26
ENGLISH
9.
The tapping point farthest from the device must be the first one opened. At the end of the
rinsing, the next tapping point from the device must be
closed.
Example:
Before rinsing, open
1-2-3-4- 5 sequentially.
After rinsing, close
5-4-3-2-1 sequentially.
10.
After the rinse, the water supply and the rinse compressor must be turned off. Then
disconnect the device from the power supply. Attention! The rinse compressor must not be
in the process of filling the container. The rinse compressor must be disconnected from the
rinsed pipe. Then a new leak test is necessary. The final pipe installation must be
completed professionally.
11.
After the rinsing process, a rinsing log (certificate) must be made out. The original copy
must remain with the customer and the carbon copy with the company performing the
work.
4.3
Rinsing with disinfectant during domestic installation
Select the program “Water and disinfectant” in connection with a dosing pump.
Only officially approved disinfectants may be used to rinse the installation.
1.
The ends of the outlet hoses must be connected to activated carbon filters.
2.
Connect the dosing pump hose to the “Disinfection” connector.
3.
Connect the pulsation output plug on the Ropuls electronics to the electronics of the
dosing pump. This will adjust the dosing to the rinse compressor pulse.
4.
Press the ON/OFF button. The compressor fills the pressure vessels automatically.
5.
Press the program button “Water with disinfectant”.
When the installed stop valves are opened, the flow rate is displayed.
6.
Open the taps on the system to be cleaned and check the disinfectant concentration. Here
also follow the information in DVGW worksheet W 291.
7.
After testing the concentration, close the taps again and, in compliance with worksheet W
291, wait until the system has been disinfected.
8.
Remove the rinse compressor and reinstall the connections.
9.
After an appropriate delay, open the taps again and let the rinse water flow out through
an activated carbon filter into the public sewer or, if necessary, catch it in a supplementary
tank.
4.4
Rinsing floor heating systems
1.
The water supply must be disconnected from the water
heater.
2.
A water fuse (pipe disconnector) must be installed before
the compressor.
3.
Disconnect or close the return pipe and attach a drain
hose. Additionally, the hose must lead to a drain of
sufficient dimensions and be fastened.
4.
When water pressure is low, rinse the heating system
strand by strand.
Содержание 1000000145