6  TROUBLESHOOTING GUIDE 

Problem

:

 Temperature Sensor does not operate

 

Solution

:

 

1.  Replace Temperature sensor or connect it to another terminal.  

2.  Test the Sensor: Disconnect the two wires of the temperature sensor and measure the 

resistance. 

a)  For 25° C the resistance should be 30 Kohm. If the temperature is higher, the resistance 

should be lower (for example at 42° C the resistance should be 15Kohm). If the temp is 
less than 25°, the resistance should be higher than 30 Kohm (for example for 15° C the 
resistance will be 45 Kohm). 

b)  If no resistance is measured (

∞) it could have been caused by a broken temperature 

sensor wire. 

 
Problem

:

 Humidity sensor does not operate 

Solution

:

 

1.  Supply Voltage: Check the 12 VDC between the Humidity Red(+) and Black(-) terminal  

(it should be 7.5 V at least). 

2.  Check output voltage of the sensor between Humidity White (+) and Black (-). Note that it 

must be 0.5 ÷ 3.0 VDC (15% to 100% of RH). 

a)  If the voltage is 0 or more than 3V the sensor is probably bad. 

b)  If the voltage is right (for example 1.5V for 50%) and the 

AC-2000

 displays the wrong 

value, it could be that this channel is bad. Move the white wire to a different analog input, 
define in Menu 94 (sensor layout) and check again. 

3.  Replace the Humidity Sensor (for 

RHS-10PL

 replace only the tip). 

 
Problem

:

 Static pressure sensor does not operate 

Solution

:

 

1.  Check that the internal static pressure is defined as 4 in Menu 94 (sensor layout). 

2.  Shut OFF all fans and close all curtains and inlets so that pressure is at 0. Go to Menu 35 

(Analog Input Test) and see that the received value is 65 counts. If it is not at 65 counts, 
calibrate the pressure sensor by the trimmer to 65. 

3.  Clean filters, and check that both tubes are not blocked. 

 
Problem

:

 Digital Input or pulse does not operate 

Solution

:

 

1.  Disconnect the wires from the input and check the 5V between the digital input and the 

common terminal. 

a)  If there is no 5 V then probably the input has been damaged (The lightning protection 

device shorted or the pull-up resistor burned out). 

2.  Go to Menu 34 and short the digital input of the common. Check if ‘0’ changes to ‘1’. 

3.  For the pulse input (water) use Menu 37 and check that the counter increase by one for 

every short across the pulse terminal. 

 
Problem

:

 Communication does not operate 

Solution

:

 

1.  If Rx and Tx LEDs are permanently ON, switch the wires between the Rx and the Tx. 

2.  Check that all jumpers are in MUX position. 

3.  Check all house numbers. There should not be a house number defined as zero, or two 

houses with same house number. 

4.  Check that all controllers have the same baud rate, and same as PC. 

5.  Connect only one controller to the network and check communication. A faulty RCLP can 

cause the whole network to not communicate. 

6.  Replace the suspected faulty RCLP. 

7.  Sometimes the Opto-Coupler isolators in the communication adaptor could be damaged 

from lightning and needs to be replaced. 

Содержание AC-2000 PLUS

Страница 1: ...AC 2000 SE and PLUS Pig Controllers Installation Manual P N 110118...

Страница 2: ...following cases i if all components of the product are not originally supplied by ROTEM ii the defect is the result of an act of nature lighting strikes electrical power surge or interruption of elect...

Страница 3: ...ng 12 4 3 1 AC 2000 Board Layout 12 4 3 2 AC 2000 SE Relays 13 4 3 3 AC 2000 SE High Voltage Wiring Relays 14 4 3 4 AC 2000 SE Terminals 15 4 3 5 AC 2000 SE Low Voltage Wiring Terminals 16 4 3 6 MUX R...

Страница 4: ...rdous situations which if not avoided could result in death or personal injury 1 3 Contact Information Rotem Control and Management Email support rotem com URL www rotem com 1 4 Document Information R...

Страница 5: ...n EMI filter in front of the inverter according to the specifications provided by the inverter manufacturer Refer to the inverter documentation 2 3 Checking the Battery Level Check the battery once a...

Страница 6: ...Amp 50 60Hz Relay Loads 5 0 Amps 250 Volts Fused Analog Inputs 0 11 Volts 10 Milliamps Maximum Analog Output 0 10 Volts Current Limited with 100 Ohm Resistor Digital Inputs 5 ma 5 Volts Dry Contact O...

Страница 7: ...perature and sensor shields to earth ground However do not connect communication wire shields which go from one house to another at both ends Connect them at one end only Connection at both ends can c...

Страница 8: ...elay normally serves as an alarm relay It is also fused with a 5 ampere 250 volt slow blow fuse and can serve as an ordinary relay oNC Normally closed contact oCom Common contact oNO Normally open con...

Страница 9: ...11 4 2 3 AC 2000 Plus High Voltage Wiring Relays NOTE The device connections fan heat cool etc that are shown in the drawing are examples only CAUTION Connect the AC 2000 Plus power input to the prote...

Страница 10: ...ine carries data to the relay extension oClk 3 This line carries a clocking signal for use by the relay extension 3 Not used 4 6 Temperature Sensors 8 9 10 25 26 27 The temperature sensor is a 2 wired...

Страница 11: ...OTE Users employing a CO2 sensor refer to Appendix Installing a CO2 sensor 4 2 6 AC 2000 Plus Communication AC 2000 Plus is wired to a MUX Communicator via an internal communication card P N C AC 2000...

Страница 12: ...E Relays page 13 AC 2000 SE High Voltage Wiring Relays page 14 AC 2000 SE Terminals page 15 AC 2000 SE Low Voltage Wiring Terminals page 16 MUX RCLP Wiring page 17 4 3 1 AC 2000 Board Layout 1 Ground...

Страница 13: ...es as an alarm relay It is also fused with a 5 ampere 250 volt slow blow fuse and can serve as an ordinary relay oNC Normally closed contact o Com Common contact o NO Normally open contact 3 Power Thr...

Страница 14: ...11 14 4 3 3 AC 2000 SE High Voltage Wiring Relays NOTE The device connections fan heat cool etc that are shown in the drawing are examples only CAUTION Connect the AC 2000 SE power input to the protec...

Страница 15: ...atter 4 Analog Inputs oAn 1 Humidity sensor with wire connections according to wire colors oAn 2 Humidity Outside Humidity input Connect the White wire of the Humidity sensor to An 2 and the Red and B...

Страница 16: ...11 16 4 3 5 AC 2000 SE Low Voltage Wiring Terminals Connect the sensor shielding wire to the grounding strip o16 Analog Input 2 o17 Analog Input 3 o18 Analog Input 1 NOTE The above illustration is an...

Страница 17: ...17 AC 2000 8 10 8 11 4 3 6 MUX RCLP Wiring...

Страница 18: ...Enter the menu number from the Installation Menu Configuration Menu 91 page 18 Ventilation Table Menu 92 page 19 Relay Layout Menu 93 page 20 Sensor Layout Menu 94 page 22 Setup Curtains Menu 95 page...

Страница 19: ...se a unique number for each AC 2000 to enable the communication program to identify each controller Curtain opening and closing times Enter the number of seconds it takes the curtains to go from fully...

Страница 20: ...no values in the timer on and off fields or only an off time or only an on time the AC 2000 defaults to constant on operation Due to limited display size the AC 2000 shows only the on off timer or th...

Страница 21: ...8 Ventilation Group 1 through 8 9 10 Zone A Heat Low High 11 12 Zone B Heat Low High 13 14 Zone C Heat Low High 15 16 17 Zone A Radiant Heat Low High Ignition 18 19 20 Zone B Radiant Heat Low High Ig...

Страница 22: ...tches and other connection information should also be available 5 4 Sensor Layout Menu 94 The AC 2000 supports up to six heating zones each with individual heaters The average of the zones determines...

Страница 23: ...sed connect it to terminal 17 Pres Sens and define as Analog Input 3 5 5 Setup Curtains Menu 95 Level 1 2 3 4 Tunnel 1 9 0 0 0 0 0 10 15 15 15 15 15 11 25 25 25 25 25 12 40 40 40 40 40 13 60 60 60 60...

Страница 24: ...k that the internal static pressure is defined as 4 in Menu 94 sensor layout 2 Shut OFF all fans and close all curtains and inlets so that pressure is at 0 Go to Menu 35 Analog Input Test and see that...

Страница 25: ...ted fuse 2 If a group of 4 or 8 relays are not working it could be that one of the relay coils shorted causing the thermal fuse automatic fuse to short Problem Sporadic resets caused by interference S...

Страница 26: ...about 10 cm 4 inches is left above grade If it is impossible to drive the rod to the proper depth it is acceptable to lay the rod horizontally 80 cm 2 5 feet below grade In case the rod is exposed to...

Страница 27: ...htning protection to the AC 2000 Controllers Refer to the RPLP 1 documentation for detailed wiring instructions While no lightning protection is perfect the RPLP 1 significantly enhances the reliabili...

Страница 28: ...1 28 8 APPENDIX INSTALLING A CO2 SENSOR The following section details the steps involved in installing a CO2 sensor 8 1 Low Voltage Wiring AC 2000 Plus Version 8 11 supports a CO2 sensor Wire the unit...

Страница 29: ...Configuring the CO2 Sensor In the CO2 sensor verify that the J2 jumper is shorted Refer to Figure 2 Figure 1 J2 Jumper Shorted All other installation instructions are the same Refer to the CO2 Manual...

Отзывы: