Rosemount 3051 Скачать руководство пользователя страница 4

January 2017

4

Quick Start Guide

2.0

Transmitter installation

2.1

Mount the transmitter

Liquid applications

Coplanar In-line

1.  Place taps to the side of the 

line.

2. Mount beside or below the 

taps.

3. Mount the transmitter so 

that the drain/vent valves 
are oriented upward.

Gas applications

1. Place taps in the top or side 

of the line.

2. Mount beside or above the 

taps.

Steam applications

1. Place taps to the side of the 

line.

2. Mount beside or below the 

taps.

3. Fill impulse lines with 

water.

Flow

Flow

Flow

Содержание 3051

Страница 1: ... Rosemount 3051 Pressure Transmitter and Rosemount 3051CF Series Flowmeters with 4 20 mA HART Revision 5 and 7 Protocol Note Before installing the transmitter confirm the correct device driver is loaded on the host systems See page 3 for system readiness ...

Страница 2: ...th intrinsically safe or non incendive field wiring practices In an Explosion proof Flameproof installation do not remove the transmitter covers when power is applied to the unit Process leaks may cause harm or result in death To avoid process leaks only use the O ring designed to seal with the corresponding flange adapter Electrical shock can result in death or serious injury Avoid contact with t...

Страница 3: ...ctionality Software release date NAMUR software revision 1 1 NAMUR software revision is located on the hardware tag of the device In accordance with NE53 revisions of the least significant level X of 1 0 X do not change functionality or operation of the device and will not be reflected in this device revision history HART software revision 2 2 HART software revision can be read using a HART capabl...

Страница 4: ...e of the line 2 Mount beside or below the taps 3 Mount the transmitter so that the drain vent valves are oriented upward Gas applications 1 Place taps in the top or side of the line 2 Mount beside or above the taps Steam applications 1 Place taps to the side of the line 2 Mount beside or below the taps 3 Fill impulse lines with water Flow Flow Flow ...

Страница 5: ...Quick Start Guide 5 January 2017 Figure 1 Panel and Pipe Mounting Panel mount 1 1 5 16 11 2 panel bolts are customer supplied Pipe mount Coplanar flange Traditional flange Rosemount 3051T ...

Страница 6: ...olts are typically carbon steel or stainless steel Confirm the material by viewing the markings on the head of the bolt and referencing Table 2 on page 7 If bolt material is not shown in Table 2 contact a local Emerson representative for more information Use the following bolt installation procedure 1 Carbon steel bolts do not require lubrication and the stainless steel bolts are coated with a lub...

Страница 7: ...the vent path free of any obstruction including but not limited to paint dust and lubrication by mounting the transmitter so that the process can drain away Figure 3 In line Gage Low Side Pressure Port A Low side pressure port atmospheric reference Installing high pressure coned and threaded connection The transmitter comes with an autoclave connection designed for high pressure applications Follo...

Страница 8: ...using rotation set screw using a 5 64 in hex wrench 2 Turn the housing left or right maximum up to 180 from its original position 1 Note Over rotating can damage the transmitter 3 Re tighten the housing rotation set screw to no more than 7 in lb when desired location is reached Figure 4 Transmitter Housing Set Screw A Housing rotation set screw 5 64 in 2 3 Set the switches Set alarm and security s...

Страница 9: ...nsmitter cover The cover must be fully engaged to comply with explosion proof requirements Figure 5 Transmitter Electronics Board A Alarm B Security 2 4 Connect the wiring and power up Figure 6 Transmitter Wiring Diagrams 4 20 mA A 24 Vdc supply B RL 250 C Current meter optional Shielded twisted pair cable should be used for best results Use 24 AWG or larger wire that does not exceed 5 000 feet 15...

Страница 10: ... close and insulated from touching the transmitter housing b Connected to the next shield if cable is routed through a junction box c Connected to a good earth ground at the power supply end 6 If transient protection is needed refer to section Grounding for transient terminal block on page 11 for grounding instructions 7 Plug and seal unused conduit connections 8 Replace the housing cover Figure 7...

Страница 11: ...AMS Device Manager Verifying configuration with a Field Communicator A Rosemount 3051 DD must be installed on the Field Communicator to verify configuration Fast Key sequences for the latest DD are shown in Table 3 on page 11 For Fast Key sequences using legacy DD s contact your local Emerson Process Management representative Note Emerson recommends installing the latest DD to access the complete ...

Страница 12: ...nal buttons Descriptor 2 2 7 1 5 2 2 7 1 4 Digital to Analog Trim 4 20 mA Output 3 4 2 3 4 2 Disable Configuration Buttons 2 2 6 3 2 2 6 3 Rerange with Keypad 2 2 2 1 2 2 2 1 Loop Test 3 5 1 3 5 1 Lower Sensor Trim 3 4 1 2 3 4 1 2 Message 2 2 7 1 6 2 2 7 1 5 Scaled D A Trim 4 20 mA Output 3 4 2 3 4 2 Sensor Temperature Trend 3051S 3 3 3 3 3 3 Upper Sensor Trim 3 4 1 1 3 4 1 1 Digital Zero Trim 3 4...

Страница 13: ...u with limited capability The following procedures will switch the HART revision mode from the generic menu 1 Manual Setup Device Information Identification Message a To change to HART Revision 5 Enter HART5 in the Message field b To change to HART Revision 7 Enter HART7 in the Message field Note See Table 3 on page 11 to change HART Revision when the correct device driver is loaded Table 4 LOI Bu...

Страница 14: ...ensor zero The LRV is unaffected The pressure value will be zero on display and HART output 4 mA point may not be at zero This requires that the factory calibrated zero pressure is within a range of 3 of the URL 0 3 URL Example URV 250 inH2O Applied Zero Pressure 0 03 250 inH2O 7 5 inH2O compared to factory settings values outside this range will be rejected by the transmitter Trimming with a Fiel...

Страница 15: ...analog zero and span option D4 1 Set the transmitter pressure 2 Press and hold the Zero button for two seconds to perform an analog zero trim Perform trim with digital zero option DZ 1 Set the transmitter pressure 2 Press and hold the Zero button for two seconds to perform a digital zero trim 3 0 Safety instrumented systems installation For safety certified installations refer to Rosemount 3051 HA...

Страница 16: ...10 FM Class 3611 2004 FM Class 3810 2005 ANSI NEMA 250 2008 Markings IS CL I DIV 1 GP A B C D CL II DIV 1 GP E F G Class III DIV 1 when connected per Rosemount drawing 03031 1019 NI CL 1 DIV 2 GP A B C D T4 50 C Ta 70 C HART T5 50 C Ta 40 C HART T4 50 C Ta 60 C Fieldbus PROFIBUS Type 4x Special Conditions for Safe Use X 1 The Rosemount 3051 Transmitter housing contains aluminum and is considered a...

Страница 17: ...ision 1 Groups B C and D Suitable for Class I Zone 1 Group IIB H2 T5 Dust Ignitionproof for Class II and Class III Division 1 Groups E F and G Class I Division 2 Groups A B C and D Suitable for Class I Zone 2 Group IIC Type 4X Factory Sealed Single Seal See drawing 03031 1053 Europe E8 ATEX Flameproof and Dust Certificate KEMA00ATEX2013X Baseefa11ATEX0275X Standards EN60079 0 2012 A11 2013 EN60079...

Страница 18: ...to protect it from impact or abrasion if located in Zone 0 3 Some variants of the equipment have reduced markings on the nameplate Refer to the Certificate for full equipment marking IA ATEX FISCO Certificate BAS97ATEX1089X Standards EN60079 0 2012 EN60079 11 2009 Markings II 1 G Ex ia IIC T4 Ga 60 C Ta 60 C Special Conditions for Safe Use X 1 The apparatus is not capable of withstanding the 500 V...

Страница 19: ...1 This device contains a thin wall diaphragm Installation maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected The manufacturer s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime 2 Flameproof joints are not intended for repair 3 Non standard paint options may cause ri...

Страница 20: ...installing the apparatus 2 It is a condition of safe use that the above input parameters shall be taken into account during installation 3 It is a condition of manufacture that only the apparatus fitted with housing covers and sensor module housing made out of stainless steel are used in Group I applications N7 IECEx Type n Certificate IECEx BAS 09 0077X Standards IEC60079 0 2011 IEC60079 15 2010 ...

