6-Excursus
15
20
25
30
35
40
45
50
55
22.1(20)
19.6(17.5)
17.1(15)
14.6(12.5)
12.1(10)
9.6(7.5)
7.1(5)
4.6(2.5)
2.1(0)
0
2.5
5
A2
TgA2=-0.5
When the parameter set :
R01=20 R02=2 R03=30 R04=2
R17=-0.5 R18=20 R19=15 R20=20 R31=-0.8,
The compensate graphs in the heating and cooling mode are as follows:
-5
0
5
10
15
20
47.8(50)
43.8(46)
39.8(42)
35.8(38)
31.8(34)
27.8(30)
0
4
5
A1
TgA1=-0.8=R31
Excursus 2 Compensate temperature chart
Heating mode:
starting(stopping) temp.
(℃)
Ambient temp.
(℃)
Cooling mode:
Ambient temp.
(
℃
)
starting(stopping) temp.
(℃)
R19
R20
R03
R01
18
SW1
SW3
SW2
Stand-by interface
OF
SW1
SW3
SW2
Boot-strap interface
45
True termperature
The unit's parameter
Range
Default
P1
P2
15~60
1-5
℃
℃
55
5
Operation instruction:
(1)
When connected to the power supply the first time, in the stand-by mode the screen
show "OF". In the turn-on mode the screen shows the T1 temperarure.
(2)
In the stand-by mode, press the "SW2" or "SW3",enter the parameter list.
(3)
Press the "SW2" or "SW3" could scan the parameter No(P1,P2);
(4)
Then press the"SW1", then the parameter is adjustable.
(5)
Press the "SW2" or "SW3" adjust the parameter value.
(6)
Press the "SW1" to confirm the adjusted parameter.Press the button "SW1" for 5
seconds
and save the parameter.
(7)
5 secconds later,the screen will come back to the original mode "OF"
Par
Unit
P1: set temperature
P2: set return difference
Malfunction protection
When the T1 is shor circuit or open circuit,the switch output is off,
and the screen show P1.
7-Super heat controller