Rotex 30308 Скачать руководство пользователя страница 4

 

IM No.: IM/V/0015, Rev. 7 

Date: 14.10.2019 

Page 4 of 6 

 

 
 

REMARKS 

 

1) 

Solenoid Valve in which media passing through the valve is 

Gaseous

 and Orifice less than 25mm, 

PED is not applicable. 

2) 

Solenoid Valve in which media passing through the valve is 

Liquid Hazardous

 nature, pressure 0.5 

bar and 

Liquid Non-Hazardous 

nature, pressure below 10 bar, PEF is not applicable. 

 

ELECTRICAL 

 

1.    

Verify name plate affixed on the Solenoid. 

2. 

For AC Voltage (50Hz or 60Hz), select solenoid with option “FR”

3. 

Connect the power supply as per the voltage rating of the Solenoid.  

4.   

Ensure that the cover of Junction Box/Terminal Box is properly tightened wherever applicable.

 

   

5.  

Install valve in such a way that the rain water / other process fluid dripping along the cable does not fall on the 
SOV and has no possibility to run along the cable and enter into the Terminal area.    

6.   

Fill in the space between cable and gland entry with a proper sealant.  If necessary, you may mount the valve 
upside down or in any other direction. 

7.   

Ensure that the Solenoid enclosure meets process and local authority requirement. 

8.  

The Plug In, Terminal Box, FPJB are provided with test leads.  Remove them before final installation. 

   9.  

Check for proper connections for the Solenoid which are polarity sensitive e.g. (a) Latched Solenoid. 

 10.  

Refer  separate  manual  for  construction  of  the  Solenoid  and  for  specific  instructions  related  to 
Solenoid e.g.  (a) Latched Solenoid (b) Exd Solenoid IP 67 

     

11.  

Ensure  that  the  solenoid  construction  is  selected  properly  meeting  the  environment  in  which  the  valve  is 
supposed  to  be  installed  e.g.  use  of  Ex  d  solenoid  for  valve  to  be  installed  in  hazardous  location  or 
Weatherproof Solenoid having IP 67 for outdoor installation.

 

  12.  

Flying  Lead  Solenoid  is  not  recommended  to  be  used  for  outdoor  or  indoor  application  where 
water/liquid splashing or high humidity is present. 

   13. 

Intrinsically Safe Solenoid can not be supplied with the Valve (Except 30308-5, 30334-5, 30333-5) 

 
MANUAL OVERRIDE OPERATION 

– OPTIONALLY PROVIDED

 

 

(A) 

PUSH & TURN TYPE (M6)

 

When  the  solenoid  is  de-energized  and  inlet  and  outlet  ports  connected  to  the  applying  rated  pressure,  the 
valve can be operated either pressing the Manual Override, when the same is released, the valve  returns to 
the normal position. The valve can also be locked in energized position by pushing the Manual Override and 
rotating clockwise.  To avoid  Manual Override  returning to normal condition, ensure that the same is turned 
above 90º.  The valve can be brought to normal condition by turning Manual Override anti clockwise. 

 

(B) 

PUSH TYPE (M8)  

When  the  solenoid  is  de-energized,  inlet  and  outlet  ports  connection  and  rated  pressure  applied,  the  valve 
can be brought to energized position by pressing Manual Override / Lever.  The valve remains in this position 
till  Manual  Override  /  Lever  is  pressed.    As  soon  as  the  same  is  released,  the  valve  returns  to  the  normal 
position. 

 

TESTING OF THE VALVE AT THE TEST BENCH 

  Check at least once in 3 years or following your routine maintenance schedule. 

a) 

Apply rated pressure at inlet port of the valve.   

b) 

Plug outlet port. 

c) 

Check operation of the valve and leakage at the exhaust port at the rated and minimum working pressure by 
applying 75% to 120% rated voltage. 

d) 

While keeping the solenoid de-energized, check operation and leakage from exhaust of the valve at the rated 
and minimum working pressure by operating Manual Override. 

  e) 

Without connecting air supply to the valve, operate Manual Override.   Energize and De-energize Solenoid to 
check  for  the  plunger  movement  (normally  movement  should  not  be  there)  which  can  be  checked  by  click 
sound.  After operating Manual Override if plunger movement is found, reduce length of the manual override 
by 0.3mm from its taper end.  Continue this till click sound stops. 

f) 

Check the insulation resistance of the Solenoid by applying 500V DC at terminals and the solenoid housing. It 
should be more than 100 Mega Ohms. 

 

RECOMMENDED SPARES :  
         

Code  

Description 

Components  

98 

Seal kit  

O ring + Plunger Assembly  

99 

Repair kit  

All components except Body, Cover and Solenoid 

34 

Solenoid kit  

Solenoid, Gasket & Nut  

 
 
 

Содержание 30308

Страница 1: ...st port 3 are connected Media cannot come out from the outlet port 2 In energized condition of the solenoid plunger assembly moves up now when we applied the pressure at inlet port 1 media pressure come out from the outlet port 2 through the duse hole In this state inlet port 1 outlet port 2 is connected and exhaust port 3 is blocked So media comes from the outlet port 2 NO Operation In de energiz...

Страница 2: ...er 2 Valve Type Code 30308 Valve Model Suffix Nil 5 Orifice mm 2R Port Connection NPT F B5 Body Material SS316 M8 Manual Override Push type S2 Seal Material Viton Sp Version Nil 3 Work Order reference Sr No of the Valve 4 Operating Pressure 5 Month Year of manufacture 6 Valve Symbol 7 Media 1 ROTEX AUTOMATION LIMITED VADODARA 390010 INDIA FLUID CONTROL SYSTEM CODE 30308 5 2R B5 M8 S2 ATM 0 10 MEDI...

Страница 3: ... grease Consult ROTEX in case if any doubt i Do not try to drill any additional holes or machine modify any of the valve components j In case if the valve is used for dangerous fluid gas liquid then the user is hereby advised to maintain during operation and maintenance of the valve below LEL or above UEL to avoid explosion due to internal spark as the valves have not been assessed for the same k ...

Страница 4: ...0333 5 MANUAL OVERRIDE OPERATION OPTIONALLY PROVIDED A PUSH TURN TYPE M6 When the solenoid is de energized and inlet and outlet ports connected to the applying rated pressure the valve can be operated either pressing the Manual Override when the same is released the valve returns to the normal position The valve can also be locked in energized position by pushing the Manual Override and rotating c...

Страница 5: ...ushed in a straight line Turning motion should be avoided Pinching of O Ring at the groove corner at the time of closing gland should be avoided User is requested to use safe practice for maintenance It is important to place the dismantled Valve Parts on a clean paper or cloth in same sequence in which you have dismantled them Ensure to keep all the components of the valve separately to avoid thei...

Страница 6: ...reduce length of the manual override by 0 3mm from its tapper end Continue this till click sound stops STORING CLEANING AND MOUNTING OF ELASTOMERS SYNTHETIC RUBBER PRODUCTS Store Plunger O Ring Set in sealed polyethylene bag kept in cool dry dust free area and avoid direct contact with all light sources emitting ultra violet rays or contact with fumes solvents fuels lubricants chemicals acids disi...