Страница 21: ... suitability for the specific application I2 INMETRO Intrinsic Safety Certificate UL BR 13 0584X Standards ABNT NBR IEC60079 0 2008 Errata 1 2011 ABNT NBR IEC60079 11 2009 Markings HART Ex ia IIC T5 T4 Ga T5 60 C Ta 40 C T4 60 C Ta 70 C Fieldbus PROFIBUS Ex ia IIC T4 Ga 60 C Ta 60 C Special Conditions for Safe Use X 1 If the equipment is fitted with an optional 90 V transient suppressor it is not ...

Страница 22: ...aximum ambient temperature is 80 C 2 The earth connection facility in the enclosure should be connected reliably 3 Cable entry certified by notified body with type of protection Ex d IIC in accordance with GB3836 1 2000 and GB3836 2 2000 should be applied when installed in a hazardous location When used in combustible dust environment cable entry in accordance with IP66 or higher level should be a...

Страница 23: ...d apparatus The cables between Rosemount 644 and associated apparatus should be shielded cables the cables must have insulated shield The shielded cable has to be grounded reliably in a non hazardous area 4 Transmitters comply with the requirements for FISCO field devices specified in IEC60079 27 2008 For the connection of an intrinsically safe circuit in accordance with FISCO Model FISCO paramete...

Страница 24: ... HART TC20579 TC20580 TC20581 TC20582 Fieldbus Markings Ex d IIC T5 Technical Regulations Customs Union EAC EM EAC Flameproof Certificate RU C US GB05 B 01197 Markings Ga Gb Ex d IIC T5 T6 X T5 60 C Ta 80 C T6 60 C Ta 65 C Special Condition for Safe Use X 1 See certificate for special conditions IM EAC Intrinsically Safe Certificate RU C US GB05 B 01197 Markings HART 0Ex ia IIC T4 T5 Ga X T4 60 C ...

Страница 25: ...reau of Shipping ABS Type Approval Certificate 09 HS446883A 5 PDA Intended Use Marine and Offshore Applications Measurement of either gauge or absolute pressure for liquid gas and vapor SBV Bureau Veritas BV Type Approval Certificate 23155 Requirements Bureau Veritas Rules for the Classification of Steel Ships Application Class notations AUT UMS AUT CCS AUT PORT and AUT IMS Pressure transmitter ty...

Страница 26: ...r LR Type Approval Certificate 11 60002 Application Environmental categories ENV1 ENV2 ENV3 and ENV5 C5 Custody Transfer Measurement Canada Accuracy Approval Certificate AG 0226 AG 0454 AG 0477 Location classes Temperature D Humidity B Vibration A EMC B Enclosure D ...

Страница 27: ...Quick Start Guide 27 January 2017 Figure 11 Rosemount 3051 Declaration of Conformity ...

Страница 28: ...January 2017 28 Quick Start Guide ...

Страница 29: ...Quick Start Guide 29 January 2017 ...

Страница 30: ...January 2017 30 Quick Start Guide ...

Страница 31: ...y X O O O O O ༣փ㓴Ԧ Housing Assembly X O O X O O Րᝏಘ㓴Ԧ Sensor Assembly X O O X O O ᵜ㺘Ṭ ᦞ SJ T11364Ⲵ㿴ᇊ㘼ࡦ This table is proposed in accordance with the provision of SJ T11364 O Ѫ䈕䜘ԦⲴᡰᴹ 䍘ᶀᯉѝ䈕ᴹᇣ 䍘Ⲵਜ਼䟿 վҾGB T 26572ᡰ㿴ᇊⲴ䲀䟿㾱 O Indicate that said hazardous substance in all of the homogeneous materials for this part is below the limit requirement of GB T 26572 X Ѫ 䈕䜘Ԧᡰ Ⲵᡰᴹ 䍘ᶀᯉ䟼ˈ㠣ቁᴹа 䍘ᶀᯉѝ䈕ᴹᇣ 䍘Ⲵਜ਼䟿儈ҾGB T 26572ᡰ㿴...

Страница 32: ... of Emerson Electric Co AMS Rosemount and Rosemount logotype are trademarks of Emerson DTM is a trademark of the FDT Group HART is a registered trademark of the FieldComm Group NEMA is a registered trademark and service mark of the National Electrical Manufacturers Association PROFIBUS is a registered trademark of PROFINET International PI All other marks are the property of their respective owner...

Отзывы: