12
ENGLISH
ROFUSE Sani 160:
ROFUSE Sani 315:
Symbols:
No fitting detected
Mains frequency is not within the
tolerances (40 - 70 Hz)
Ambient temperature is too hot
Power failure has caused a
power loss
Ambient temperature is too cold
Stopped by an error
Mains voltage or current is too low (during
welding)
Prompt to press a button
Mains voltage or current is too high (during
welding)
OK
No welding adapter attached
5.2
Connecting the Electrofusion Fitting
WARNING! Mains voltage is applied to the socket connector during operation.
Please use a residual current circuit breaker.
Connect the connection terminals to the fitting and check for proper fit. The contact surfaces of
the connection terminals and the fitting have to be clean. Dirty terminals may lead to improper
welding and also to overheated and fused terminal plugs.
The welding mode screen will appear after the fitting makes contact and provided that no errors
are present.
The welding time, the fitting type and the press the Start button prompt will be displayed.
Press the START button to start the welding process.
The welding time will finish (it depends on the ambient temperature) after approx. 80 secs.
For ROFUSE Sani 315:
Connect the welding adapter that you want to use to the socket on the welding cable. The weld-
ing adapter will be detected automatically. The compatible fitting types will be displayed on the
screen.
A00 connector – fitting with diameter ranging from 32 – 160 mm; Manufacturers: Valsir,
Akatherm, Eurofusion, Geberit, Waviduo, Coes.
A01 connector – fitting with diameter ranging from 200 – 315 mm; Manufacturers: Valsir,
Akatherm, Eurofusion, Waviduo.
A02 connector – fitting with diameter ranging from 200 – 315 mm; Manufacturer: Geberit.
A04 connector – fitting with diameter ranging from 200 – 315 mm; Manufacturer: Coes.