Safety Instrumented Systems (4-20 mA only)
May 2016
Safety Instrumented Systems (4-20 mA only)
7.
Perform a one-point level measurement verification of the device. Verify the
current level measurement with an independent measurement such as the BPCS
level-sensor or a manual reading.
This step verifies that the analog output is correct in the operating range and that the
Primary Variable is properly configured.
Note that the applied level has to be between Upper and Lower Range values,
otherwise the device enters alarm mode. If level is outside Maximum Measuring
Range, the level reading accuracy may be reduced. For best performance, use the
4-20 mA range points as calibration points. See
.
Figure 8-2. Range Values
8.
Remove the bypass and otherwise restore normal operation.
For troubleshooting the transmitter, see
Section 7: Service and Troubleshooting
4mA
20mA
Reduced accuracy
Reduced accuracy
R
ange 0 -100 %
Upper Blind Zone
Lower Blind Zone
Maximum Measuring Range
Содержание 5300 Series
Страница 2: ......
Страница 12: ...Reference Manual 00809 0100 4530 Rev DD Contents May 2016 xii Contents ...
Страница 94: ...80 Reference Manual 00809 0100 4530 Rev DD Electrical Installation May 2016 Electrical Installation ...
Страница 162: ...148 Reference Manual 00809 0100 4530 Rev DD Operation May 2016 Operation ...
Страница 214: ...200 Reference Manual 00809 0100 4530 Rev DD Service and Troubleshooting May 2016 Service and Troubleshooting ...
Страница 310: ...Product Certifications May 2016 Reference Manual 00809 0100 4530 Rev DD 296 Product Certifications ...
Страница 358: ...Level Transducer Block May 2016 Reference Manual 00809 0100 4530 Rev DD 344 Level Transducer Block ...
Страница 431: ...5 Reference Manual 00809 0100 4530 Rev DD May 2016 ...