3.

 

Installation 

3.1

 

Installation Kit 

The installation kit consists of the following items to be used during 

the installation procedure: 

 

One mounting template 

 

Two pan head screws and wall plugs 

 

One L-shaped security screw tool 

 

One security screw 

3.2

 

Mounting the AY-x20 Reader 

Before mounting, you should determine the best location for the 

reader. 
To mount the reader: 
1.

 

Peel off the back of the self-adhesive mounting label template and 
place it at the required mounting location. 

2.

 

Using the template as a guide, drill two holes (sizes indicated on 
the template) used for mounting the reader onto the surface. 

3.

 

Insert a suitable wall plug into each hole. 

4.

 

Drill a 10-mm (7/16”) hole for the cable. If mounting on metal, 
place a grommet or electrical tape around the edge of the hole. 

5.

 

Wire the reader to the controller as described in Sectio

 4

. A linear 

type power supply is recommended. 

6.

 

Remove the reader's snap-off front cover to reveal the two screw 

holes (see Figure 2 ). 

Figure 2: Removing the Top Cover 

 

7.

 

Align the two holes of the reader with those drilled in the wall and 

firmly attach the reader to the wall with two screws, whose size is 

indicated on the template. 

8.

 

Relocate the front cover onto the reader. 

 

The reader can also be mounted using strong epoxy glue. After 

application, the reader should be firmly held in place until the 
glue dries. 

 

 

Card readers are to be used with control panels whose power 
supply is UL Listed Class 2 or equivalent. 

4.

 

Wiring 

The AY-x20 is supplied with a 10-conductor 18” pigtail. 
To connect the reader to the controller: 
1.

 

Prepare the reader cable by cutting its jacket back about 3 cm 
(1¼") and strip the insulation from the wires about 1.2 cm (½"). 

2.

 

Prepare the controller cable by cutting its jacket back 3 cm (1¼") 

and strip the insulation from the wires about 1.2 cm (½"). 

3.

 

Splice the reader’s pigtail wires to the corresponding controller 

wires (as indicated in Table 1) and cover each joint with insulating 
tape. 

4.

 

If the tamper output is being utilized, connect the purple wire to 

the correct input on the controller. 

5.

 

Trim and cover all unused conductors. 

 

 

The individual wires from the reader are color-coded according the 
Wiegand standard. 

 

When using a separate power supply for the reader, this supply 
and that of the controller must have a common ground. 

 

The reader’s cable shield wire should be preferably attached to an 
earth ground, or a signal ground connection at the panel, or 

power supply end of the cable. This configuration is best for 
shielding the reader cable from external interference. 

Table 1: Wiring 

Wire Color 

Wiegand 26-Bit Output 
Mode 

Clock & Data Output 
Mode 

Red 

+DC 

+DC 

Black 

Ground 

Ground 

Green 

Data 0 

Data 

White 

Data 1 

Clock 

Orange 

Green LED 

Green LED 

Brown 

Red LED 

Red LED 

Yellow 

Buzzer 

Buzzer 

Blue 

Hold 

Hold 

Purple 

Tamper 

Tamper 

Grey 

Open Input 

Connected to GND 

 