RS-500 WIC, RS-500M, and RS-600M Door Training Guide 

Section 5: Program Parameters 

Parameter 

Definition 

Default Value 

P1 

Close Time Delay (Seconds) 

20 

P3 

Deceleration Range 

P4 

Warning Output Function 

0 – Door Movement/About to Close 

0 – Door Movement/About to Close 

1 – Sequential Interlock 

2 – Passive Interlock 

3 – Door Open Indication 

4 – Door Closed Indication 

P7 

Refresh Door Limits 

25 

P10 

Service Cycle Reset 

No 

0 – No 

1 – Yes 

P11 

Service Reminder (Cycles x 100) 

240 

P12 

Input Status 

P20 

Open Input Function 

0 (Timed Open) 

P21 

Input Switch Response 

0 (Momentary) 

P22 (RS-500 WIC Door Only) 

Auxiliary Safety Response 

1 (Enabled) 

P23 

Encoder Operation 

0 (2 Channels) 

P24 

CMS Output Function 

P25 

CMS On-Time 

15 (If P24=0) 

P26 

CMS Off-Time 

10 (If P24=0) 

PS1 

Setup Door Limits 

PS2 

Set Open Limit 

PS3 

Set Close Limit 

 

Section 6: Setting Limits 

PS1 – Change Program Limits:

 This can be set to Yes or No. To change the Open Limit (PS2) or Closed Limit (PS3), set PS1 to Yes, 

then press the Mode button. To exit programming mode, set PS1 to No and press the Mode button. 

PS2 – Set Open Limit:

 When the Mode button is pressed after PS1 has been set, the door will open to the Home switch 

position, then proceed toward the Open limit. Use the Up and Down arrows to set the door to a new Open limit, then press the 

Mode button to proceed to the next parameter. 

PS3 – Set Close Limit:

 When the Mode button is pressed after the Open limit has been set, the door will close to the current 

setting of the Closed limit. Use the Up and Down arrows to set the new Closed limit, then press the Mode button to exit 

programming mode and resume displaying the Actual Position. 

 

 

Содержание RS-500 WIC

Страница 1: ...aining Guide NOTICE If you encounter any issues that cannot be resolved using the information in this document contact RollSeal at 1 888 765 5732 Section 1 Comparison of RS 500 Walk In Cooler WIC Door...

Страница 2: ...4802 7536C 2 15 November 2021 RS 500 WIC RS 500M and RS 600M Door Training Guide Section 3 Door Wiring Diagrams 3 1 RS 500 WIC Door...

Страница 3: ...4802 7536C 3 15 November 2021 RS 500 WIC RS 500M and RS 600M Door Training Guide 3 2 RS 500M RS 600M Door...

Страница 4: ...r 5 seconds to disengage Jog Mode The controller will return to normal operating mode and the display will show the Actual Position The controller will not know the door s exact position so it will di...

Страница 5: ...5 If P24 0 P26 CMS Off Time 10 If P24 0 PS1 Setup Door Limits PS2 Set Open Limit PS3 Set Close Limit Section 6 Setting Limits PS1 Change Program Limits This can be set to Yes or No To change the Open...

Страница 6: ...Closing Over Speed Fault FE RS 500M RS 600M Door Code Condition Panel Movement Problem Area Recommended Action s EO1 Opening Home Switch Tripped Home Switch Check wiring Ensure Home switch arm is ful...

Страница 7: ...d determine whether the door will jog If the door jogs the door assembly brake relay is defective If the door does not jog contact RollSeal 1 888 765 5732 while remaining at the door o If the door jog...

Страница 8: ...00 WIC doors and RS 500M RS 600M doors RS 500 WIC doors use a FLY sensor as an auxiliary safety RS 500M RS 600M doors use an egress strap as an auxiliary safety 1 If the switch lights up but does not...

Страница 9: ...ondition Possible Cause s Solid Green Slowly Flashing Green Operation is normal N A Quickly Flashing Green Current is over load Drive is operating between 120 and 200 of rated load Slowly Flashing Red...

Страница 10: ...turn fan is not operational Supply Fan L ON Green The supply fan is running at the designated RPM Supply Fan L FAIL Red The supply fan is not operational Heat ON Green At least one of the two fans is...

Отзывы: