4.2

 

Outputs 

Electrical devices can be switched using the voltage free relay contacts.  
Rosslare recommends using suppression diodes for all outputs that are 

connected to inductive loads and activated by DC current, such as 
Magnetic Lock ("Maglock") or door strike devices. 
Each suppression diode must be connected near its inductive load. 

Always attach the diode's cathode to the +V terminal of the load. 
Attach the diode's anode to the –V terminal. 
For more information, refer to your access controller's Installation and 
User Guide. 

4.3

 

Readers 

The reader terminal supports the reader's two data lines. For Wiegand 
readers, these are data lines D0 and D1. For Clock & Data readers, D0 

is the DATA line and D1 is the CLOCK line. 
There is also support for a tamper signal input from the reader and for 
one LED control output to the reader. 
Proximity and keypad readers are supplied with a limited cable. The 
color of the cable cover represents the cable’s function. 
In general, the cable length should be no more than 150 m with an 18 

AWG cable. Refer to each reader's installation guide for specific details. 
Readers connected through an MD-D02 are recognized as "Reader 3 

and "Reader 4" in the software system. 
Figure 9 and Figure 10 show the wiring for Readers 3 and 4, 

respectively. 

Figure 9: Wiring for Reader 3 

 

 

Figure 10: Wiring for Reader 4 

  

5.

 

Using the MD-D02

5.1

 

Operating the MD-D02 

The access control panel detects the MD-D02 expansion board when it 
powers up. When defining the panel in the access control panel's PC 

application (such as AxTraxNG™), select the option designating the 

panel name with a designation of “MD-D02”. 
Readers, inputs and outputs must be defined using the access system 

software. Readers connected through an MD-D02 will be recognized 
as "Reader3" and "Reader4" in the software system. 
Define each input's type and make sure the connection is compatible 

with the input wiring. 
When selecting inputs and outputs from the software, note that input 

and output type and function in the access control software normally 
reflect the host access control panel's general purpose inputs and 

outputs. 
When using AxTrax, define input types from the "Inputs" tree menu. 
Input and output functions are defined using the "Links" element 

within each "Panel" tree menu item.  
For more information, refer to the 

AxTraxNG Software Manual. 

 

R

ead

er

R

ead
er

 4

 

R

ead

er

 4

 

R

ead

er

 3

 

Содержание MD-D02

Страница 1: ...en Normally Closed Supervised with one resistor three states normally open or normally closed Supervised with two resistors four states Normally Open or Normally Closed 2 3 7BPhysical Characteristics Dimensions L x W x D 100 x 75 9 x 32 5 mm 3 94 x 2 99 x 1 28 in Weight 98 2 g 3 46 oz 2 4 8BReader Characteristics Reader Output Voltage 12 VDC Max Reader Current 245 mA LED Control Output Open collec...

Страница 2: ...pen supervised input connection with double resistor Figure 6 Normally Open Supervised Inputs with Double Resistor Normally Open Supervised inputs with two resistors must be connected with an 8 2K resistor in parallel and a 2 2K resistor in series to the input switch contacts Figure 7 shows the normally closed supervised input connection with single resistor Figure 7 Normally Closed Supervised Inp...

Страница 3: ...r specific details Readers connected through an MD D02 are recognized as Reader 3 and Reader 4 in the software system Figure 9 and Figure 10 show the wiring for Readers 3 and 4 respectively Figure 9 Wiring for Reader 3 Figure 10 Wiring for Reader 4 5 Using the MD D02 5 1 Operating the MD D02 The access control panel detects the MD D02 expansion board when it powers up When defining the panel in th...

Страница 4: ...lare Security Products Inc Southlake TX USA 76092 Toll Free 1 866 632 1101 Local 1 817 305 0006 Fax 1 817 305 0069 support na rosslaresecurity com Europe Rosslare Israel Ltd Rosh HaAyin Israel 48091 Tel 972 3 938 6838 Fax 972 3 938 6830 support eu rosslaresecurity com Latin America Rosslare Latin America Buenos Aires Argentina Tel 54 11 4001 3104 support la rosslaresecurity com China Rosslare Elec...

Отзывы: