Quick Installation Guide
00825-0100-4750, Rev BA
June 2009
Rosemount 8750WA
7
S
TEP
3: M
OUNTING
Upstream/Downstream Piping
To ensure specification accuracy over widely varying process conditions, install the sensor a
minimum of five straight pipe diameters upstream and two pipe diameters downstream from
the electrode plane (see Figure 3).
The 8750WA may be installed with as few as zero pipe diameters upstream. Consult the
factory for performance in applications with less than ideal straight runs. Sensors can be
installed with as few as zero diameters of straight run.
Flow Direction
The sensor should be mounted so the FORWARD end of the flow arrow, shown on the
sensor identification tag, points in the direction of flow through the sensor.
Sensor Orientation
The sensor should be installed in a position that ensures the sensor remains full during
operation. Vertical installation allows upward process fluid flow and keeps the
cross-sectional area full, regardless of flow rate. Horizontal installation should be restricted
to low piping sections that are normally full. In these cases, orient the electrode plane to
within 45 degrees of horizontal.
Figure 3. Upstream and Downstream Straight Pipe Diameters
5 Pipe Diameters
2 Pipe Diameters
Flow
4750RevBAQIG.fm Page 7 Thursday, July 16, 2009 3:52 PM
Содержание 8750WA
Страница 37: ...Quick Installation Guide 00825 0100 4750 Rev BA June 2009 Rosemount 8750WA 37 ...
Страница 38: ...Quick Installation Guide 00825 0100 4750 Rev BA June 2009 Rosemount 8750WA 38 ...
Страница 39: ...Quick Installation Guide 00825 0100 4750 Rev BA June 2009 Rosemount 8750WA 39 ...
Страница 40: ...Quick Installation Guide 00825 0100 4750 Rev BA June 2009 Rosemount 8750WA 40 ...