Operation manual

11

RKHBRD011~0Y17

Indoor unit for air to water heat pump system and options

4P403582-1B – 2017.09

Operation example

: Schedule timer based on temperature set

points.

When setback function is enabled, the setback operation will have
priority over the scheduled action in the schedule timer.

Operation example

: Schedule timer based on ON/OFF instruction.

When setback function is enabled, the setback operation will have
priority over the scheduled action in the schedule timer if ON
instruction is active. If OFF instruction is active this will have priority
over the setback function. At any time the OFF instruction will have
the highest priority.

1

Schedule timer

2

Setback function

3

When both setback function and schedule timer are enabled

A

Setback function

t

Time

T

Temperature set point

Room temperature

Leaving water temperature

Method 2
[0-03]=0

Space heating based on ON/OFF instruction

During operation

When the schedule timer switches space heating OFF, 
the controller will be switched off (operation LED will stop 
working). Note that this has no influence on the domestic 
water heating.

When pushing 
the 

 button

The schedule timer for space heating will stop (when 
active at that moment) and will start again at the next 
scheduled ON function.
The "last" programmed command overrules the 
"preceding" programmed command and will remain 
active until the "next" programmed command occurs.

Example: imagine the actual time is 17:30 and actions 
are programmed at 13:00, 16:00 and 19:00. The "last" 
programmed command (16:00) overruled the 
"previous" programmed command (13:00) and will 
remain active until the "next" programmed command 
(19:00) occurs.

So in order to know the actual setting, one should consult 
the last programmed command. It is clear that the "last" 
programmed command may date from the day before. 
Refer to 

"Consulting programmed actions" on page 14

.

The controller will be switched off (operation LED will 
stop working).

However the schedule timer icon will stay displayed 
which means that the domestic heating stays enabled.

When pushing 
the  /  button

The schedule timer for space heating 

and

 domestic 

water heating along with the quiet mode will be stopped 
and will not start again.

The schedule timer icon will not be displayed anymore.

T

t

6:30

9:00

16:00

0:30

19

19

°

C

19

19

°

C

19

19

°

C

22

22

°

C

21

21

°

C

62

62

°

C

62

62

°

C

62

62

°

C

65

65

°

C

64

64

°

C

62

°

C

19

°

C

19

°

C

19

°

C

22

°

C

21

°

C

62

°

C

62

°

C

65

°

C

64

°

C

0:30

1

T

t

18

18

°

C

57

57

°

C

57

°

C

18

°

C

A

5:00

5:00

23:00

23:00

5:00

23:00

2

T

t

5:00

9:00

16:00

23:00

19

19

°

C

18

18

°

C

19

19

°

C

22

22

°

C

21

21

°

C

62

62

°

C

60

60

°

C

62

62

°

C

65

65

°

C

64

64

°

C

60

°

C

19

°

C

18

°

C

19

°

C

22

°

C

21

°

C

62

°

C

62

°

C

19

19

°

C

62

62

°

C

19

°

C

62

°

C

19

19

°

C

62

62

°

C

19

°

C

62

°

C

19

19

°

C

62

62

°

C

19

°

C

62

°

C

65

°

C

64

°

C

6:30

3

57

57

°

C

57

°

C

60

60

°

C

60

°

C

1

Schedule timer

2

Setback function

3

When both setback function and schedule timer are enabled

A

Setback function

B

ON/OFF instruction

t

Time

T

Temperature set point

Room temperature

Leaving water temperature

t

18

18

°

C

60

60

°

C

60

°

C

18

°

C

A

5:00

5:00

23:00

23:00

5:00

23:00

2

B

t

9:00

16:00

19

19

°

C

19

19

°

C

22

22

°

C

21

21

°

C

62

62

°

C

62

62

°

C

65

65

°

C

64

64

°

C

19

°

C

19

°

C

22

°

C

21

°

C

62

°

C

62

°

C

65

°

C

64

°

C

1

OFF

ON

ON

6:30

0:30

B

t

6:30

9:00

16:00

23:00

19

19

°

C

19

19

°

C

22

22

°

C

21

21

°

C

62

62

°

C

62

62

°

C

65

65

°

C

64

64

°

C

19

°

C

19

°

C

22

°

C

21

°

C

62

°

C

62

°

C

65

°

C

64

°

C

3

OFF

ON

ON

18

18

°

C

60

60

°

C

60

°

C

18

°

C

4PEN403582-1B_2017_09.book  Page 11  Saturday, October 7, 2017  11:02 AM

Содержание RKHBRD011ADV17 RKHBRD014ADV17 RKHBRD016ADV17

Страница 1: ...RKHBRD011ADV17 RKHBRD014ADV17 RKHBRD016ADV17 RKHBRD011ADY17 RKHBRD014ADY17 RKHBRD016ADY17 Indoor unit for air to water heat pump system and options 4PEN403582 1B_2017_09 book Page 1 Saturday October...

Страница 2: ...d knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children should be supervised to ensure that they do not pla...

Страница 3: ...ge on page 7 The icon will display Hot water will be produced at next scheduled action When water heat up starts the icon will be blinking 1 second interval Manual storage one time water heat up refer...

Страница 4: ...T AVAILABLE This icon is displayed whenever a non installed option is addressed or a function is not available A function not available can mean insufficient permission level or can mean that a slave...

Страница 5: ...case not zero will display 31 ROOM TEMPERATURE ADJUST BUTTONS and These multi purpose buttons are used to adjust the current room temperature set point in normal operation mode or in schedule timer p...

Страница 6: ...mode heating will be activated as required by the water temperature set point The set point can be set manually through the schedule timer or weather dependent automatic Selecting space heating operat...

Страница 7: ...e Lo_A low outdoor temperature 3 01 High ambient temperature Hi_A high outdoor temperature 3 02 Set point at low ambient temperature Lo_Ti the target outgoing water temperature when the outdoor temper...

Страница 8: ...dependent domestic water heating is turned ON 1 or OFF 0 If enabled the storage set point will be set weather dependent In case of a higher ambient temperature e g during summer time temperature of s...

Страница 9: ...storage temperature is reached It can also be stopped at any time by pushing the button NOTE If weather dependent domestic water heating is enabled b 02 the storage temperature will be set automatica...

Страница 10: ...there are no error conditions in leaving or returning water thermistors the heater kit can start to follow emergency operation Other operation modes Start up operation During start up the icon display...

Страница 11: ...ule timer The actions programmed in the schedule timer will be executed automatically The schedule timer is enabled icon displayed or disabled icon not displayed by pressing the button Space heating R...

Страница 12: ...ve until the next programmed command 19 00 occurs So in order to know the actual setting one should consult the last programmed command It is clear that the last programmed command may date from the d...

Страница 13: ...ram depending on remote controller model 4 or 5 actions can be programmed per mode The same actions are repeated on a daily basis Take your time to enter all data accurately Try to program the actions...

Страница 14: ...s to set the room temperature 11 Use the button to select to switch heating and the remote controller off to select automatic temperature calculation for leaving water temperature Use the and buttons...

Страница 15: ...en action number 3 is displayed actions 1 2 and 3 are stored but 4 and 5 are deleted By pressing the button several times you return to previous steps in this procedure and finally return to normal op...

Страница 16: ...er action number than the one that is displayed E g when the button is pressed when action number 3 is displayed actions 1 2 and 3 are stored but 4 and 5 are deleted Deleting a mode 1 Press the button...

Страница 17: ...for a minimum of 5 seconds to enter FIELD SET MODE The icon 3 will be displayed The current selected field setting code is indicated 2 with the set value displayed to the right 1 2 Press the button t...

Страница 18: ...w ambient temperature Lo_Ti 70 25 80 1 C 03 Set point at high ambient temperature Hi_Ti 45 25 80 1 C 4 Disinfection function 00 Status disinfection operation 1 ON 0 1 01 Disinfection operation day sel...

Страница 19: ...04 Automatic maximum hot water tank storage temperature 70 55 75 1 C C Leaving water temperature limits 00 Installation related setting 80 37 80 1 C 01 Installation related setting 25 25 37 1 C 02 No...

Страница 20: ...e information If the supply cord is damaged it must be replaced by the manufacturer its agent or similar qualified persons in order to avoid hazards During longer periods of standstill e g during summ...

Страница 21: ...4PEN403582 1B_2017_09 book Page 1 Saturday October 7 2017 11 02 AM...

Страница 22: ...4PEN403582 1B_2017_09 book Page 2 Saturday October 7 2017 11 02 AM...

Страница 23: ...4PEN403582 1B_2017_09 book Page 1 Saturday October 7 2017 11 02 AM...

Страница 24: ...nd Nos partenaires l tranger Le nostre sedi all estero Neustros representantes en el extranjero Nasi partnerzy za granic Na i partne i v zahrani http de rotex heating com ueber rotex international 4P4...

Отзывы: