AC-215
Single and Double Door Access Control Unit
Installation Manual
Страница 1: ...2012 October AC 215 Single and Double Door Access Control Unit Installation Manual ...
Страница 2: ...erty rights covering the subject matter in this manual TEXTS IMAGES AND ILLUSTRATIONS INCLUDING THEIR ARRANGEMENT IN THIS DOCUMENT ARE SUBJECT TO THE PROTECTION OF COPYRIGHT LAWS AND OTHER LEGAL RIGHTS WORLDWIDE THEIR USE REPRODUCTION AND TRANSMITTAL TO THIRD PARTIES WITHOUT EXPRESS WRITTEN PERMISSION MAY RESULT IN LEGAL PROCEEDINGS The furnishing of this manual to any party does not give that par...
Страница 3: ... Unit 13 2 1 2 Outputs 13 2 1 3 Inputs 13 2 1 4 Indicators and Annunciators 13 2 1 5 Environmental Specifications 13 2 1 6 Mechanical Specifications 13 3 Inputs and Outputs 14 3 1 Inputs 14 3 1 1 Release to Exit Button REX 14 3 1 2 Door Monitor 14 3 1 3 Tamper 15 3 1 4 General 15 3 1 5 Outputs 15 3 1 6 Door Lock 15 3 1 7 Door Alarm 15 3 1 8 Auxiliary 16 3 1 9 General 16 3 1 10 Card Readers 16 3 1 ...
Страница 4: ...ng 25 6 1 Inputs 25 6 2 Outputs 25 6 2 1 Power Supply 26 6 3 AC 215 Access Control Panel Diagram 27 6 4 Reader 28 7 Accessories Proximity Readers 29 7 1 AY C09 AY D09 PIN Readers 29 7 2 AY C11 AY D11 Prox Readers with Bell 29 7 3 AY C11 AY D11 Prox Readers 30 7 4 AY H12 AY J12 AY K12 AY L12 AY M12 Prox Readers 30 7 5 AY C19 AY D19 PIN Prox Readers 31 7 6 AY L23 RF Reader 31 A Connecting between MD...
Страница 5: ...Connections PC Side 36 B 4 Connections AC 215 Panel Side 36 B 5 MD N33 Configuration with AxTrax AS 525 37 B 6 PC modem configuration and initialization 37 B 7 Remote modem configuration and initialization 39 B 8 Remote Modem Status 40 B 9 Restoring factory default configuration 41 C Power Supply Specifications 42 D Limited Warranty 43 ...
Страница 6: ...23 Figure 3 MD N32 Configuration Connecting a Single Panel 24 Figure 4 Connecting Multiple Access Control Panels with MD N32 24 Figure 5 Wiring Four AC 215 Inputs 25 Figure 6 Door Lock Fail Closed 26 Figure 7 Door Lock Fail Open 26 Figure 8 AC 215 Wiring to Power Supply 27 Figure 9 AC 215 Wiring Communications 27 Figure 10 Reader Cable Coloring 28 ...
Страница 7: ...List of Tables AC 215 Installation Manual vii List of Tables Table 1 DIP Switches and their Functions 18 Table 2 Switch Baud Rates 18 Table 3 Available Panel Addresses 20 Table 4 RS 232 Connection 22 ...
Страница 8: ...tion of the system with the maximum number of functions including future options Therefore not all functions described in this manual may be available in the specific system and or product configuration you purchased Incorrect operation or installation or failure of the user to effectively maintain the system relieves the manufacturer and seller from all or any responsibility for consequent noncom...
Страница 9: ...e controller and up to 512 doors 256 networks and 5000 users when used as a networked controller using the AxTrax AS 525 software The AxTrax AS 525 software which is user friendly and intuitive defines settings and event logs A single server communicating to and from the ACU can serve unlimited network clients The system s database is saved in the server The database can be set to back up and can ...
Страница 10: ...S 485 232 Converter AC 215 Single Door Up to 32 ACUs AC 215 AC 215 Single Door AC 215 Double Door RS485 RS232 RS485 RS485 Door Monitor Door 2 Maglock Exit button Reader Door 4 Exit button Reader Keypad and Door Release 2 readers for Reader In and Reader Out Door 3 Door 1 Reader Keypad and Door Release ...
Страница 11: ...rammable relock when opening closing doors Man trap door in double door configuration Built in sounder generator for chime bell and siren signals 1 1 2 System Up to 256 access control units Up to 256 networks with one controller per network Up to 32 ACU in every network 64 doors in every network Up to 5000 users with rights up to 25000 users recorded 5000 log events 64 holidays copied from MS Outl...
Страница 12: ... downloaded to the ACU and event logs which are uploaded to the PC to generate reports A single server which communicates to and from the ACU can serve unlimited network clients The system s database is saved in the server The database can be set to backup and can import export previous configurations Clients are able to modify the database for example define new employees and their access permiss...
Страница 13: ... General Inputs High impedance active low inputs Maximum voltage 5 VDC Reader s Electrical requirements Voltage 12 VDC Max Current 300 mA 2 1 4 Indicators and Annunciators Visual 8 on board LEDs as well as three PS LEDs power Low Battery output V Fail Audio Built in sounder Bell Chime and Siren Speaker s Electrical Characteristics 8 Ohm 250 mW 2 1 5 Environmental Specifications Operating Temperatu...
Страница 14: ...2 Door Monitor The Door Monitor connects to a door s micro switch for door status monitoring The following should be defined Single door controller Door 1 IN1A Double door controller Door 1 IN 1A Door 2 IN 2A Two alarm states can be generated Forced alarm When the door is forcibly opened by unauthorized persons Door held open alarm When the door is open for a period exceeding the lock strike progr...
Страница 15: ...ays Their contacts are voltage free and rated 5A at 12V AC or DC This indicates that output is very versatile and can operate virtually any electrical equipment including Fail Open and Fail Close locks electric gates and so on 3 1 5 Outputs We recommend using a suppression diode for all outputs 3 1 6 Door Lock There are two types of door locking devices Fail open fail secure Fail close fail safe T...
Страница 16: ...ing should be defined Single door controller Door 1 OUT2A The output has three activation modes Follow input output follows the input state Toggle active for every change in the output trigger the trigger changes state Time active for a specified time and closes when the timer ends 3 1 10 Card Readers Two card readers can be connected to the ACU The following should be defined Single door controll...
Страница 17: ... should be defined Single door controller Door 1 Keypad Reader 1 IN OUT Keypad Reader 2 IN OUT Double door controller Door 1 Keypad Reader 1 IN OUT Door 2 Keypad Reader 2 IN OUT The keypad type must be a Rosslare format keypad A keypad has to be connected for any reader mode that requires PIN code entries such as Card or PIN PIN only or Card and PIN Secured mode ...
Страница 18: ...ch numbers and their functions Table 1 DIP Switches and their Functions DIP Switch Function 1 2 Set ACU baud rate 3 Sets ACU type single door or double door controller 4 8 Set ACU address 4 1 ACU Baud Rate The ACU serial port baud rate set in dipswitches one and two defines the communication speed for connecting with a PC in a network connection The following lists switch 1 and 2 status and baud r...
Страница 19: ...rs IN and OUT as follows Outputs Door lock strike Auxiliary output Alarm output General purpose output Inputs Release to exit Door monitor input Tamper input General purpose input For more information see Chapter 3 4 2 2 Double Door Controller This access type has two readers IN and OUT as follows Outputs Door 1 lock strike Door 1 alarm output Door 2 lock strike Door 2 alarm output Inputs Release ...
Страница 20: ...4 Switch 5 Switch 6 Switch 7 Switch 8 1 Off Off Off Off Off 2 Off Off Off Off On 3 Off Off Off On Off 4 Off Off Off On On 5 Off Off On Off Off 6 Off Off On Off On 7 Off Off On On Off 8 Off Off On On On 9 Off On Off Off Off 10 Off On Off Off On 11 Off On Off On Off 12 Off On Off On On 13 Off On On Off Off 14 Off On On Off On 15 Off On On On Off 16 Off On On On On 17 On Off Off Off Off 18 On Off Off...
Страница 21: ...ings Configuration AC 215 Installation Manual 21 Address Switch 4 Switch 5 Switch 6 Switch 7 Switch 8 27 On On Off On Off 28 On On Off On On 29 On On On Off Off 30 On On On Off On 31 On On On On Off 32 On On On On On ...
Страница 22: ...e AxTrax AS 525 software By default the default is set to 9600 for direct connection to the PC using the standard RS 232 interface 5 1 1 RS 232 Connection Table 4 RS 232 Connection ACU DB9 Connector DB25 Connector GND Pin 5 Pin 7 Tx Pin 2 Pin 3 Rx Pin 3 Pin 2 DTR Pin 4 Pin 20 The RS232 connection can only be used for one ACU The distance between the PC and ACU can be no more than 150 feet 50 meter...
Страница 23: ...lowing another J1 must be in the RS485 position 5 1 4 Termination Resistors At each end of the data line a termination resistor of 130 Ohm is required across the L1 and L2 connections 5 2 Modem The PC modem connection used to control the ACU is assigned in the AxTrax AS 525 software s Network Properties dialog box The modem is used when the distance between the ACU and the PC is greater than the r...
Страница 24: ... address in the Local Area Network The following type of connection is used when a LAN network already exists and therefore the long RS485 network is not required This schematic illustrates the connection of a single AC 215 to the PC using the LAN network MD N32 must be first configured by Rosslare s Netconfig software The setting is stored in a non volatile memory in the MD N32 Figure 3 MD N32 Co...
Страница 25: ...ing for four AC 215 inputs For further details see Chapter 3 Figure 5 Wiring Four AC 215 Inputs 6 2 Outputs Figure 6 and Figure 7 illustrate wiring for two main types of 12VDC electric release mechanisms Other electrical devices can be switched using the voltage free relay contacts ...
Страница 26: ...e 8 illustrates wiring between the PS 14 power supply and the AC 215 It is recommended to add a 12 VDC lead acid backup battery to backup power if the main fails If the main output is 12 VDC wire it to the PS 14 otherwise support your power supply according to output requirements For further information see Section 2 1 2 ...
Страница 27: ...e 8 AC 215 Wiring to Power Supply 6 3 AC 215 Access Control Panel Diagram Figure 9 presents a complete view of the AC 215 control panel s PCB including all connector buttons and LED schematics not to scale Figure 9 AC 215 Wiring Communications ...
Страница 28: ... a limited cable The color of the cable covering represents the cable s function When extending cable distance be careful with the color of the cable cover The distance is limited by the Wiegand standard Figure 10 Reader Cable Coloring Key V Red Black D0 Green D1 White G LED Brown Tamper Purple ...
Страница 29: ...r Audible buzzer indicator Built in tamper w Rosslare controllers Includes bell button w Rosslare controllers 7 2 AY C11 AY D11 Prox Readers with Bell Reading distance 8 to 10cm RF modulation ASK at 125 kHz For indoor use Slim stylish design USA gang box Bi color light indicator Audible buzzer indicator Built in tamper w Rosslare controllers Includes bell button w Rosslare controllers ...
Страница 30: ...ng box Bi color light indicator Audible buzzer indicator w Rosslare controllers Built in tamper w Rosslare controllers 7 4 AY H12 AY J12 AY K12 AY L12 AY M12 Prox Readers Reading distance 7 to 12cm RF modulation ASK at 125 kHz For outdoor use Slim stylish design UK or USA gang box Mullion Bi color light indicator Includes LED control input Audible buzzer indicator Built in tamper output ...
Страница 31: ...SA gang box Bi color light indicator Audible buzzer indicator Built in tamper w Rosslare controllers Includes bell button w Rosslare controllers 7 6 AY L23 RF Reader Read range 70 meters 200 feet For outdoor use waterproof Frequency 433MHz Slim stylish design Mullion Bi color LED indicator LED control Audible buzzer indicator Size 145mm x 43mm x 20mm Used with the SA 26 wireless remote ...
Страница 32: ...he PC to the LAN network with regular network cable If the PC is already identified and known in the local network it is already connected and you do not need any further installation A 4 Connections AC 215 Panel Side 1 Connect a 9 VDC adapter to the MD N32 Check that the power LED Red is on 2 Connect the MD N32 to the LAN by using a regular network cable through the MD N32 s RJ 45 connector Check...
Страница 33: ...hing is complete 3 Click OK 4 Select the suitable MAC address from the MD N32 list The MD N32 s MAC address should be labeled on the MD N32 s box 5 In the Configuration area type the IP Address and Subnet that the network administrator supplied you 6 In the Port field enter 1000 7 In the Speed area select the speed of your serial connection 9600 19200 38400 57600 ...
Страница 34: ... Manual 8 Click Apply to send the configuration to the unit and wait for following message 9 Click OK to start verification process and wait for the following message 10 Click OK twice and verify that the configuration was accepted by the AxTrax AS 525 software ...
Страница 35: ... N32 and AC 215 AC 215 Installation Manual 35 The MD N32 and AxTrax AS 525 software are now configured ready for testing From this stage you can continue working per the procedure for adding a new panel to the AxTrax AS 525 ...
Страница 36: ...the panel must initialize at PC running the AxTrax AS 525 software B 3 Connections PC Side 1 Connect a 9 VDC adapter to the first MD N33 2 Make sure that the power LED Red is on 3 Connect the PC using a free COM port to the MD N33 with cross serial cable 4 Connect the MD N33 s RJ11 jack to telephone line using the telephone cable B 4 Connections AC 215 Panel Side 1 Connect a 9 VDC adapter to the s...
Страница 37: ...e AxTrax AS 525 software for more details see the AxTrax user manuals The network type should be selected as Modem B 6 PC modem configuration and initialization 1 Click the Configuration tab to get the Modem configuration screen 2 In the Dialing section a In the Remote modem phone number field enter the destination telephone number to call ...
Страница 38: ...ndition can be chosen Disconnect by schedule end or Disconnect on upload complete It is allowed when the selected time zone is different than the default time zones Always Never 3 In the Settings section For most applications the default initialization string of AS 525 is enough The initialization string is displayed in the window Adding or editing initialization string is allowed by clearing Use ...
Страница 39: ...The initialization string is displayed in the window Adding or editing initialization string is allowed by uncheck Use default and type the AT command in the Initialization string window 3 Set the number of rings before the PC modems will answer 4 Connect the remote modem to the PC via the selected com port and click Apply to initialize the PC modem 5 Click OK for the successful initialization If ...
Страница 40: ...igured ready for testing From this stage you can continue working per the AxTrax AS 525 adding new panel procedure B 8 Remote Modem Status When a panel is connected to a modem network you can see the status of the modem by clicking the phone icon in the toolbar There is a manual option to dial or disconnect the modem ...
Страница 41: ...nd readers configuration to factory default and clears all the users properties To return to default 1 Turn off the supply power 2 It is recommended to disconnect the doors and readers wiring 3 Connect Data 0 Data 1 and Tamper inputs to GND in both Reader 1 and 2 totally 6 wires 4 Power up the supply power for few seconds and wait for the control LEDs to flash 5 Turn off the supply power 6 Connect...
Страница 42: ...ns Input Voltage 16 VAC 2 5 A From Transformer Backup Battery Charger 12 VDC 300 mA From Transformer Output Voltage 1 13 8 V Access control panel Output Voltage 2 12 VDC 0 5 A From ACU to lock strike Output Voltage 3 12 VDC 1 5 A Power Supply Indication Tamper Output open collector Indicates faulty power Power LEDs Power In AC Green LED1 Main power Power Out DC Red LED2 Low voltage Charger BAT Red...
Страница 43: ...s of this warranty Unless otherwise requested by a ROSSLARE representative return of the failed product s is not immediately required If ROSSLARE has not contacted the Customer within a sixty 60 day holding period following the delivery of the warranty claim Customer will not be required to return the failed product s All returned Product s as may be requested at ROSSLARE S sole discretion shall b...
Страница 44: ...ampering with the Product if Product disassembled or repaired in such a manner as to adversely affect performance or prevent adequate inspection and testing to verify any warranty claim ROSSLARE does not warrant the installation maintenance or service of the Product Service life of the product is dependent upon the care it receives and the conditions under which it has to operate In no event shall...
Страница 45: ...pport na rosslaresecurity com Europe Rosslare Israel Ltd Rosh HaAyin Israel Tel 972 3 938 6838 Fax 972 3 938 6830 support eu rosslaresecurity com Latin America Rosslare Latin America Buenos Aires Argentina support la rosslaresecurity com China Rosslare Electronics Shenzhen Ltd Shenzhen China Tel 86 755 8610 6842 Fax 86 755 8610 6101 support cn rosslaresecurity com India Rosslare Electronics India ...