C. Low Voltage DC can be used to turn the

control 

ON

 and 

OFF.

  Move jumper "J1" from

terminal 7, to terminal 5, (6 remains the
same).

Connect a +5 to 30VDC (10mA) signal to
terminal 12 and the reference (GND) to
terminal 11 of TB2.  The control will now turn

ON

 when the DC signal is present at terminals

11 and 12 of TB2.  This input is optically
isolated. Refer to Section C of the OFF/ON
CONTROL GUIDE.

D. AC Voltage may be used to turn the control

ON

 and 

OFF

.  This requires a 105-250VAC

signal, with 2mA leakage maximum.  Set up
the control by moving the jumper "J1" from
terminal 7, to terminal 5, (6 remains the
same).  Connect the 105-250VAC Signal to
terminal 12 (L1) and the common (L2) to
terminal 10 of TB2.  The FC-40 control will
now turn 

ON

 whenever the AC signal is

applied to terminals 10 and 12 of TB2. This
input is optically isolated.  Refer to Section D
of the OFF/ON CONTROL GUIDE.

TB-2 terminals 5-7 are transformer isolated from
the line voltage circuit.

4.  MAIN CONTROL DIAL

The output power is controlled by the 

MAIN

CONTROL DIAL

.  A special logarithmic-tapered

power out curve (non-linear) spreads the power
broadly across the 

MAIN CONTROL DIAL

 to help

give maximum "Fine Control" over the output
speed of the vibratory feeder. 

5. SETTING THE SOFT-START

The start-up of the control output can be adjusted
to ramp up to the desired output level instead of
starting abruptly. This keeps parts from falling off
the tooling of a vibratory feeder when it turns on; it
can reduce hammering during turn on; it can also
simulate a paddle switch ON delay.  Adjust the

SOFT

 Start trimpot clockwise for the gentlest start

(about a 10-second ramp up to full output).  Turn
the trimpot fully counter-clockwise for no soft start.

6. LINE VOLTAGE COMPENSATION

Fluctuations in the line Voltage can cause a feeder
bowl to vary its feed rate.  The line voltage
compensation feature adjusts the control's output
to help compensate for fluctuations in the supply
voltage. If it becomes necessary to disable this
feature, remove resistor R4 from the bottom of the
board with a pair of pliers, twist R4 to snap it off.

  

7.  REMOTE SPEED CONTROL

Remote control of the power signal level can be
accomplished by the following methods:

A.   0-5VDC Analog input signal may be applied in

place of the Main Control Dial.   For further
information, contact  RODIX.

B. 4-20mA signal from a PLC can be used to

remotely vary the output of the control instead
of the Main Control Dial.  This feature is
automatically turned on whenever a 4-20mA
signal is applied to the control.  To return
control to the Main Control Dial, remove the 4-
20mA signal by turning it off or use a switch to
open the circuit.  The 4-20mA input is
transformer isolated from the power line.

C.   Remote control of the output power level can

be accomplished by using an optional 

Step

Up/Down Remote Speed Interface P/N 123-
148

WARNING:

Fuses should be replaced with Littelfuse 3AB
"Fast Acting" type or equivalent of
manufacturer's original value.

Mounting this control on a vibrating surface
will void the warranty.

WARRANTY

Rodix Control Products are Warranted to be
free from defects in material and workmanship
under normal use for a period of two years
from date of shipment.  

For the full description of

the warranty, terms, and software license, please
contact the factory.

For assistance installing or operating your Rodix
Control please call the factory.  Technical help is
available to answer your questions and Fax any
needed information.  To return a control for IN or
OUT of Warranty Service, please ship it prepaid
to:

Rodix Inc.,  ATTN: Repair Department

If under Warranty, Rodix will repair or replace your
control at no charge; If out of Warranty, we will
repair it and you will be billed for the repair charges
(Time and Material) plus the return freight.  Quotes
for repairs are available upon request.  A brief note
describing the symptoms is appreciated by our
Technicians.