background image

3 Operation

Operation manual

6

08DA

ROTEX HPSU Bi-Bloc Ultra

4P495263-1C – 2018.11

▪ The  desired  room  temperature  will  return  to  its  scheduled  value

whenever a scheduled action occurs.

You  can  avoid  scheduled  behaviour  by  (temporarily)  turning  off
scheduling.

To turn off room temperature scheduling

1

Go to [1.1]: Room > Schedule.

2

Select No.

3.3.3

To change the desired leaving water
temperature

INFORMATION

The  leaving  water  is  the  water  that  is  sent  to  the  heat
emitters.  The  desired  leaving  water  temperature  is  set  by
your  installer  in  accordance  with  the  heat  emitter  type.
Only adjust the leaving water temperature settings in case
of problems.

You  can  use  the  leaving  water  temperature  setpoint  screen  to  read
out and adjust the desired leaving water temperature.

1

Go to [2]: Main zone or [3]: Additional zone.

You can read out the desired and actual leaving
water temperature in the center of the setpoint
screen.

2

Adjust the desired leaving water temperature.

3.4

Domestic hot water control

3.4.1

Reheat mode

In  reheat  mode  the  DHW  tank  continuously  heats  up  to  the
temperature shown on the home screen (example: 50°C).

t

60°C

00:00

07:00

50°C

15°C

40°C

14:00

21:00

1

2

3

4

Tt

T

t

DHW tank temperature

t

Time

INFORMATION

Risk  of  space  heating  capacity  shortage  for  domestic  hot
water  tank  without  internal  booster  heater:  In  case  of
frequent  domestic  hot  water  operation,  frequent  and  long
space  heating/cooling  interruption  will  happen  when
selecting the following:

Tank > Heat up mode > Reheat only.

INFORMATION

When  the  DHW  tank  mode  is  reheat,  the  risk  for  capacity
shortage  and  comfort  problem  is  significant.  In  case  of
frequent  reheat  operation,  space  heating/cooling  function
is regularly interrupted.

3.4.2

Scheduled mode

In scheduled mode the DHW tank produces hot water corresponding
to a schedule. The best time to allow the tank to produce hot water is
at night, because the space heating demand is lower.

Example: 

t

60°C

00:00

07:00

50°C

15°C

40°C

14:00

21:00

1

2

3

4

5

Tt

T

t

DHW tank temperature

t

Time

3.4.3

Sch reheat mode

In  scheduled  +  reheat  mode,  the  domestic  hot  water  control  is  the
same  as  in  scheduled  mode.  However,  when  the  DHW  tank
temperature drops below a preset value (=reheat tank temperature –
hysteresis  value;  example:  35°C),  the  DHW  tank  heats  up  until  it
reaches  the  reheat  set  point  (example:  45°C).  This  ensures  that  a
minimum amount of hot water is available at all times.

Example: 

t

Tt

60°C

00:00

07:00

50°C

45°C

15°C

14:00

21:00

35°C

1

2

4

5

3

T

t

DHW tank temperature

t

Time

3.4.4

Using DHW powerful operation

About powerful operation

Powerful  operation  allows  the  domestic  hot  water  to  be  heated  by
the  backup  heater  or  booster  heater.  Use  this  mode  on  days  when
there is more hot water usage than usual.

To check if powerful operation is active

If 

 is displayed on the home screen, powerful operation is active.

Activate or deactivate Powerful operation as follows:

1

Go to [5.1]: Tank > Powerful operation

2

Turn powerful operation Off or On.

Usage example: You immediately need more hot water

You are in the following situation:

▪ You already consumed most of your domestic hot water.

▪ You  cannot  wait  for  the  next  scheduled  action  to  heat  up  the

domestic hot water tank.

Then  you  can  activate  powerful  operation.  The  domestic  hot  water
tank will start heating up the water to the Comfort temperature.

INFORMATION

When  powerful  operation  is  active,  the  risk  of  space
heating/cooling and capacity shortage comfort problems is
significant.  In  case  of  frequent  domestic  hot  water
operation,  frequent  and  long  space  heating/cooling
interruptions will happen.

3.5

Advanced usage

The  amount  of  information  you  can  read  out  in  the  menu  structure
depends on your user permission level:

Содержание Bi-Bloc Ultra RHBX04DA6V

Страница 1: ...Operation manual ROTEX HPSU Bi Bloc Ultra English Operation manual ROTEX HPSU Bi Bloc Ultra RHBX04DA6V RHBX04DA9W RHBX08DA6V RHBX08DA9W ...

Страница 2: ... about the settings that he used to configure your system Check if he has filled in the installer settings tables If not request him to do so Keep the documentation for future reference Target audience End users Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions that you must read before operating your system F...

Страница 3: ... a certain time of non interaction with the user interface the screen darkens Pressing any button or rotating any dial awakens the display The time of non interaction differs depending on the user permission level User or Advanced user 15 min Installer 1 h Dials and buttons You use the dials and buttons To navigate through the screens menus and settings of the LCD screen To set values a b c d e It...

Страница 4: ...re Item Description Additional zone h3 h1 h2 h1 Heat emitter type Underfloor heating Fancoil unit Radiator h2 Leaving water temperature setpoint h3 Room thermostat type External control Hidden Leaving water temperature control Domestic hot water i1 i2 i1 Domestic hot water i2 Measured tank temperature Malfunction j or A malfunction occurred See 6 1 To display the help text in case of a malfunction...

Страница 5: ...ce operation modes Depending on your heat pump model you have to tell the system which space operation mode to use heating or cooling If a heat pump model is installed Then Heating cooling The system can heat up and cool down a space You have to tell the system which space operation mode to use Heating only The system can heat up a space but NOT cool down a space You do NOT have to tell the system...

Страница 6: ...e DHW tank produces hot water corresponding to a schedule The best time to allow the tank to produce hot water is at night because the space heating demand is lower Example t 60 C 00 00 07 00 50 C 15 C 40 C 14 00 21 00 1 2 3 4 5 Tt Tt DHW tank temperature t Time 3 4 3 Scheduled reheat mode In scheduled reheat mode the domestic hot water control is the same as in scheduled mode However when the DHW...

Страница 7: ...ostat control is active If leaving water temperature control is active you can program the main zone schedule instead 1 Go to the schedule 2 Clear the contents of the schedule optional 3 Program the schedule for Monday 4 Copy the schedule to the other weekdays 5 Program the schedule for Saturday and copy it to Sunday 6 Give the schedule a name To go to the schedule 1 Go to 1 1 Room Schedule 2 Set ...

Страница 8: ...t Edit 3 Use the left dial to select an entry and edit the entry with the right dial 0 8 00 23 00 21 C 18 C 12 24 Sat 4 Confirm the changes 5 Select Saturday 6 Select Copy 7 Select Sunday 8 Select Paste Result Mon Sat Wed Fri Thu Tue Sun User defined 1 C To rename the schedule INFORMATION Not all schedules can be renamed 1 Select the name of the current schedule Mon Sat Wed Fri Thu Tue Sun User de...

Страница 9: ...e date Holiday Quiet Electricity price Gas price C Operation Room Space heating cooling Tank B User profile 7 3 Holiday Activation From Till 7 4 Quiet Activation Schedule 7 5 Electricity price High Medium Low Schedule 7 2 Time date Hours Minutes Year Month Day Daylight savings time Format 8 1 Energy data Electricity input Produced heat 1 Room Room sensor offset Setpoint range Antifrost Cooling sch...

Страница 10: ...eriods You can use the holiday mode Tips about DHW tank temperature Use a weekly schedule for your normal domestic hot water needs only in scheduled mode Program to heat up the DHW tank to a preset value Comfort higher DHW tank temperature during the night because then space heating demand is lower If heating up the DHW tank once at night is not sufficient program to additionally heat up the DHW t...

Страница 11: ...mperature cannot be reached Increase the desired leaving water temperature in accordance with the heat emitter type 6 3 Symptom The water at the tap is too cold Possible cause Corrective action You ran out of domestic hot water because of unusual high consumption If you immediately need domestic hot water activate the DHW tank Powerful operation However this consumes extra energy If you can wait o...

Страница 12: ...s or collectors Before you purge air from heat emitters or collectors check if or is displayed on the home screen of the user interface If not you can purge air immediately If yes make sure that the room where you want to purge air is sufficiently ventilated Reason Refrigerant might leak into the water circuit and subsequently into the room when you purge air from the heat emitters or collectors 7...

Страница 13: ......

Страница 14: ......

Страница 15: ......

Страница 16: ...rtners abroad Unsere Partner im Ausland Nos partenaires à l étranger Le nostre sedi all estero Neustros representantes en el extranjero Nasi partnerzy za granicą Naši partneři v zahraničí http de rotex heating com ueber rotex international 4P495263 1C 2018 11 ROTEX Subject to change and correction 4P495263 1 C 00000001 ...

Отзывы: