3 Operation
Operation manual
6
08DA
ROTEX HPSU Bi-Bloc Ultra
4P495263-1C – 2018.11
▪ The desired room temperature will return to its scheduled value
whenever a scheduled action occurs.
You can avoid scheduled behaviour by (temporarily) turning off
scheduling.
To turn off room temperature scheduling
1
Go to [1.1]: Room > Schedule.
2
Select No.
3.3.3
To change the desired leaving water
temperature
INFORMATION
The leaving water is the water that is sent to the heat
emitters. The desired leaving water temperature is set by
your installer in accordance with the heat emitter type.
Only adjust the leaving water temperature settings in case
of problems.
You can use the leaving water temperature setpoint screen to read
out and adjust the desired leaving water temperature.
1
Go to [2]: Main zone or [3]: Additional zone.
You can read out the desired and actual leaving
water temperature in the center of the setpoint
screen.
2
Adjust the desired leaving water temperature.
3.4
Domestic hot water control
3.4.1
Reheat mode
In reheat mode the DHW tank continuously heats up to the
temperature shown on the home screen (example: 50°C).
t
60°C
00:00
07:00
50°C
15°C
40°C
14:00
21:00
1
2
3
4
Tt
T
t
DHW tank temperature
t
Time
INFORMATION
Risk of space heating capacity shortage for domestic hot
water tank without internal booster heater: In case of
frequent domestic hot water operation, frequent and long
space heating/cooling interruption will happen when
selecting the following:
Tank > Heat up mode > Reheat only.
INFORMATION
When the DHW tank mode is reheat, the risk for capacity
shortage and comfort problem is significant. In case of
frequent reheat operation, space heating/cooling function
is regularly interrupted.
3.4.2
Scheduled mode
In scheduled mode the DHW tank produces hot water corresponding
to a schedule. The best time to allow the tank to produce hot water is
at night, because the space heating demand is lower.
Example:
t
60°C
00:00
07:00
50°C
15°C
40°C
14:00
21:00
1
2
3
4
5
Tt
T
t
DHW tank temperature
t
Time
3.4.3
Sch reheat mode
In scheduled + reheat mode, the domestic hot water control is the
same as in scheduled mode. However, when the DHW tank
temperature drops below a preset value (=reheat tank temperature –
hysteresis value; example: 35°C), the DHW tank heats up until it
reaches the reheat set point (example: 45°C). This ensures that a
minimum amount of hot water is available at all times.
Example:
t
Tt
60°C
00:00
07:00
50°C
45°C
15°C
14:00
21:00
35°C
1
2
4
5
3
T
t
DHW tank temperature
t
Time
3.4.4
Using DHW powerful operation
About powerful operation
Powerful operation allows the domestic hot water to be heated by
the backup heater or booster heater. Use this mode on days when
there is more hot water usage than usual.
To check if powerful operation is active
If
is displayed on the home screen, powerful operation is active.
Activate or deactivate Powerful operation as follows:
1
Go to [5.1]: Tank > Powerful operation
2
Turn powerful operation Off or On.
Usage example: You immediately need more hot water
You are in the following situation:
▪ You already consumed most of your domestic hot water.
▪ You cannot wait for the next scheduled action to heat up the
domestic hot water tank.
Then you can activate powerful operation. The domestic hot water
tank will start heating up the water to the Comfort temperature.
INFORMATION
When powerful operation is active, the risk of space
heating/cooling and capacity shortage comfort problems is
significant. In case of frequent domestic hot water
operation, frequent and long space heating/cooling
interruptions will happen.
3.5
Advanced usage
The amount of information you can read out in the menu structure
depends on your user permission level: