INSTALLATION
ELECTRICAL SPECIFICATIONS
IMPORTANT
** for all other capacities, please consult us.
A main fuse must mandatorily be provided on the power supply.
Fuses not supplied
Cables not supplied
The unit is not designed to withstand weights or stresses from adjacent equipment, pipe work or
constructions. Any foreign weight or stress on the unit structure could lead to a malfunction or a
collapse with dangerous consequences for personnel and property. In such an event, the warranty
shall be null and avoid.
The unit supporting base shall be supplied as indicated in the manual. There could be a risk of
personal injury or damage to property in the event of the unit being incorrectly supported.
The building structure must be capable of carrying the weight of the unit during operation.
The place of installation must not be subject to flooding.
The ROOFTECH should be installed on a flat, clean surface without any obstacles. The surface area
must be sufficient to spread the weight of the unit over the building structure.
Ensure that the recommended free clearances around the unit are maintained to avoid any risk of
malfunctions.
The installer is responsible for providing the weaterproof seal between the building and the ROOFTECH.
The installer must be fully versed in the practice of roof mounted equipments and must comply with
the recommendations and rules detailed in the Technical Directives.
In order to avoid risk of condensation and energy losses, all outdoor ducting and piping must be
insulated.
The unit’s tightness must not be deteriorated by power supply connections.
UNIT WITHOUT HEATING
UNIT WITH HEATING TYPE CH1
PLACE OF INSTALLATION AND REQUIREMENTS
UNIT WITH HEATING TYPE CH2
Models
100
120
140
160
PE
GE
PE
GE
PE
GE
PE
GE
Power supply
3+N /400 /50Hz
Maximum current
A
123
136
127
140
139
152
167
180
Total starting current
A
209.6
223
231.6
245
228.6
242
289.6
303
Fuse rating aM
A
160
160
160
160
160
160
200
200
Models
100
120
140
160
PE
GE
PE
GE
PE
GE
PE
GE
Power supply
3 /400 /50Hz
Capacities **
KW
63
Maximum current
A
233
246
237
250
249
262
277
290
Total starting current
A
319.6
333
341.6
355
338.6
352
399.6
413
Fuse rating aM
A
250
250
250
250
250
315
315
315
Models
100
120
140
160
PE
GE
PE
GE
PE
GE
PE
GE
Power supply
3 /400 /50Hz
Capacities **
KW
105
Maximum current
A
306
319
310
323
322
335
350
363
Total starting current
A
392.6
406
414.6
428
411.6
425
472.6
486
Fuse rating aM
A
315
315
315
400
400
400
400
400
Содержание 100
Страница 2: ......
Страница 29: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO ...
Страница 45: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO XVII CONTROL pCO1 ...
Страница 46: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO XVIII pCO1 ...
Страница 47: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO XIX pCO1 ...
Страница 48: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO XX pCO1 ...
Страница 49: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO XXI POWER 1P N T P O P H N ...
Страница 50: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO XXII ...
Страница 51: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO XXIII ...
Страница 53: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO XXV 1P N T P O P H N ...
Страница 58: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO XXX ...