Following detection of any of the said problems or failures, the Far
module behaves as shown in the following table:
Problem
Activity
Reader Tamper
Sends trouble and problem to the Near module
Far Module Tamper
Sends trouble and problem to the Near module
Low Battery
Sends trouble and problem to the Near module
(Trouble LED turns on)
AC Fail
Sends trouble and problem to the Near module
(Trouble LED turns on)
RF Device Failure/Problem
Trouble LED flashes at a fast rate (after power on)
Incorrect DIP Switch
Setting
All LEDs flash at a slow rate (after power on)
The MD-W11 Near module detects following troubles:
Near module tamper
Supervision fail
RF device failure/problem
Incorrect DIP Switch setting
Following detection of any of the said problems or failures, the Near
module behaves as shown in the following table:
Problem Name
Activity
Near Module Tamper
Activates Near Unit’s tamper output
Supervision Failure
Activates Near Unit’s supervision output
(Trouble LED turns on)
RF Device Failure/Problem
Trouble LED flashes at a fast rate (after power
on)
Incorrect DIP Switch Setting
All LEDs flash at a slow rate (after power on)