Quick Installation Guide
00825-0100-4825, Rev CA
February 2006
Rosemount 248
S
TEP
4
CONTINUED
...
Figure 2. Power, Communication, and Sensor Terminals
Ground the Transmitter
Ungrounded Thermocouple, mV, and RTD/Ohm Inputs
Each process installation has different requirements for grounding.
Use the grounding options recommended by the facility for the specific
sensor type, or begin with grounding Option 1 (the most common).
Option 1 (for grounded housing):
1. Connect sensor wiring shield to the transmitter housing.
2. Ensure the sensor shield is electrically isolated from surrounding
fixtures that may be grounded.
3. Ground signal wiring shield at the power supply end.
+
_
Sensor Terminals
Power/Communication
Terminals
24
8\
24
8_
10
a.
ep
s
4–20 mA loop
Sensor Wires
Shield ground point
Transmitter