Input and Output Connections
AC-825IP Hardware Installation and User Guide
31
4.
Input and Output Connections
This chapter describes the AC-825IP access control panel's input and output
connections.
4.1
Input Types
There are four input types:
Normally Closed (N.C.)
Normally Open (N.O.)
Single EOL resistor
Double EOL resistor
Supervised inputs have three states:
Normal
Abnormal
Trouble
The Trouble state is caused by either tampering with the input circuit or by a
faulty hardware installation. Once an input is configured as a supervised input,
add a resistor of 2.2 k
Ω
, 8.2 k
Ω
, or both on the input circuit. See the following
diagrams.
4.1.1
Normally Open Input Connection
A Normally Open Input has 2 states:
Switch Open – Normal State:
Loop resistance = Infinite (open circuit)
Switch Closed – Abnormal State:
Loop resistance = 0 (short circuit)
Figure 23: Normally Open Input Connection
4.1.2
Normally Closed Input Connection
A Normally Closed Input has two states:
Switch Closed – Normal State:
Loop resistance = 0 (short circuit)
Switch Open – Abnormal State:
Loop resistance = Infinite (open circuit)