Appendix A Specifications
Accura 2350-IDC User Guide
Page 28
ⓒ
2014 Rootech Inc. All Rights Reserved
Appendix A Specifications
Analog Input: 8 DC Current Channels
Ch 1
Ch 2
Ch 3
Ch 4
Ch 5
Ch 6
Ch 7
Ch 8
Port name
IDC
1
IDC
2
IDC
3
IDC
4
IDC
5
IDC
6
IDC
7
IDC
8
Ground
1
IDC
1G
IDC
2G
IDC
3G
IDC
4G
IDC
5G
IDC
6G
IDC
7G
IDC
8G
1. IDC1G , IDC2G
…
IDC8G are different grounds corresponding to each channel.
Item
Description
Connector type
Terminal block
Wire specification
1.5 to 3.5 mm
2
(16 to 12 AWG),
copper or aluminum
Input current
DC current -20 mA to 20 mA
Isolation/channel
AC 2,000 V for 1 minute, 8 channels
(differential inputs, non-isolated between channels)
Input resistance
150
Ω
Measurement accuracy
±
0.5% FS
1
Event
“
Over
”
/
”
Under
”
2
event selectable based on the threshold value for each channel
1. Full Scale (FS) indicates 20 mA.
2.
An “
Over
”
event indicates an event where the measured value rises above the threshold.
An “
Under
”
event
indicates an event where the measured value falls below the threshold. Over and Under current events consist of start
and end events. Either event can be configured.
Item
Description
Power supply
Receives power from Accura 2300[S] through the RJ12 6C communication line
Current consumption
0.11A @ 5V RJ12 power supply
General
Weight
164 g
Excluding mounting wings L/S
167 g
Including mounting wings L/S
Environmental Conditions
Operating temperature
-20 to 70
℃
(-4 to 158
℉
),
Safe operating temperature
1
-20 to 65
℃
(-4 to 149
℉
),
Storage temperature
-20 to 85
℃
(-40 to 185
℉
),
Operating humidity
5 to 95% (non-condensing)
Operating altitude
Up to 2,000 m
1. Compliant with the UL61010-1 standard(3rd edition)
Содержание Accura 2350-IDC
Страница 1: ......