Quick Start Guide
11
January 2017
Grounding for transient terminal block
Ground termination is provided on the outside of the electronics housing and
inside the terminal compartment. These grounds are used when the transient
protection terminal blocks are installed. It is recommended that 18 AWG or
larger wire is used to connect housing ground to earth ground (internal or
external).
If the transmitter is currently not wired for power up and communication, follow
Connect the wiring and power up
, step
1
through
8
. When the transmitter is
properly wired, refer to
Figure 7
for internal and external transient grounding
locations.
2.5
Verify configuration
Verify the configuration using any HART capable configuration tool or LOI -
option code M4. Configuration instructions for a Field Communicator and LOI
are included in this step. See Rosemount 3051
Reference Manual
for
configuration instructions using AMS
™
Device Manager.
Verifying configuration with a Field Communicator
A Rosemount 3051 DD must be installed on the Field Communicator to verify
configuration. Fast Key sequences for the latest DD are shown in
Table 3 on
page 11
. For Fast Key sequences using legacy DD's, contact your local Emerson
Process Management representative.
Note
Emerson recommends installing the latest DD to access the complete functionality. Visit
Emerson.com/Field-Communicator
for information on updating the DD Library.
1. Verify device configuration using the fast key sequences in
Table 3
.
a. A check (
) indicates the basic configuration parameters. At minimum,
these parameters should be verified as part of configuration and startup.
Table 3. Device Revision 9 and 10 (HART 7), DD Revision 1 Fast Key Sequence
Function
Fast Key sequence
HART 7
HART 5
Alarm and Saturation Levels
2, 2, 2, 5, 7
2, 2, 2, 5, 7
Damping
2, 2, 1, 1, 5
2, 2, 1, 1, 5
Range Values
2, 2, 2
2, 2, 2
Tag
2, 2, 7, 1, 1
2, 2, 7, 1, 1
Transfer Function
2, 2, 1, 1, 6
2, 2, 1, 1, 6
Units
2, 2, 1, 1, 4
2, 2, 1, 1, 4
Burst Mode
2, 2, 5, 3
2, 2, 5, 3
Custom Display Configuration
2, 2, 4
2, 2, 4
Date
2, 2, 7, 1, 4
2, 2, 7, 1, 3
Содержание 3051
Страница 27: ...Quick Start Guide 27 January 2017 Figure 11 Rosemount 3051 Declaration of Conformity ...
Страница 28: ...January 2017 28 Quick Start Guide ...
Страница 29: ...Quick Start Guide 29 January 2017 ...
Страница 30: ...January 2017 30 Quick Start Guide ...