Appendix A Troubleshooting 

PROBLEM 

POSSIBLE CAUSE 

ACTION TO TAKE 

Power switch not pushed or 

push-time too short 

Press the power switch more 

than 1 second 

Battery voltage less than 20V 

Recharge the UPS at least 24

 

hours 

PCB failure 

Replace the PCB, call for 

service 

UPS can not turn on LED not 

light 
 

Load less than 30W at battery 

mode 

Normal condition, “No load 

shutdown function” is active 
(See 3.2) 

Power cord lose 

Plug in the power cord   

AC fuse burn out 

Replace the AC fuse or 

Breaker 

Line voltage too high, too low or 

black out 

Normal condition 

UPS always at battery mode 

PCB failure   

Replace PCB, call for service 

battery not fully charged 

Recharge the UPS at least 24 

hours 

Back up time too short 

PCB failure 

Replace PCB, call for service 

Buzzer continuous beeping 

Overload 

Remove some loads 

 

Appendix B Specifications 

Model 

1000A/AP  1200A/AP  1500A/AP  2000A/AP  3000A/AP 

Capacity 

1000VA 

1200VA 

1500VA 

2000VA 

3000VA 

Voltage 

110V, 115V, 120V/

 

220V, 230V, 240V, +/-25% at line input 

(3000A/AP Only for 220V 230V 240V) 

Input 

Frequency 

50 or 60Hz +/- 10% (auto sensing) 

Voltage (Backup mode) 

Simulated sine wave like rating voltage, +/-5% 

Frequency (Backup 

Mode) 

50 or 60Hz +/- 1Hz 

Output 

Auto Voltage 
Regulation (AVR) 

AVR automatically increase output voltage 15% above input 

voltage if -9% to-25% of nominal. AVR decrease output 

voltage 13% below input voltage if+9% to +25% of nominal 

- 8 - 

 

Transfer Time 

4 milliseconds (typical) 

Spike Protection 

280Joules (2X0 V) / 1185Joules (1X0 V) 8/20us

 

Unit Input 

Fuse or circuit breaker for overload & short circuit protection 

Overload Protection 

UPS automatic power off if overload exceeds 110% of 

nominal at 60s and 130% at 3s 

10 Base-T Cable Port 

Optional/YES 

Protection and 

Filtering 

Short Circuit 

UPS output cut off immediately or input fuse protection 

Type 

Sealed, maintenance-free lead acid batteries with 3-6years 

typical lifetime 

Typical Recharge Time 

6 hours (to 90% of full capacity) 

Protection 

Auto discharge protection 

Battery 

Back up Time (PC with 

15” LCD monitor) 

50

 min 

55

 min 

60

 min 

6

5 min 

90min 

Net Weight Kg(lbs) 

13.4 (28.6)  13.4 (28.6)  13.6 (30.0)  14.5 (31.9)  22.0(48.5)

Shipping Weight Kg 

(lbs) 

14.8 (32.6)  14.8 (32.6)  15.0 (33.0)  15.9 (35.0)  23.4(51.5)

130 x 382 x 200 (5.1” x 15.0” x 7.9”)

Dimension (mm) 
W x D x H 

130 x 438 x 200 (5.1” x 17.2” x 7.9”) (3000A/AP)

Input Inlet 

IEC 320 power inlet 

Physical 

Receptacles 

NEMA5-15R (115V), IEC320 female appliance coupler 

(220V) 

Battery Back-Up 

Slow beeping sound (about 0.47Hz) 

Battery Low 

Rapid beeping sound (about 1.824Hz) 

Alarm 

Overload 

Continuously beeping sound 

Interface 

(Free software)  RS-232 or USB 

NO/YES 

Ambient Operation 

3,500 meters max. elevation, 0-95% humidity 

non-condensing, 0-30

 

Audible Noise 

<40dBA (1 meter from surfac

<50dBA

e) 

Environment 

Storage Condition 

15,000 meters max. 

 

 

 

 

 

 

©