background image

3.5 Linear or Square Root Function 

Selection

Model X54-201L provides a display which is a
linear representation of the input, and Model X54-
201SR provides a display which is the square root
function of the input. The square root display
versus the input current can be found as follows:

DISPLAY =    (mA  

4 mA) ÷ 16 mA  × Display 

Range + Display Zero;

Or, 
DISPLAY =  0.25     mA Input – 4 × Display Range

+ Display Zero.

In order to change the X54-201’s function from
linear to square root, or vice versa, the module
must be removed from its enclosure as the
function jumper plugs are located on the bottom
board. The jumpers are located at JP1 and JP2

3.2  Span Selection

Refer to Table 3-1 to obtain the spans shown in
the left column which indicates the positions of
SW1-1 through SW1-5. For example, a span of
2.00, 20.0 or 200, SW1-2 and -5 are set to the ON
position and SW1-1, -3 and -4 are OFF.

3.3  Zero Selection

Table 3-2 indicates which positions of SW2-1
through SW2-6 and S1-6 are set to ON to obtain
the zero offset, in digits, indicated in the columns
directly below the switch. The indicated offsets are
additive, i.e., two or more of the switches may be
set to their ON position to obtain the sum of their
indicated offsets. The display span is located in
the left column, then the offset digits are found in
the same row as the display range. When the
desired offset digits are found, the switch or
switches, at the head of the column(s) should be
set to the ON position.

When changing spans or offsets, the zero and
span controls will need to be fine tuned to obtain
the specified accuracy. See Section 4.0
Calibration, for a procedure to adjust the zero and
span controls.

3.4  Decimal Point Selection

The decimal point position is selected by the
position of the DP-jumper plug located at the
lower left edge of the display board. The jumper
plug can be placed in any one of the following four
positions: 0, 1, 2 or 3, and corresponds to (0) no
decimal point, (1) one digit to the right of the
decimal point, (2) two digits to the right of the
decimal point, or (3) three digits to the right of the
decimal point.

SW1-1

SW1-2

SW1-3 SW1-4

SW1-5

1.00, 10.0, 100

Off

Off

Off

On

On

1.40, 14.0, 140

Off

Off

On

Off

On

2.00, 20.0, 200

Off

On

Off

Off

On

3.00, 30.0, 300

On

Off

Off

Off

On

4.00, 40.0, 400

Off

Off

Off

Off

On

5.00, 50.0, 500

Off

Off

Off

On

Off

7.00, 70.0, 700

Off

Off

On

Off

Off

10.00, 100.0,

Off

On

Off

Off

Off

1000

15.00, 150.0,

On

Off

Off

Off

Off

1500

19.99, 199.9,

Off

Off

Off

Off

Off

1999

Display Spans

Digits ± 20%

Selection of Span Switches, SW 1    

SW2- SW2- SW2- SW2- SW2- SW2- SW1-

1

2

3

4

5

6

6

1.00, 10.0,

5

10

20

40

80

160

60

200

100

*120

1.40, 14.0,

7

14

28

56

110

220

90

275

140

*160

2.00, 20.0,

10

20

40

80

160

320

125 400

200

*240

3.00, 30.0,

15

30

60

120

240

480

190 600

300

*360

4.00, 40.0,

20

40

80

160

300

600

230 760

400

*460

5.00, 50.0,

25

50

100

200

400

800

100 1000

500

*600

7.00, 70.0,

35

70

140

280

560

1120

140 1300

700

*1300

10.00, 100.0, 50

100

200

400

800

N/A

200 1000

1000

*1000

15.00, 150.0, 75

150

300

600

N/A

N/A

300 500

1500

*500

19.99, 199.9, N/A

N/A

N/A

N/A

N/A

N/A

360 N/A

1999

Display

Spans

Digits

± 20%

Max.

Offset

Digits Offset Vs Offset Switches, SW2 and SW1-6

* Equals Square Root Mode.

Note:

Offset of 2 or more switches may be combined.

Table 3-2:

Digits Offset.

JP1 Position

JP2 Position

Jumpered

Jumpered

Linear

1,2

1,3

Square Root

Not used

1,2,3,4

Table 3-3: 

JP1 and JP2 plug positions for selection of linear or square root

function.

3

Table 3-1:

Selection of Span Switches, SW1

Содержание X54-201L

Страница 1: ...Instructions and Operating Manual SERIES X54 201L SR LOOP POWERED INDICATOR ...

Страница 2: ... X54C92 5 X54 201 Panel Mount Assembly 6 X54 201L SR Installation Drawing Using I S Barriers or Explosion Proof Conduit 7 Warranty Ronan warrants equipment of its own manufacture to be free from defects in material and workmanship under normal conditions of use and service and will repair or replace any component found to be defective on its return transportation charges prepaid within one year of...

Страница 3: ...ground Terminals Compression type for wire size up to 14 AWG 3 0 OPERATION 3 1 General Model X54 201 is put into service by connecting it in series with 4 20 mA current loop The connections are made to the two position compression type screw terminal mounted on the lower board and accessible from the top of the module The loop indicator module needs to be removed from the enclosure in order to fee...

Страница 4: ...djust the zero and span controls 3 4 Decimal Point Selection The decimal point position is selected by the position of the DP jumper plug located at the lower left edge of the display board The jumper plug can be placed in any one of the following four positions 0 1 2 or 3 and corresponds to 0 no decimal point 1 one digit to the right of the decimal point 2 two digits to the right of the decimal p...

Страница 5: ... output range and 4 00 mA or set the current using the circuit of Figure 2 to 4 00 mA B Adjust the zero control for the correct span zero display C Repeat Step A using 20 00 mA D Adjust the span control for the correct span full scale display E Repeat Steps A through D until the controls no longer need adjustment 4 2 Square Root Display Model X54 201SR A Set the calibrator to its mA output range a...

Страница 6: ... CAPTIVE SCREW RONAN 6 1 X54B165 1 WIRE ASSY RONAN 7 1 X54B165 2 WIRE ASSY RONAN 8 1 X54B86 1 FRONT PLATE RONAN 9 1 X54B88 BASE PLATE RONAN 10 1 XIHFGCX2LS42311 E P HOUSING ADALET 11 1 600 4 TERMINAL BLOCK KULKA 12 2 6 32 X 0 375 PH PAN HD MS 13 4 8 32 X 0 250 PH PAN HD MS 14 2 4 40 X 1 250 PH FLAT HD MS 15 4 8 INTER TOOTH LKWR 16 1 X54B229 DECAL SET X54 201 Exp Proof Assy DRAWING NUMBER X54C92 RE...

Страница 7: ...G MIDDLE RONAN 4 1 X54B158 MTG RING BOTTOM RONAN 5 2 X54B159 CAPTIVE SCREW RONAN 6 1 X54C119 TERMINAL PLATE RONAN 7 1 X54B86 FRONT PLATE RONAN 8 1 X54B165 3 WIRE ASSY RONAN 9 1 GFTCX 5 TERMINAL BLOCK CURTIS 10 2 TINNERMAN NUT CURTIS 11 1 20 AWG 6 00 IN LG RED UL1429 WIRE 12 1 22 AWG 6 00 IN LG BLK UL1429 WIRE 13 1 6 32 X 0 250 PH PAN HD MS 14 2 4 40 X 1 250 PH FLAT HD MS 15 1 6 INTER TOOTH LKWR 6 ...

Страница 8: ... inductance and the internal inductance Li of each FMRC Approved apparatus installed in the loop Ca The sum of the cable capacitance and the internal capacitance Ci of each FMRC Approved apparatus installed in the loop 3 Maximum safe area voltage should not exceed 250 Vrms 4 De energize supply power before disconnecting loop apparatus 5 Vmax and Imax values do not apply in explosion proof installa...

Страница 9: ... com RONAN ENGINEERING LIMITED U K 1 Tilley Road Crowther Industrial Estate Washington Tyne and Wear United Kingdom NE38 OEA E Mail ronanenguk aol com Ph 191 416 1689 Fx 191 416 5856 RONAN ENGINEERING LIMITED 32 Bermondsey Road Toronto Ontario Canada M4B 1Z5 416 752 0310 FAX 416 752 8072 E Mail ronantor primus ca Printed in U S A X54 201L SR 600 ...

Отзывы: