background image

Stand by mode. Monitoring pulses.

Under certain conditions, sealing is also possible with the

so-called

procedure. In this mode, the

remaining heat in a sealing element is calculated to be

just enough for the sealing process. This means that in

the timing process, the temperature drops in phase 4 .

The current is cut off when the jaws touch. The heat flows

into the film and "unloads" the heat stored in the heatseal

element, which results in a faster cooling. For this method

to be effective the thickness, therefore the mass, of the

heatseal element must be great enough to hold the

required total heat.

rest-heat

The pre-set temperature should always be attained

before the sealing jaws make contact. This allows the

sealing element to expand without constraint and

eliminates stressing of the heatseal element ends

(phase 2 ).

R O P E X

R O P E X

R O P E X

R O P E X

INDUSTRIE - ELEKTRONIK GmbH

Page 11

9. IMPULSE SEALING

When the impulse sealing method is employed the start

signal is synchronized with the operating cycles of the

machine. Every heating cycle is followed by a cooling

cycle

. It is Important that the cooling is

effected with jaws closed so that the seal can set and

gain strength and good appearance befor the jaws are

opened. This method is preferred if adequate sealing

time is availabel because the strength and appearance

of the seal are optimized.

Since the heat sealing is a thermodynamically reversible

procedure and is often influenced by time constraints, it

is very important that the relevant parameters; tempera-

ture, time and pressure are very carefully synchronized.

The following diagram shows an example of the timely

setting of each parameter.

Basic rules for Impulse Heatsealing:

A.

with jaws closed

B.

PRECISION TIMING FOR PERFECT HEATSEALS

High performance productivity with perfection

requires coordinated timing between the heatseal

impulse and the jaw action.

The timing chart below describes the relationship of (A) Heating and cooling

cycles. (B) Heatseal Band temperature. (C) Heatseal Jaw action. (D) Power Output.

START

HEATING CYCLE TIME

COOLING CYCLE TIME

TEMP.

SET POINT

COOLING

Phase

1

1

2

2

3

3

4

4

4

5

5

6

6

t

t

t

JAW ACTION

S

S

OPEN

OPEN

CL

OSING

CLOSED

OPENING

CURRENT

(= LED OUTPUT)

I

2

I

MAX

MONITORING

PULSE

MONITORING

PULSE

A

B

C

D

Phase :

Jaws are opening.

Cooling phase:

set-up

Start of cooling time. Time must be allowed for the

seal to

befor jaws are opened.

Power output is

. Temperature remains at set point.

controlled

While jaws are closing, the heatseal band temperature rises to the set

point so that full temperature is reached befor the jaws closed.

START is "OFF"

open

. Jaws are

and the heatseal band is cooling

from the previous cycle. (Monitoring Mode)

Diagram D

shows the rate of current flow during a sealing phase.

This can also be measured with an amp-meter.

Phase

:

1

Phase

:

2

Phase

:

3

Phase

:

4

Phase

und

:

Phase

5

6

Heatseal process:

Start of sealing time. Time must be allowed for the

heat to full penetrate the material to be sealed.

9.1

The system should be designed to drive the heatseal

element to the preset temperature in minimum time.

The total system, principally the secondary voltage,

must be optimized to achieve the best result.

.

C.

Our application service will give you the necessary

data for your special application

The cool down of the heatseal element while still

under the force of the jaws is the main advantage of

impulse sealing (phase 5 ). At the completion of the

heatseal cycle, most of the excess heat will be

absorbed by the jaws. Cooling of the jaws is

sometimes recommended so that they can absorb

enough heat from the heatseal element quickly.

Contrary to the constant heat mode, good thermal

conductivity between the sealing element and the

jaws must be assured by using a thin backup material

behind the heatseal element.

Notice that it is possible to energize the heatseal band

prior to jaw closing because the temperature controller

eliminates the risk of overheating.

Controller "ON" heating up with full secondary voltage,

maximum power.
Controller "ON" and regulating to maintain the preset

temperature while the jaws are still open.

Controller "ON" and regulating. Increased power is

being supplied to maintain the preset temperature

during the sealing process.

Controller "OFF" and the heatseal band is cooling,

Содержание Resistron RES-241

Страница 1: ...nd Operation Built in Timers Preferred for General Applications FEATURES TABLE OF CONTENTS 1 APPLICATION AND SHORT DESCRIPTION 2 FUNCTIONS OF THE RES 241 242 2 1 Control Function 2 2 Zero Calibration 2 3 Start Function 2 4 Cycle Timing 2 5 Alarm Function 2 5 1 Alarm Signal 2 5 2 Reset 3 CONTROLS AND INDICATORS 4 PROGRAMMING OF THE TIMING FUNCTIONS 5 EXAMPLE 6 WIRING DIAGRAM 7 OPERATING INSTRUCTION...

Страница 2: ...esired values are entered according to the appropriate units i e and or Numerous functional sequences can be programmed with the dip switches mounted on side of the controller This allows the user to select the best program for any specific heatsealing process Processes that are primarily temperature dependent can be programmed e g closing of the jaw only after full sealing temperature has been re...

Страница 3: ...trimmer with the heatseal element at ambient temperature and the controller in the monitoring mode Z 20 C 68 F After calibration the hand should rest quietly at Z START FUNCTION A heating cycle is initiated with the start function The controller then switches from the monitoring mode to the regulating mode and concurrently starts the timing cycles The START signal can be given in three different w...

Страница 4: ...ond Functions of the RES 241 242 Continuation CYCLING TIMING Heating and cooling cycle time follow each other Depending upon the program selected by use of the DIP switch the either starts with the START signal or when the heating element reaches the pre set temperature see Section 4 Timing Functions Programming The always starts at the end of the heating cycle The maximum time duration for heatin...

Страница 5: ...y Selection LED GREEN for Cooling Time LED RED for Sealing Time DIP Switch to select U2 DIP Switches for Programming of Sealing Process 1 2 3 4 5 6 7 8 9 10 ON 10 Turn ZERO Trimmer for setting Calibration to Z LED is RED when START HAND BUTTON will start controller with a full timing cycle LED RED blinks in monitoring mode remains when controller starts heating cycle LED YELLOW Indicates status of...

Страница 6: ...mperature has been reached 1 2 3 4 5 6 7 8 9 10 ON 1 2 3 4 5 6 7 8 9 10 ON A F 1 2 3 4 5 6 7 8 9 10 ON 1 2 3 4 5 6 7 8 9 10 ON B G 1 2 3 4 5 6 7 8 9 10 ON C 1 2 3 4 5 6 7 8 9 10 ON D 1 2 3 4 5 6 7 8 9 10 ON E 1 2 3 4 5 6 7 8 9 10 ON H 4 1 PROGRAMMING THE OUTPUT RELAY tK Cooling Time tH Heating Time K1 Relay 4 2 PROGRAMMING THE HEATING TIME 4 3 PROGRAMMING FOR CONSTANT HEAT At the initial start sig...

Страница 7: ... the end of the relay K1 opens the valve is deactivated and the jaws open The sealing cycle is complete cooling cycle cooling cycle time This program is the same as example 1 until the end of the heating cycle At the end of the heating cycle the cooling cycle starts and ends only when the has drop below the temperature pre selected on the COOL digital selector switch digits x 10 in C Only then the...

Страница 8: ...5 4 3 12 13 14 15 16 17 18 START SWITCH START 24VDC ALARM INTERNAL ALARM RELAY RES 242 ONLY Normally open max 50V 0 2A U IR R R CURRENT TRANSFORMER HEATSEAL BAND U U1 2 PRI SEC LINE RELAY TERMINALS 100 VDC 1 5A 240 VAC 1 5A 0 K1 2x 47nF 560R POWER TRANSFORMER 6 WIRING DIAGRAM twisted FILTER ...

Страница 9: ... 7 8 9 10 ON Connect the controller as shown in the wiring diagram No special attention must be given to the polarity of the measuring wires for current and voltage as well as the transformer s primary or secondary Section 12 Make sure that there is START signal at See General Installation Instructions VERY IMPORTANT NO ALARM and LED ALARM is red all wiring system must be rechecked for correct and...

Страница 10: ...clockwise if the hand is on the right side turn the trimmer counter clockwise If the ZERO calibration is not possible the meter hand remains on the right side pass the wire only with the heatseal element at ambient temperature through the current transformer a second time in extreme cases a third pass might be necessary This situation might occur when the heatseal element is very long and thin hig...

Страница 11: ...tput START HEATING CYCLE TIME COOLING CYCLE TIME TEMP SET POINT COOLING Phase 1 1 2 2 3 3 4 4 4 5 5 6 6 t t t JAW ACTION S S OPEN OPEN CLOSING CLOSED O P E N I N G CURRENT LED OUTPUT I2 IMAX MONITORING PULSE MONITORING PULSE A B C D Phase Jaws are opening Cooling phase set up Start of cooling time Time must be allowed for the seal to befor jaws are opened Power output is Temperature remains at set...

Страница 12: ... on base for DIN rail 35 x 7 5mm oder 35 x 15mm nach DIN EN 50022 10 OUTLINE DIMENSIONS 147 75 60Hz 50Hz 130 43 32 30 136 147 PANEL JUMPER FOR LINE FREQUENCY 20mm TYPE RES XXX 0 45mm TYPE RES XXX 1 CLEAR COVER GASKET MOUNTING BRACKET TERMINAL BLOCKS OUTLINE DIMENSIONS CLEAR COVER 138 x 68 1 0 0 0 0 7 DIP SWITCH to select U2 PANEL CUTOUT CURRENT TRANSFORMER ...

Страница 13: ...e Every tenth cycle 200 msec at 50Hz or 166 msec at 60Hz In controlling mode Every voltage cycle 20 msec at 50Hz or 16 6 msec at 60Hz Calibrated for heating elements with T 10 x 10 K 5 C bis 45 C Terminal Blocks with plug in connectors IP 20 Controller 1 2 kg 2 64 Ibs Current Transformer 0 15 kg 0 33 Ibs K 4 1 Page 13 11 TECHNICAL SPECIFICATIONS Type of Construction Operating Range of Line Voltage...

Страница 14: ... 230 V 50 60 Hz Line Voltage Standard 230 VAC Option 115 VAC oder 400VAC Temperature Range X 3 0 300 C X 5 0 500 C X 0 X 1 Maximum Load Current see Technical Specifications X 1 Alarm X 2 Alarm without with SERIES RESISTRON Supply Controller with clear front panel gasket and mounting brackets Current transformer ...

Страница 15: ...perature coefficient No additional resistances in the secondary circuit Observe the number of passes twisted No push on connectors Current measuring wires I R Correct dimensions of transformer secondary voltage power duty cycle Controller Set DIP Switch into correct position Set jumper for line frequency into proper position Voltage measuring wire U connected directly to the ends of heatseal eleme...

Отзывы: