Installation manual
7
RKRTW
Room thermostat
4PW50082-1
Temperature control codes
Rotex advizes not to change below temperature control
parameters. They are set for an optimal use of the floor cooling/
heating application.
6®
02
Use
proportional
band control?
ÚêÒ
ÚêÒ
(proportional
band)/
≈œ
(hysteresis)
—
03
Hysteresis
value
00.5
00.5
~
02.0
0.1°C
04
+
p
Duration
proportional
band (heating).
020
010
~
060
1 min.
05
+
p
Minimum "on"
time (heat
demand).
007
002
~
6® 04
/2
1 min.
06
+
p
Minimum delay
between 2
heating cycles.
003
001
~
6® 04
/2
1 min.
07
+
o
Duration
proportional
band (cooling).
020
010
~
060
1 min.
08
+
o
Minimum "on"
time (cool
demand).
007
002
~
6® 07
/2
1 min.
09
+
o
Minimum delay
between 2
cooling cycles.
003
001
~
6® 07
/2
1 min.
10
Value of
proportional
band.
02.0
01.0
~
04.0
0.1°C
11
Compensating
value.
00.0
00.0
~
08.0
0.1°C
1st
code
2nd
code
Description
Default
Range
Step
1O_IM_4PW50082-1.book Page 7 Monday, October 20, 2008 9:15 AM