Dip[Sag]/Swell Measurement
Half-cycle Refreshed 1-cycle RMS
RMS value for 1-cycle is measured by sliding in half-cycle interval. Time resolution of this 1-cycle RMS value is
half-cycle. By monitoring this 1-cycle RMS value, Dip[Sag]/Swell event is detected.
Fig 5.5 Half-cycle Refreshed 1-cycle RMS Calculation
Half-cycle refreshed 1-cycle RMS
220.0 173.8 110.0 110.0 110.0 173.8 220.0 220.0
Dip[Sag]/Swell Detection
As it is defined in IEC 61000-4-30, Dip[Sag]/Swell of voltage is detected by monitoring the half-cycle
refreshed 1-cycle RMS value. Time resolution of Dip[Sag]/Swell is half-cycle.
Fig 5.6 Voltage Dip[Sag] Detection
1-cycle RMS
220.0
173.8 110.0 110.0 110.0 173.8
220.0 220.0
220.0
Dip theshold = 180.0
Dip start time
Dip end time
Dip duration
Dip end voltage
Dip start voltage
Dip peak voltage (Max. Residual Voltage)