4 Installation

Installation manual

8

RBLQ011~016CAW1

ROTEX HPSU monobloc compact outdoor unit

4P537991-1 – 2018.08

4.3.2

To insulate the water piping

The  piping  in  the  complete  water  circuit  MUST  be  insulated  to
prevent  condensation  during  cooling  operation  and  reduction  of  the
heating and cooling capacity.

To  prevent  the  freezing  of  the  outdoor  water  piping  during  winter
time, the thickness of the sealing material MUST be at least 13 mm
(with λ=0.039 W/mK).

If  the  temperature  is  higher  than  30°C  and  the  humidity  is  higher
than RH 80%, the thickness of the insulation materials should be at
least  20  mm  to  prevent  condensation  on  the  surface  of  the
insulation.

During  winter,  protect  the  water  piping  and  shut‑off  valves  against
freezing  by  adding  heat  tape  (field  supply).  If  the  outdoor
temperature  can  drop  below  –20°C  and  no  heat  tape  is  used,  it  is
recommended to install the shut‑off valves indoors.

4.4

Connecting the electrical wiring

DANGER: RISK OF ELECTROCUTION

WARNING

ALWAYS use multicore cable for power supply cables.

4.4.1

To connect the electrical wiring on the
outdoor unit

1

Remove the switch box cover. See 

"4.1.1 To open the outdoor

unit" on page 5

.

2

Insert the wiring at the back of the unit:

a

b
c

≥25 mm

a

Low voltage cable

b

High voltage cable

c

Power supply cable

NOTICE

The  distance  between  the  high  voltage  and  low  voltage
cables should be at least 25 mm.

Routing

Possible cables (depends on the installed
options)

a

Low voltage

▪ Interconnection  cable  to  HPSU  monobloc

tank

▪ Remote outdoor sensor (option)

b

High voltage

▪ Shut-off valve (field supply)

c

Main power supply

▪ Main power supply

3

Inside the unit, route the wiring as follows:

a

a

Power supply cable

b

Cable tie

4

Make sure that the cable does NOT come in contact with sharp
edges or hot gas piping.

5

Install the switch box cover.

INFORMATION

When  installing  field  supply  or  option  cables,  foresee
sufficient cable length. This will make it possible to remove/
reposition  the  switch  box  and  gain  access  to  other
components during service.

CAUTION

Do NOT push or place redundant cable length in the unit.

4.4.2

To connect the main power supply

1

Connect the main power supply.

1 2 3 L1 L2 L3 N

X1M

a

a

Power supply cable (including earth)

4.4.3

To connect the remote outdoor sensor

1

2

10 mm

Содержание RBLQ011CAW1

Страница 1: ...Installation manual ROTEX HPSU monobloc compact outdoor unit English Installation manual ROTEX HPSU monobloc compact outdoor unit RBLQ011CAW1 RBLQ014CAW1 RBLQ016CAW1...

Страница 2: ...B C 500 250 100 A B C E 500 250 150 1000 500 500 D 500 500 D E 1000 500 B D 250 500 B D E 250 250 400 400 400 400 400 1000 150 150 150 150 150 150 150 1000 1000 1000 500 HD HU HD HU HB HU HD HU HB HU...

Страница 3: ...v daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputama 16 17 18 19 20 21...

Страница 4: ...3 To connect the remote outdoor sensor 8 4 4 4 To connect the shut off valve 9 5 Commissioning 9 5 1 Checklist before commissioning 9 6 Hand over to the user 9 7 Technical data 10 7 1 Piping diagram...

Страница 5: ...water volume in the installation is minimum 80 litre the internal water volume of the outdoor unit NOT included INFORMATION In critical processes or in rooms with a high heat load extra water might b...

Страница 6: ...s follows 150 6 2 0 350 3 4 5 3 5 5 a mm 2 6 1 5 6 M12 a Make sure not to cover the drain holes INFORMATION The recommended height of the upper protruding part of the bolts is 20 mm 20 NOTICE Fix the...

Страница 7: ...the outdoor unit 3 Insert a rubber sheet between the cables and the outdoor unit to prevent the cables from scratching the paint field supply 4 Attach the ends of the cables and tighten them 4 3 Conne...

Страница 8: ...4 1 To connect the electrical wiring on the outdoor unit 1 Remove the switch box cover See 4 1 1 To open the outdoor unit on page 5 2 Insert the wiring at the back of the unit a b c 25 mm a Low voltag...

Страница 9: ...een the outdoor unit and the HPSU monobloc tank The system is properly earthed and the earth terminals are tightened The fuses or locally installed protection devices are installed according to this d...

Страница 10: ...nt liquid side thermistor 12 Inlet water thermistor 13 Gas stop valve with service port 14 Electronic expansion valve main 15 4 way valve 16 Not applicable 17 High pressure switch 18 Compressor 19 Pre...

Страница 11: ...kcase heater F1U F2U A1P Fuse T 31 5 A 500 V F3U F6U A1P Fuse T 6 3 A 500 V F7U A2P Fuse T 5 A 250 V F8U F9U Fuse F 1 A 250 V H1P H7P A2P LED service monitor is orange HAP A1P A2P LED service monitor...

Страница 12: ...15H Internal pipe heater 2 33 W F1U A1P Fuse T5 A 250V K R A1P Magnetic relay English Translation M1P Main supply pump Q4DI Earth leakage circuit breaker R1T Outlet water heat exchanger thermistor R3T...

Страница 13: ......

Страница 14: ......

Страница 15: ......

Страница 16: ...r partners abroad Unsere Partner im Ausland Nos partenaires l tranger Le nostre sedi all estero Neustros representantes en el extranjero Nasi partnerzy za granic Na i partne i v zahrani http de rotex...

Отзывы: