Rotem AC-2000 PLUS Скачать руководство пользователя страница 20

 

 

AC-2000 

|

 8.10/8.11 

20 

Ventilation Level 

Ventilation Groups 

On Minutes 

Off Minutes 

Diff 

Var  

Var #2 

15 

1 2 3 4 0 0 0 0 0 0 0 0 

1.0 

0.0 

16 

1 2 3 4 0 0 0 0 0 0 0 0 

1.0 

0.0 

1.0 

17 

1 2 3 4 5 0 0 0 0 0 0 0 

1.0 

0.0 

2.0 

18 

1 2 3 4 5 6 0 0 0 0 0 0 

1.0 

0.0 

3.0 

19 

1 2 3 4 5 6 7 0 0 0 0 0 

1.0 

0.0 

4.0 

20 

1 2 3 4 5 6 7 0 0 0 0 0 

1.0 

0.0 

4.0 

 

The 

AC-2000 

increases the fan power as ventilation requirements rise.  The increments should be 

proportional from level to level.  This means that the ventilation increases about 50% to 100% at each level.  
For example, at Level One a single fan is set to 0.5 minutes on and 9.5 minutes off. At Level Two, if you set 
the fan to 1.0 minute on and 9.0 minutes off, there is a 100% increase.  At a much higher level, such as 
ventilation level 15, an increase from 4 fans to 6 fans represents a 50% increase in fan power.  Please 
review the example ventilation tables for this principle.   

The ventilation table, 

Menu 92

, defines the fan powered ventilation levels for the poultry house.  This 

includes variable speed, timer and on/off fans for up to 20 levels of ventilation. At each ventilation level, a 
cycle timer can run the highest numbered fan group used at that level.  With no values in the timer on and 
off fields, or only an off time or only an on time, the 

AC-2000 

defaults to constant on operation.  

 

Due to limited display size, the 

AC-2000 

shows only the on-off timer or the variable speed setting at each 

level.  Use 

Menu 91

, item 4 to select which setting the 

AC-2000 

shows.  However, both settings remain in 

memory. 

Since air movement provides a cooling effect, the 

AC-2000 

provides a temperature differential at each 

level.  This is particularly important in tunnel ventilation, where the cooling effect can be (–12) °C.  The 

AC-2000 

waits until the target temperature plus the differential before using that ventilation level. 

NOTE: 

The ventilation table coordinates with the curtain table.  For natural ventilation, one should 
regard the curtain table as part of the ventilation table.  The two tables together serve as one 
larger table. 

5.3  Relay Layout (Menu 93) 

Relay 

Code 

NO/NC 

25 

26 

7…20 

Select 

Menu 93

 for relay layout. Each relay may work normally or reversed using the NO/NC field.  Most 

relays should be set to normal.  

There are twelve/twenty relays inside the 

AC-2000 SE / AC-2000 PLUS 

respectively, and there may be 

additional relay extensions.  All the relays are numbered sequentially.  Assigning the relay code to each 
relay causes it to assume the particular function.  Simply changing the relay code changes the function of 
the relay.  

First Tunnel Level 

Содержание AC-2000 PLUS

Страница 1: ...AC 2000 SE and PLUS Pig Controllers Installation Manual P N 110118...

Страница 2: ...following cases i if all components of the product are not originally supplied by ROTEM ii the defect is the result of an act of nature lighting strikes electrical power surge or interruption of elect...

Страница 3: ...ng 12 4 3 1 AC 2000 Board Layout 12 4 3 2 AC 2000 SE Relays 13 4 3 3 AC 2000 SE High Voltage Wiring Relays 14 4 3 4 AC 2000 SE Terminals 15 4 3 5 AC 2000 SE Low Voltage Wiring Terminals 16 4 3 6 MUX R...

Страница 4: ...rdous situations which if not avoided could result in death or personal injury 1 3 Contact Information Rotem Control and Management Email support rotem com URL www rotem com 1 4 Document Information R...

Страница 5: ...n EMI filter in front of the inverter according to the specifications provided by the inverter manufacturer Refer to the inverter documentation 2 3 Checking the Battery Level Check the battery once a...

Страница 6: ...Amp 50 60Hz Relay Loads 5 0 Amps 250 Volts Fused Analog Inputs 0 11 Volts 10 Milliamps Maximum Analog Output 0 10 Volts Current Limited with 100 Ohm Resistor Digital Inputs 5 ma 5 Volts Dry Contact O...

Страница 7: ...perature and sensor shields to earth ground However do not connect communication wire shields which go from one house to another at both ends Connect them at one end only Connection at both ends can c...

Страница 8: ...elay normally serves as an alarm relay It is also fused with a 5 ampere 250 volt slow blow fuse and can serve as an ordinary relay oNC Normally closed contact oCom Common contact oNO Normally open con...

Страница 9: ...11 4 2 3 AC 2000 Plus High Voltage Wiring Relays NOTE The device connections fan heat cool etc that are shown in the drawing are examples only CAUTION Connect the AC 2000 Plus power input to the prote...

Страница 10: ...ine carries data to the relay extension oClk 3 This line carries a clocking signal for use by the relay extension 3 Not used 4 6 Temperature Sensors 8 9 10 25 26 27 The temperature sensor is a 2 wired...

Страница 11: ...OTE Users employing a CO2 sensor refer to Appendix Installing a CO2 sensor 4 2 6 AC 2000 Plus Communication AC 2000 Plus is wired to a MUX Communicator via an internal communication card P N C AC 2000...

Страница 12: ...E Relays page 13 AC 2000 SE High Voltage Wiring Relays page 14 AC 2000 SE Terminals page 15 AC 2000 SE Low Voltage Wiring Terminals page 16 MUX RCLP Wiring page 17 4 3 1 AC 2000 Board Layout 1 Ground...

Страница 13: ...es as an alarm relay It is also fused with a 5 ampere 250 volt slow blow fuse and can serve as an ordinary relay oNC Normally closed contact o Com Common contact o NO Normally open contact 3 Power Thr...

Страница 14: ...11 14 4 3 3 AC 2000 SE High Voltage Wiring Relays NOTE The device connections fan heat cool etc that are shown in the drawing are examples only CAUTION Connect the AC 2000 SE power input to the protec...

Страница 15: ...atter 4 Analog Inputs oAn 1 Humidity sensor with wire connections according to wire colors oAn 2 Humidity Outside Humidity input Connect the White wire of the Humidity sensor to An 2 and the Red and B...

Страница 16: ...11 16 4 3 5 AC 2000 SE Low Voltage Wiring Terminals Connect the sensor shielding wire to the grounding strip o16 Analog Input 2 o17 Analog Input 3 o18 Analog Input 1 NOTE The above illustration is an...

Страница 17: ...17 AC 2000 8 10 8 11 4 3 6 MUX RCLP Wiring...

Страница 18: ...Enter the menu number from the Installation Menu Configuration Menu 91 page 18 Ventilation Table Menu 92 page 19 Relay Layout Menu 93 page 20 Sensor Layout Menu 94 page 22 Setup Curtains Menu 95 page...

Страница 19: ...se a unique number for each AC 2000 to enable the communication program to identify each controller Curtain opening and closing times Enter the number of seconds it takes the curtains to go from fully...

Страница 20: ...no values in the timer on and off fields or only an off time or only an on time the AC 2000 defaults to constant on operation Due to limited display size the AC 2000 shows only the on off timer or th...

Страница 21: ...8 Ventilation Group 1 through 8 9 10 Zone A Heat Low High 11 12 Zone B Heat Low High 13 14 Zone C Heat Low High 15 16 17 Zone A Radiant Heat Low High Ignition 18 19 20 Zone B Radiant Heat Low High Ig...

Страница 22: ...tches and other connection information should also be available 5 4 Sensor Layout Menu 94 The AC 2000 supports up to six heating zones each with individual heaters The average of the zones determines...

Страница 23: ...sed connect it to terminal 17 Pres Sens and define as Analog Input 3 5 5 Setup Curtains Menu 95 Level 1 2 3 4 Tunnel 1 9 0 0 0 0 0 10 15 15 15 15 15 11 25 25 25 25 25 12 40 40 40 40 40 13 60 60 60 60...

Страница 24: ...k that the internal static pressure is defined as 4 in Menu 94 sensor layout 2 Shut OFF all fans and close all curtains and inlets so that pressure is at 0 Go to Menu 35 Analog Input Test and see that...

Страница 25: ...ted fuse 2 If a group of 4 or 8 relays are not working it could be that one of the relay coils shorted causing the thermal fuse automatic fuse to short Problem Sporadic resets caused by interference S...

Страница 26: ...about 10 cm 4 inches is left above grade If it is impossible to drive the rod to the proper depth it is acceptable to lay the rod horizontally 80 cm 2 5 feet below grade In case the rod is exposed to...

Страница 27: ...htning protection to the AC 2000 Controllers Refer to the RPLP 1 documentation for detailed wiring instructions While no lightning protection is perfect the RPLP 1 significantly enhances the reliabili...

Страница 28: ...1 28 8 APPENDIX INSTALLING A CO2 SENSOR The following section details the steps involved in installing a CO2 sensor 8 1 Low Voltage Wiring AC 2000 Plus Version 8 11 supports a CO2 sensor Wire the unit...

Страница 29: ...Configuring the CO2 Sensor In the CO2 sensor verify that the J2 jumper is shorted Refer to Figure 2 Figure 1 J2 Jumper Shorted All other installation instructions are the same Refer to the CO2 Manual...

Отзывы: