by qualified personnel.
Typical wiring diagrams are shown on page 7. Actual
wiring should follow the print supplied with the
actuator.
Fusing must be installed in line with input power, and
should be of the slow blow type. After installation, it is
recommended that all conduits be sealed to prevent
water damage. All low level signal wiring should be a
shielded type with the shield grounded at source
common.
Installation Wiring