Chapter 2 Accura 2350-DCM Operation/Setup
Accura 2350-DCM User Guide
Page 14
ⓒ
2018 Rootech Inc. All Rights Reserved
Chapter 2 Accura 2350-DCM Operation/Setup
Fig 2.1 Accura 2350-DCM Front
Device Configuration and Operation
Voltage Connection and Control Power Supply
Item
Description
Voltage Connection Terminal
Terminal name
1
Source(S) +, - / Load(L) +, -
Connector type
Bus bar type
Voltage range
DC 12
–
55 V
Accura 2350-DCM-50V Stand-alone operation
DC 0
–
55 V
Accura 2350-DCM-50V Linked operation
DC 0
–
550 V
Accura 2350-DCM-500V Linked operation
Control Power Supply
Power supply
Supplied from Accura 2300[S] with the RJ12 communication line
Bus bar
2
DC 12
–
55 V
Accura 2350-DCM-50V Stand-alone operation
Power consumption
125mA when connected to Accura 2300[S] with the RJ12 communication line
3
40mA @ DC 12V bus bar
Accura 2350-DCM-50V Stand-alone operation
12mA @ DC 48V bus bar
1. The power source side and the load side are indicated as S and L, respectively.
Connections should be made properly according to the indicated po/-). When the polarity is connected in
reverse, voltage and current are measured as negative values.
2. The DCM-50V module receives control power via DC busbar voltage in case of a stand-alone operation.
3. The number of DCM modules that can be connected to Accura 2300[S] is limited to 10. (5 modules connected to each
port.)