Rotex 30308 Скачать руководство пользователя страница 6

 

IM No.: IM/V/0015, Rev. 7 

Date: 14.10.2019 

Page 6 of 6 

 

(C) 

REPLACEMENT OF MANUAL OVERRIDE 

– OPTIONALLY PROVIDED 

1) 

Remove Grub Hex Socket Set Screw and pull out Manual Override. 

2) 

Replace  new  Manual  Override  applying  light  layer  of  Silicon  Grease  Molykot  M55  and  tighten  the 
grub screw fully till the Manual Override stops traveling in and out. 

3) 

Open the Grub Hex Socket Set Screw slightly (1/4 turn) and check the smooth movement of the grub 
screw. 

  4) 

Without connecting  air supply to the valve, operate Manual Override.   energized and De-Energized 
Solenoid to check for the plunger movement (normally movement should not be there) which can be 
checked by click sound.   
After operating Manual Override if plunger movement is found, reduce length of the manual override 
by 0.3mm from its tapper end.  Continue this till click sound stops. 
 
 

 

STORING, CLEANING AND MOUNTING OF ELASTOMERS: SYNTHETIC RUBBER PRODUCTS  

 

Store  Plunger,  O  Ring  Set  in  sealed  polyethylene  bag,  kept  in  cool,  dry,  dust  free  area  and  avoid  direct 
contact  with  all  light  sources  emitting  ultra  violet  rays,  or  contact  with  fumes,  solvents,  fuels,  lubricants, 
chemicals, acids, disinfectants. 

 

Follow Maintenance General Instruction & specific procedures to replace O Ring set as listed above. 

 
 

 

 

 

 

 

Guide Opening Tool M-32/24 

Photo - 1

 

              
                 Flat Face this side 

Photo 

– 2 

Plunger with sleeve 

Photo 

– 3 

 

 

 

 

 

          Manual Override  in

“OFF”                    Manual Over ride in „ON‟ 

         Turn clockwise to On Valve                   Turn Anti Clockw

ise to „OFF‟ 

                     Photo 

– 4                                               Photo-5 

                

 

 
Contact:  
 
ROTEX AUTOMATION LIMITED 
987/11, GIDC, MAKARPURA, VADODARA 

– 390010, INDIA 

Tel.: +91 265 2638136, 2638746, 2638795   Fax: +91 265 2638130 
E-mail

[email protected]

  Website: 

www.rotexautomation.com

 

Содержание 30308

Страница 1: ...st port 3 are connected Media cannot come out from the outlet port 2 In energized condition of the solenoid plunger assembly moves up now when we applied the pressure at inlet port 1 media pressure come out from the outlet port 2 through the duse hole In this state inlet port 1 outlet port 2 is connected and exhaust port 3 is blocked So media comes from the outlet port 2 NO Operation In de energiz...

Страница 2: ...er 2 Valve Type Code 30308 Valve Model Suffix Nil 5 Orifice mm 2R Port Connection NPT F B5 Body Material SS316 M8 Manual Override Push type S2 Seal Material Viton Sp Version Nil 3 Work Order reference Sr No of the Valve 4 Operating Pressure 5 Month Year of manufacture 6 Valve Symbol 7 Media 1 ROTEX AUTOMATION LIMITED VADODARA 390010 INDIA FLUID CONTROL SYSTEM CODE 30308 5 2R B5 M8 S2 ATM 0 10 MEDI...

Страница 3: ... grease Consult ROTEX in case if any doubt i Do not try to drill any additional holes or machine modify any of the valve components j In case if the valve is used for dangerous fluid gas liquid then the user is hereby advised to maintain during operation and maintenance of the valve below LEL or above UEL to avoid explosion due to internal spark as the valves have not been assessed for the same k ...

Страница 4: ...0333 5 MANUAL OVERRIDE OPERATION OPTIONALLY PROVIDED A PUSH TURN TYPE M6 When the solenoid is de energized and inlet and outlet ports connected to the applying rated pressure the valve can be operated either pressing the Manual Override when the same is released the valve returns to the normal position The valve can also be locked in energized position by pushing the Manual Override and rotating c...

Страница 5: ...ushed in a straight line Turning motion should be avoided Pinching of O Ring at the groove corner at the time of closing gland should be avoided User is requested to use safe practice for maintenance It is important to place the dismantled Valve Parts on a clean paper or cloth in same sequence in which you have dismantled them Ensure to keep all the components of the valve separately to avoid thei...

Страница 6: ...reduce length of the manual override by 0 3mm from its tapper end Continue this till click sound stops STORING CLEANING AND MOUNTING OF ELASTOMERS SYNTHETIC RUBBER PRODUCTS Store Plunger O Ring Set in sealed polyethylene bag kept in cool dry dust free area and avoid direct contact with all light sources emitting ultra violet rays or contact with fumes solvents fuels lubricants chemicals acids disi...

Отзывы: