Quick Installation Guide
00825-0100-4809, Rev DB
December 2009
Flanged 485 Annubar
13
S
TEP
6
CONTINUED
...
Table 4. Description of Impulse Valves and Components
Recommended Installations For Remote Mount Transmitters
Gas Service
Secure the transmitter above the sensor to prevent condensable liquids from collecting in
the impulse piping and the DP cell.
Name
Description
Purpose
Components
1
Transmitter
Reads Differential Pressure
2
Manifold
Isolates and equalizes electronics
Manifold and Impulse Valves
PH
Primary Sensor
(1)
(1)
High Pressure
High and low side pressure process connections.
PL
Primary Sensor
(2)
(2)
Low Pressure
DVH
Drain/Vent Valve
(1)
Drains (for gas service) or vents (for liquid or steam service) the DP
sensor diaphragms
DVL
Drain/Vent Valve
(2)
MH
Manifold
(1)
Isolates high side or low side pressure from the process
ML
Manifold
(2)
MEH
Manifold Equalizer
(1)
Allows high and low pressure side access to the vent valve, or for
isolating the process fluid
MEL
Manifold Equalizer
(2)
ME
Manifold Equalizer
Allows high and low side pressure to equalize
MV
Manifold Vent Valve
Vents process fluid
Figure 11. Horizontal Gas
Figure 12. Vertical Gas