6. FEATURE PROGRAMMING CHART
“
X
” means the setting could be in either position
because the position doesn’t matter.
“
0
” means the “resistor” jumper has been removed.
7. LOW VOLTAGE AT “1”
Some small feeders may feed faster than desired at low
settings on the dial. The “Low Voltage at 1” program
allows the control’s output to operate at a much lower
minimum voltage than the standard minimum voltage.
To enable this feature break through resistor R25 with a
knife.
TROUBLESHOOTING
For the control to run: The
AMPLITUDE POT
must be
turned up and the RUN LED must be lit. To light the
RUN LED, connect a Run Jumper from TB2 terminal
3 to 4, or apply a 10-30 VDC signal at TB2 terminals 1
& 2. See the “FC-70 Troubleshooting Guide” for more
information. If the feeder only hums or barely moves
parts, toggle the 60/120 dip switch to match the
feeder’s tuning.
DIMENSIONS
WARNING:
Fuses should be replaced with a Bussman ABC
or Littelfuse 3AB "Fast Acting" type or
equivalent of manufacturer's original value.
Mounting this control on a vibrating surface will
void the warranty.
WARRANTY
Rodix Control Products are Warranted to be free from
defects in material and workmanship under normal use
for a period of two years from date of shipment.
For the
full description of the warranty, terms, and software license,
please contact the factory.
For assistance installing or operating your Rdix Feeder
Cube® please call the factory or visit our web site.
Technical help is available to answer your questions and
email any needed information. To return a control for IN or
OUT of warranty service, please ship it prepaid to:
Rodix Inc., ATTN: Repair Department
If under warranty, Rodix will repair or replace your control at
no charge; If out of warranty, we will repair it and you will be
billed for the repair charges (Time and Material) plus the
return freight. Quotes for repairs are available upon
request. A brief note describing the symptoms helps our
technicians address the issue.
Feeder Cube® is a registered TM of Rodix Inc.
RODIX, INC.
2316 23
rd
Ave., Rockford, IL 61104
Toll Free (800) 562-1868, FAX (815) 316-4701
E-mail [email protected]
www.rodix.com
FC-70 24-214.doc 2/13/2015 Page 2
Feature Programming Chart
Program Description
SW1 R24 R25
Standard Program
X
1
1
60 Pulse Reverse
60
0
X
40 Pulse Operation
120
0
X
Low Voltage at “1”
X
X
0