Controller functions
RES-403
Page 27
Part 1 of 3: Error messages as of October 2005 (faults)
NOTE:
The error messages shown here are output as faults (constant error voltage at actual value output,
alarm LED lit continuously, alarm relay energized).
Error
code
Act. val.
output
voltage
[V]
Cause
Action if machine
started for first time
Action if machine
already operated, HS
band not changed
101
0.66
No current signal
Fault area
c
Fault area
c
102
1.33
No voltage signal
Fault area
e
Fault area
e
103
2.00
No current / voltage signals
Fault area
d
Fault areas
dk
107
2.66
Temperature step, down
Fault areas
fgh
("loose contact")
Fault areas
fgh
("loose contact")
108
Temperature step, up
307
Temperature too high / low
(
ª
section 6.8)
-
-
308
309
310
201
3.33
No line frequency / line fre-
quency fluctuates
Check power supply
Check power supply
202
Line frequency too high /
fluctuates
203
Line frequency too low /
fluctuates
304
4.00
Heatup time too long
(
ª
section 6.9)
Perform
RESET
Perform
RESET
901
4.66
No line voltage / sync signal
Replace device
Replace device
913
Triac defective
Replace device
Replace device
914
Internal fault, device defective
Replace device
Replace device
915
916
917
Jumper for alarm output incor-
rect
Check jumper
Check jumper
918